Professional Documents
Culture Documents
Correction
Correction
Average Fresh air requirement per person per second is 8 ltrs (Standard breathing rate)
Based on ASHRAE standards, ideal ventilation rates for building space is expressed as:
Design airflow rate per unit area (cfm per square foot)
Design airflow rate based on occupancy (cfm per person)
Vbz = Rp · Pz + Ra · Az
Vbz – Air Vol requirements for breathing zone
Az = zone floor area (the net occupiable floor area of the ventilation zone in sqft/sqm)
Pz = zone population
Rp = outdoor airflow rate required per person as determined from ASHRAE Table 6-1
Ra = outdoor airflow rate required per unit area as determined from ASHRAETable 6-1
Example
Consider
A Restaurant (Building Type)
of Floor Area 3000 sqft
Design Occupancy of 100 pers
It is then divided by the Zone Air Distribution Effectiveness, to obtain the Zone
Outdoor Airflow that must be supplied by the ventilation system. If the distribution
effectiveness for the example above is 0.8,
the zone outdoor airflow must be 1540 cfm / 0.8 = 1925 cfm.