Professional Documents
Culture Documents
03-Earth FAult and FAult Resistance - New
03-Earth FAult and FAult Resistance - New
Fault Resistance
Power Transmission
and Distribution
©
Siemens AG 2006
Distance protection: Earth fault in system with solid, isolated or
compensated system neutral earthing
D A B C
ZT Z2...
Z1
G
D
Neutral Earthing :
Peterson Coil or Isolated or Solid
IE RE + j XE
L1
ret to remote
Rret Xret(Lret) line end
Infeed L3
Ufwd Uret
E
U L2 - U L3
RL2 - L3 = Re
I L2 - I L3
U L2 - U L3
ZL2 - L3 =
I L2 - I L3 U L2 - U L3
XL2 - L3 = Im
I L2 - I L3
©
Siemens AG 2006
Page 7 TLQ 2004 Distance Protection – Earth Faults and fault resistance Power Transmission and Distribution
Numeric impedance-calculation, Ph-E-loop (1)
L RL XL
L1
L2
G
L3
Uph-E RE XE
Z E
U Ph E I L Z L IE ZE Z I I E
L L
Z L
L RL XL
L1
L2
G
L3
Uph-E RE XE
ZL ZPh-E
UPh - E = IL ZL + ZE + RF IL assume IL - IE
ZE
1+
UPh - E ZL RF
ZPh - E = ZL +
IL kE IE 1 + kE 1 + kE R
ZE RF RF
If kE setting adapted to , then ZPh - E ZL ZL
ZL ZE ZE j(E-L)
1 1 e
ZL ZL
RF
UPh-E K RF
E X 1+kE,R
XE RE
EA A ZL B EB
D A RF B
UA
X
U A = I A ZL + I A + IB RF
U A = I A ZL + RF + IB RF RF B
RF
A
UA IB ZL
ZA = = ZL + RF + RF
IA IA
R
©
Siemens AG 2006
Page 12 TLQ 2004 Distance Protection – Earth Faults and fault resistance Power Transmission and Distribution
Fault locating:
distance-to-fault measurement with arc compensation
lF
ZL
USC ISC RF
RF
X Measurement of
ZL the Reactance
gives the best
ZSC ZSC sin SC
accuracy
(USC)
SC ISC R
USC
XSC= K sin SC = ZSC ·sin SC
ISC
©
Siemens AG 2006
Page 13 TLQ 2004 Distance Protection – Earth Faults and fault resistance Power Transmission and Distribution
Short-circuit with arc resistance and double-sided in-feed,
influence on distance measurement
I1 I2
ZL1 ZL2
= I1+I2 - I1
U1
X
UARC
The phase angle difference between the two sources (load influence)
causes an additional error in the measured reactance (see angle )
©
Siemens AG 2006
Page 14 TLQ 2004 Distance Protection – Earth Faults and fault resistance Power Transmission and Distribution
Influence of load flow on the distance
measurement for faults with fault resistance
U1 U2
load
L
ZL1 ZL2 SC2
SC1 1
U1 RF U2
1 2
RF = fault resistance 2
1
2 R
RF RF 2 F
1 RF X
X
ZL1 ZL2 An Over-reach
ZSC2 (left) or
ZSC1 ZSC2 sinSC2
ZSC1 sinSC1 an Under -reach
(right) is possible.
The grading
SC1 SC2
characteristic must
R R be adapted.
2 1
ZK1 = ZL1 + RF + R ZK2 = ZL1 + RF + RF
1 F 2
Siemens AG 2006
©
Page 15 TLQ 2004 Distance Protection – Earth Faults and fault resistance Power Transmission and Distribution
Estimation of arc resistance
28700
Worrington formula: R ARC lm Ohm
IA 1,4
Rough
2500 V/m dm
estimation: R ARC Ohm
UARC = 2500 V/m I F A
Phase-to-phase distances
d= 3,5 m (110 kV)
X Variable d= 7 m (220 kV)
R/X-setting d= 11 m (380 kV)
Insulator lengths (long-rod insulator)
©
Siemens AG 2006
Page 16 TLQ 2004 Distance Protection – Earth Faults and fault resistance Power Transmission and Distribution
Ph-PH-E short-circuit with fault resistances,
Measured loop impedances depending on fault location
D
1 1
L2-L3-E
4
100 % L2-L3
L2-E
In the case of multiple earth-faults
with fault resistances, complex 50 %
conditions arise for the distance
RTower measurement.
R
A special logic for loop selection is required
(blocking of leading phase (L2-E) to prevent an over-reach)
©
Siemens AG 2006
Page 17 TLQ 2004 Distance Protection – Earth Faults and fault resistance Power Transmission and Distribution
Loop impedances during Ph-Ph-E short-circuit,
depending on fault resistance to earth and load conditions
742 MW
RE
lagging
phase 10 150 RPh = 0
5
15
RE
20
2 RE (Ohm)
30 100
0 2 40 The impedance of the
40 5 10 20 -742 MW leading phase is seen
-742 MW to be too short.
742 MW
leading
phase Phase-Phase loop is
50
nearly measured correctly
(small X-error)
50 100 X (Ohm) ©
Siemens AG 2006
Page 18 TLQ 2004 Distance Protection – Earth Faults and fault resistance Power Transmission and Distribution
Effective arc resistance „seen“ by the distance relay
with double-sided in-feed (example)
A = 1 kA B U A = I A ZL + U ARC
UA U ARC
D 6m RARC ZA = = ZL +
IA IA
RARC iARC
with constant
15 arc voltage uARC
UARC = 2500 V/m
10
with current dependent
arc voltage
5 28 700
RLB = Ohm/m ARC in A
ARC1.4
2 4 6 8 10 kA B
The rate of arc resistance reducing is greater,
if the current increasing is considered
©
Siemens AG 2006
Page 19 TLQ 2004 Distance Protection – Earth Faults and fault resistance Power Transmission and Distribution
Resultant fault resistance on overhead lines with
earth-wire
IPh phase-
conductors
IE''
earthing
earth-wire(s)
resistance
of the station
R R R R R R R R R
tower footing
resistances
IE'
tower currents
RF 1 + 2
D
2
ZF = ZL + RF + RF
1
load
• High arc compensation even with
short lines
R
X X- and R-reach separately
settable at all zones