(OLTC)
•As the name
suggests, permit tap
changing and hence
voltage regulation
with the transformer
during on-load.
On Load Tap Changer
(OLTC)
Quick Review of Voltage Regulation
•“On Load Tap Changer” is used
to compensate the drop in output
voltage of high power
transformer, drop in output
voltage from no load to full load
in know as voltage regulation.
V•(Load
oO taL geT R C eg)
on consumer end of ulati
l on
transformer is never fixed, it
varies at random, its higher value
is matter of concern.
On Load Tap Changer
Quick Review of
V•(Light
oO ltaLLoad
Load; geTmay
RC be eg)u
low lation
due
to fact that much of the time not
all the connected load remain
“on”.
•Though at low load there is slight
drop in voltage at the load end
but not matter of concern up to
certain level.
On Load Tap Changer
Quick Review of
V•(High
oO ltaLwhen
Load; geTsoRmany
Ceg)ulation
connected load gets on same
time high current is drown out
from transformer to drive all.
1
On Load Tap Changer
(OLTC)
Quick Review of Voltage Regulation
•Drop in voltage on LV side is
compensated by reducing
number of turns of HV side,
selector arm is moved from
tap 1 to tap 2 to reduce
number of turns.
1
On Load Tap Changer
(OLTC)
Detail Insight of OLTC
1. Selector Switches High Voltage
These switches select the physical tap Winding
position on the transformer winding.
2. Reactors
During each tap change, there is an interval
where two voltage taps are spanned.
Bypass
Reactors (inductors) are used in the circuit
to increase the impedance of the selector
switch
circuit and limit the amount of current
circulating due to this voltage difference. Vacuu
m
3. Vacuum Switch switch
During each tap change the duty of circuit Reactor
breaker is performed by vacuum switch. Selector coil
switches
4. Bypass Switch
This switch operates during the tap changing
sequence but, at no time, does it make or
break load current.
On Load Tap Changer
(OLTC)
Detail Insight of OLTC
High Voltage
•Change in tap position during on load is not Winding
a quite simple process, proper steps must be
followed to do this without causing sever
transient and damage to the windings
Bypass
switch
Vacuu
m
switch
Reactor
Selector coil
switches
On Load Tap Changer
(OLTC)
Detail Insight of OLTC
Step 1
•tap changer selected to tap 1, all
switches in home position.
On Load Tap Changer
(OLTC)
Detail Insight of OLTC
Step 2
•“Selector Switch” arm moving from Tap-
1 to Tap-2.
Step 3
•Isolated part of “selector arm’ comes in
contact with tap-2 which is relatively at
lower voltage than tap 1.
Step 4
•“Vacuum Switch” get closed, tap 1 and
tap 2 get short.
Step 5
•“Vacuum Switch” remain closed, voltage
of turns from tap-1 to tap-2 ceased at
line voltage.
Step 6
•“Bypass Switch” gets completely in
contact with right part of “Selector
Switch”.
On Load Tap Changer
(OLTC)
Detail Insight of OLTC
Step 7
•“Vacuum Switch” get opened, right part
get isolate.
Step 8
•Left part of “selector switch” can left
tap-1 without facing discharge/spark.
On Load Tap Changer
(OLTC)
Detail Insight of OLTC
Step 8
•“Selector Switch” completely rest on
Tap-2 after leaving Tap-1.
C
B
A
On Load Tap Changer
(OLTC)
OLTC Connections
R Y B
A
B
C
On Load Tap Changer
(OLTC)
OLTC Connections
R Y B
A
B
C
On Load Tap Changer
(OLTC)
OLTC Connections
R Y B
A
B
C
On Load Tap Changer
(OLTC)
OLTC Connections
On Load Tap Changer
(OLTC)
OLTC Connections