Professional Documents
Culture Documents
1) PROJECT REPORT:
- Project statement (introduction) 2 pages
Explain what are you designing/analyzing and why is that important
On the second page clearly identify (bullet list) project outcomes
- Building description (geometry) 1-3 pages
Schematics that focus on your system(s)
Identify all assumptions and simplifications you introduced
- Methodology 1-3 pages
Describe methodology (equations, schematics, …)
Provide a list of assumptions used in your methodology
- Results 3-5 pages
Formatted results with comments
Tables, Charts, Diagrams, …
Analysis and Results discussion
- Conclusion 0.5-1 page
Summary of most important results
2) PRESENTATION:
- 5 minutes (exactly)
-Power point presentation (4-6 slides)
GRADING CRITERIA:
1) Analysis approach: 60%
- Methodology 20%
- Accuracy analysis 20%
- Result analysis 20%
2) Deliverables: 40%
- Final report 30%
- Presentations 10%
Sequence of operation for the
control system design
Adiabatic
CC humidifier HC
OA SA
mixing
RA
Define the sequence of operation for:
WINTER operation and:
- case when humidity is not controlled
- case when humidity is precisely controlled
Solution on the whiteboard
Economizer
% fresh air
Fresh air volume flow rate control
enthalpy 100%
Fresh
(outdoor) TOA (hOA) Minimum for
damper air ventilation
mixing
Recirc.
air
T & RH sensors
Economizer – cooling regime
If TOA < Tset-point open the fresh air damper the maximum position
Then, if Tindoor air < Tset-point start closing the cooling coil valve
If cooling coil valve is closed and T indoor air < Tset-point start closing the
damper
till you get T indoor air = T set-point
Sensor
Measures quantity of
interest
Controller
Interprets sensor
data
Controlled device
Changes based on
controller output Figure 2-13
outdoor
Direct Indirect
Closed Loop or Feedback Open Loop or Feedforward
Set Point
Desired sensor value
Control Point
Current sensor value
Error or Offset
Difference between control point and set point
Two-Position Control Systems
Cooling coil
air
x
water
Position (x)
fluid
K
x A K (Tset point Tmeasured ) (Tset point Tmeasured )d
Ti
If controller is tuned
properly, offset is
reduced to zero
Figure 2-18a
Issues with PI Controllers
Scheduling issues
Require more tuning than for P
But, no offset
Proportional + Integral +
Derivative (PID)
Improvement over PI because of faster response and less deviation from offset
Increases rate of error correction as errors get larger
But
HVAC controlled devices are too slow responding
Requires setting three different gains
Ref: Kreider and Rabl.Figure 12.5
The control in HVAC system – only PI
K
x K (Tset point Tmeasured )
Ti (Tset point Tmeasured )d
Proportional Integral
value
Set point
Proportional
affect the slope