Professional Documents
Culture Documents
Circuit Breaker Testing - New Approach: Thomas Renaudin
Circuit Breaker Testing - New Approach: Thomas Renaudin
Circuit Breaker Testing - New Approach: Thomas Renaudin
Thomas Renaudin
SEEEI conference
*
Circuit Breaker Testing
© OMICRON Page 2
Definition of Circuit Breaker
closed open
R=0Ω R = ∞Ω
© OMICRON Page 3
Purpose of Circuit Breakers in Power Systems
Network
> Minimize losses in closed position
x Circuit Breaker
> Open and close on command
Busbar
>Open or close a circuit to connect
the power to/from the transmission
Disconnector
line
(O - break, C - make)
>Open a circuit for planned x Circuit Breaker
maintenance (O - break)
>Open a circuit at system fault to Power
protect the system behind the Transformer
© OMICRON Page 5
Circuit Breaker Components
A: interrupter chamber
B: insulated support column
C: support structure
D: central cubical
E: wiring
F: operating mechanism
Source: Siemens
© OMICRON Page 6
Standards – ANSI
> C37.04-1999
> Standard ratings defined
> C37.06-2000
> Schedule of preferred ratings
> C37.09-1999
> Type tests
> Routine tests
© OMICRON Page 7
Standards – IEC
> IEC 62271-100, 2001
> Type, routine & field tests
> Timing definitions
> Guide for selection and
specification
© OMICRON Page 8
IEC - timing definition
© OMICRON Page 9
Circuit Breaker Testing
© OMICRON Page 10
What is usually needed to test breakers
© OMICRON Page 11
Typical tests on circuit breakers
© OMICRON Page 12
1. Minimum Pick-up Test
© OMICRON Page 13
1. Minimum Pick-up Test
© OMICRON Page 14
2. Contact Resistance Test
Conventional Setup
© OMICRON Page 15
2. Contact Resistance Test
© OMICRON Page 16
3a. Timing Test
> Connect to all main contacts
> Connect to trip & close coil
> Voltage supply required
Conventional Setup
Time-consuming and
error-prone
© OMICRON Page 17
3a. Timing Test - Measured Values
Open Time, Close Time, Contact Spread, Phase Spread, Trip-Free Time, Reclose Time
© OMICRON Page 18
3b. Timing undervoltage condition
> Coils are normally driven by station battery
> What happens if battery condition is not the best
> Perform a test with reduced supply voltage (e.g. 80
%)
> Check times for under voltage
> does it work anyhow
> are there any delays compared to nominal voltage?
> Measure the overall times and compare to
manufacturer values
© OMICRON Page 19
3c. Coil Current
> Important tool in circuit breaker analysis
> Detect potential problems in actuating coils
> Reveal information on power supply
> Comparison is best method of analysis
© OMICRON Page 20
4. Motor Current
© OMICRON Page 21
5. Contact Travel
© OMICRON Page 23
6. Dynamic Resistance Measurement (DRM)
© OMICRON Page 24
6. Dynamic Resistance Measurement (DRM)
Use DRM to find out
> Problems with contact fingers
> Lubrication problems
> The arcing contact length
© OMICRON Page 25
6. DRM Diagnosis: arcing contact length
main contact
motion
dynamic resistance
coil current
ms
© OMICRON Page 26
Circuit Breaker Testing
© OMICRON Page 27
Conventional Setup for Circuit Breaker Testing
© OMICRON Page 28
CIBANO 500 – 3-in-1 Test System
> Timing analyzer
> Possible operations: O, C, CO, OC, O-CO, CO-CO, O-CO-CO
> Motion measurement is possible in parrallel
© OMICRON Page 29
CIBANO 500 – one system for all types of breakers
© OMICRON Page 30
Unique connection concept
CB MC2
© OMICRON Page 31
Modular concept for simplified testing –
Main Contact Module CB MC2
> 2 high-current outputs and 2 sensitive voltage
measurement channels
> Keeps high-current cables as short as possible
> minimizing the weight of the necessary cables
© OMICRON Page 32
Unique connection concept
© OMICRON Page 33
Unique connection concept
© OMICRON Page 34
Modular concept for simplified testing –
Transducer Node CB TN3
> Accessory for motion/contact travel test
> 3 analog and digital channels for data
acquisition of linear or rotational motion
sensors
> Interference-free digital transmission of
results via one cable
© OMICRON Page 35
Powerful software support
© OMICRON Page 36
Benefits of all-in-one OMICRON approach
© OMICRON Page 37
© OMICRON Page 38