You are on page 1of 7

SIPROTEC 5/

DIGSI 5 BASIC-Course
02 Basic function of SIPROTEC 5
www.siemens.com/poweracademy Copyright © Siemens AG 2012. All rights reserved.
Basic function of SIPROTEC 5

SIPROTEC 5

Protection 21 87L 50 51 50BF 25 79

Measurement Q cos φ A max


A V f P
Metering
+kWh -kWh

Copyright © Siemens AG 2012. All rights reserved.


Self Monitoring SW HW ∑ I=0
Feeder Monitoring SF6 loss Pick up CB Live time
Control Local Remode SLD
Data Acquisition Trip log Status log Alarm log
Current iL2/-4
-2
2
0
A -0,4 -0,3 -0,2 -0,1 -0,0 0,1 0,2 0,3 0,4 0,5 t/s

Fault Recording

Automation-Logic Bay Interlocking Sequences


Time Synchronization GPS IRIG B DCF 77 IEC 103
Communication IEC 103 IEC 61850 GOOSE
Security Safe CT Interlock Passwort
Test BI BO Interfase I-Simulation

02 Basic function of SIPROTEC 5


Version: D_03_Page 2 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5 Protection Application

SIPROTEC 5

Protection  SIPROTEC 5 includes all protection functions for transmission and subtransmission
networks
Measurement

Metering  SIPROTEC 5 is applicable for different substation designs


 Single, double and triple busbar designs

Copyright © Siemens AG 2012. All rights reserved.


Self Monitoring
 1,5 CB schemes, ….
Feeder Monitoring
 Application templates are available for different schemes
Control
 Pre configuration reduces the engineering efforts
Data Acquisition  User defined standards leads simplification and repeatability
 Copying of functions and setting between the devices
Fault Recording

Automation-Logic  The library concept increases the flexibility


 Required functions can easily be loaded into the device
Time Synchronization
 A wide range of proven protection functions are available
Communication  Possible extensions are made simple (add stages, zones,..)

Security
 A clear functional structure (function groups) clusters the functions, allows flexible
Test applications and guarantees correct operation

02 Basic function of SIPROTEC 5


Version: D_03_Page 3 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5 Control and Automation

SIPROTEC 5

SIPROTEC 5 includes all functions for Control and Automation of transmission


Protection
and subtransmission networks
Measurement
CFC (continuous function chart) includes all elements for interlocking
Metering  Local control on the device
 Remote control through DIGSI

Copyright © Siemens AG 2012. All rights reserved.


Self Monitoring
 Remote control from the SSA through serial interface
Feeder Monitoring
Application templates are available with predefined interlocking
Control  Pre configuration reduces the engineering efforts
 User defined standardization
Data Acquisition

Fault Recording Complete Station interlocking through IEC61850 and GOOSE

Automation-Logic Automation solutions


Time Synchronization
 Tap changer control
 Intelligent load shedding (active power + frequency)
Communication  Network changeover, stability supervision
 Management of distributed generation in Smart Grid plants
Security

Test

02 Basic function of SIPROTEC 5


Version: D_03_Page 4 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5 Monitoring

SIPROTEC 5

Protection SIPROTEC 5 includes all functions for effective monitoring of transmission


and subtransmission network
Measurement

Metering Self supervision


 All internal hardware components and external interfaces, runtime of software

Copyright © Siemens AG 2012. All rights reserved.


Self Monitoring
 Clear text indication (cause of failure and countermeasure)
Feeder Monitoring
Monitoring of primary equipment
Control
 Operational log records process data with a time stamp (up to 2000 events)
Data Acquisition  Monitoring of the system through measurement supervision (voltage and frequency, power
and load) and through measuring transducer (analogue 4 to 20 mA ) inputs
Fault Recording
(SF6 loss, gas pressure, temperature,…)
Automation-Logic
Powerful fault analysis
Time Synchronization
 Fault recording with a high sampling rate and a long period (8 kHz & 20s or 1 kHz & 160 s)
Communication  Trip log with 1 ms resolution and up to 1000 events

Security

Test

02 Basic function of SIPROTEC 5


Version: D_03_Page 5 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5 Communication

SIPROTEC 5

Netzleitstelle
Protection
 Redundant interfacing to control center,
Measurement e.g. with DNP3, (black)

Metering
SICAM PAS SICAM PAS • Connection to both substation systems

Copyright © Siemens AG 2012. All rights reserved.


Self Monitoring
• IEC 61850 (blue)

Feeder Monitoring
 IEC 60870-5-103 (rot)

Control SIPROTEC 5 SIPROTEC 5


 Separate connection to field level for

Data Acquisition GOOSE communication IEC 61850 (grün)

Fault Recording

Automation-Logic  Separate connection to DIGSI 5 – PC with

Ethernet IEC 61850


Time Synchronization

Communication

Security

Test
DIGSI 5

02 Basic function of SIPROTEC 5


Version: D_03_Page 6 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course
SIPROTEC 5 Communication

SIPROTEC 5

Protection
SIPROTEC 5 includes powerful communication functionality
Measurement  Flexible communication modules  standard hardware components (physical hardware is independent
of software)
Metering  Support of standard communication protocols
 IEC 61850; IEC 60870-5-103
 DNPi 3.0,….

Copyright © Siemens AG 2012. All rights reserved.


Self Monitoring
 Flexible communication solutions are possible
Feeder Monitoring  Double 103 protocol
 Redundant topologies with SSA
Control  Powerful protection data interface (for differential protection, data exchange in substation, DIGSI 5
communication)
Data Acquisition
Communication is the key feature of all applications
Fault Recording  Smart grid means flexibility in communication

Automation-Logic SIPROTEC 5 supports Cyber Security requirements


 Present standards are fulfilled (NERC CIP, BDEW,…)
Time Synchronization
 DIGSI 5 communication with encryption and strong password access
Communication

Security

Test

02 Basic function of SIPROTEC 5


Version: D_03_Page 7 Siemens Power Academy TD
SIPROTEC 5/ DIGSI 5 Basic Course

You might also like