August 2021 Ventilation Standards 0 Ventilation rate measure is the air change rate (or air changes per hour): the hourly ventilation rate divided by the volume of the space (I or ACH; units of 1/h).
0 ANSI/ASHRAE Standards 62.1 and 62.2 are the
recognized standards for ventilation system design and acceptable indoor air quality (IAQ).
0 Both standards specify minimum ventilation rates and other
measures in order to minimize adverse health effects for occupants. Purpose of ventilation Standards
0 To specify minimum ventilation rates and other measures
intended to provide indoor air quality that is acceptable to human occupants and that minimizes adverse health effects.
0 This standard is intended for regulatory application to new
buildings, additions to existing buildings, and those changes to existing buildings that are identified in the body of the standard.
0 This standard is intended to be used to guide the improvement
of indoor air quality in existing buildings. SCOPE 0 applies to spaces intended for human occupancy within buildings. 0 This standard defines requirements for ventilation and air-cleaning-system design, installation, commissioning, and operation and maintenance. 0 Additional requirements for laboratory, industrial, health care, and other spaces may be dictated by workplace and other standards, as well as by the processes occurring within the space. Standard values Standard values Standard values Sample calculation of ventilation requirement 0 For a lecture classroom of 1000sq.ft floor area and 50 students
0 Cfm required = (cfm /person )*no of person
+(cfm/sq.ft)* floor area =7.5*50 +0.06*1000 = 435 cfm ACPH = (CFM *60)/(Area *Height) = (435*60)/(1000*10) = 2.61 ACPH It means that entire room air needs to changed 2.61 times in one hour for optimum indoor air quality.