You are on page 1of 2

SITE TEST REPORT Date :

Customer:
Contractor’s name:
NG-SA
ALFANAR CO.
Name of substation: Dammam Housing 115/13.8KV Substation # 3 NG-SA Contract No. :
4400006264
DESCRIPTION : TRIPPING RELAY MVAJ 205
Page 1 of 2
Panel/ Bay No: Equip. No.: Dwg. Ref.: Record No.:

1. GENERAL DATA AND INFORMATION:

Bay No. : Aux. Voltage: 110-125V DC

Bay Name : Serial No. :

Manufacturer : ALSTOM Type no. : MVAJ205

Contact reset : HAND & ELECTRICAL No. of contacts: 16 NO + 4 NC

ELECTRICAL TEST

A) PICK-UP TEST FOR OPERATE AND RESET COILS:

Operating Range :
Minimum Operating Voltage 60% Of Lower Rated Voltage
See Technical Page No. 16

B) OPERATING TIME TEST (At 100% of rated voltage):

Limits:
Time limits for Operate Coil < 10 ms
Time limits for Reset Coil <15 ms
(As per Technical Data Page.2)

DATE:
TESTING ENGINEER CSD- Engineer
Signature: ________________ Signature: ________________
Name : Eng/VIGNESH RAMADOSS(FAN-422) Name : EnG/SIVA VIBU KANNAN
SITE TEST REPORT Date :
Customer:
Contractor’s name:
NG-SA
ALFANAR CO.
Name of substation: Dammam Housing 115/13.8KV Substation # 3 NG-SA Contract No. :
4400006264
DESCRIPTION : TRIPPING RELAY MVAJ 205
Page 2 of 2
Panel/ Bay No: Equip. No.: Dwg. Ref.: Record No.:

C) RELAY BURDEN DURING OPERATION (At 100% of rated voltage):

Limits:
Relay Burden for Operate Coil <150W
Relay Burden for Reset Coil <80W
(As per Technical Data Page.7)

D) TESTING KITS

No. Test Equipment Serial Number Calibration date Calibration due date
1 Sverker 780 1300998 09/02/2017 08/02/2017
2 Multimeter 143438 NKH 30/11/2016 29/11/2016

DATE:
TESTING ENGINEER CSD- Engineer
Signature: ________________ Signature: ________________
Name : Eng/VIGNESH RAMADOSS(FAN-422) Name : EnG/SIVA VIBU KANNAN