You are on page 1of 10

Introduction to ProsafeRS

YOKOGAWA Safety System


ProsafeRS is the Safety System of YOKOGAWA

What is a safety system ?

?
A safety system is an Independent system that leads to a
Predetermined safe state in case that the process
runs out of control
What is a meant by an Independent system ?

SIF LOOP
System Architecture
This is how a Prosafe looks in the Cabinet

Safety control Unit (SCU) or Node1

ESB redundant module for inter domain communication

SCU FAN unit

KS1 cables
Note:
in this System, all the I/O
Node 2 cards are connected to the
terminal boards in each
marshalling cabinet via
dedicated KS1 cables

Node 3
Redundancy
• All hardware should be redundant in a safety system.
• Different hardware topologies (i.e. 1oo2, 1oo3) are used in field Instruments to achieve safety and availability
• In ProsafeRS- CPU, PSU, I/O modules, even Network will be Redundant
• In Vnet-IP, 2 different network system Bus1 & Bus2 will be utilized for redundancy

SIL certification (Safety Integrity Level)


• The most important standards for functional safety are IEC 61508 & 61511
• All hardware should be safety certified, that includes field instruments also .
• SIL certification is given by TUV.
• Prosafe can support up to SIL 4, However it depends on the Demand rate, Consequences etc
• SIL level can predict Average Probability of failure on demand(PFD)

SIL Level Average probability of failure on demand Risk reduction factor (1/PFD)
4 < >10000
3 ≥ 1000-10000
2 ≥ 100-1000
1 ≥ 10-100
Redundancy for Sensor Redundancy for final elements
Difference between normal PLC/DCS and Safety System(ProsafeRS)

Normal PLC/DCS Safety PLC


High flexibility needed to develop and maintain Fixed functionality, carefully minimized during design
(complex) control and automation applications
Configuration changes can be done Online Complex procedure are Involved in making any
changes
During the failure of the control system, state of Output states are predictable during the functional
outputs are unpredictable failure of the system
Regular testing is not required except for some Complex procedures are followed to test the system
backup/ redundant parts hardware
Control system Runs 24/7 all the time Safety system is always on Hot standby

Not a fail safe design Fail safe Design


Introduction to the Software

Prosafe-RS Workbench is the software program used to


configure the Prosafe system, the software also provides the user
with the ability to:

• Edit a Project
• View and Update Variables
• Perform Trouble shooting
• Produce documentation

The Languages are available for configuring the Prosafe-RS


system:

1. Functional Block diagram


2. Ladder
3. Structure Text