Professional Documents
Culture Documents
Load Estmition 11111
Load Estmition 11111
•LOAD ESTIMATION
•The electric load in electricity distribution varies with time
and place (See examples of load variation of three types of
customers in figure) and the power production and
distribution system must respond to customers’ load
demand at any time.
Demand factor is the ratio of the maximum demand of a system to the total
connected load (maximum demand when all are used).
Demand factor is usually less than one.
Demand factor for residential building according to IEC.
Illumination: 50% of total connected load. Small appliance circuits:
100% of rated load for maximum outlet wattage in the circuit plus
40% of the total connected loads of other outlets in the circuit.
Fixed appliance circuits and Fixed electric ranges: 100% of rated load
of largest equipment plus 50% for rated load for the 1st equipment
following the largest one plus 33% for the 2nd equipment following
the largest load plus 20% of total connected load of other equipment.
•COINCIDENCE FACTOR:
•The coincidence factor is the ratio of the maximum
demand of a system, or part under consideration, to
the sum of the individual maximum demands of the
subdivisions or EQUATION: Coincidence factor =
Maximum systemdemand Sum of individual maximum
demands
LOAD FACTOR:
The load factor is the ratio of the average load over a designated period of time, usually 1
year, to the maximum load occurring in that period or EQUATION: Loadfactor = Average
load Maximum load
MAXIMUM DEMAND:
The maximum demand is the integrated demand for a specified time interval, i.e., 5
minutes, 15minutes, 30 minutes, or other appropriate time intervals, rather than the
instantaneous or peak demand.
•Methods of Electrical load estimation:
•Area method.
Total floors loads= Load Density (KVA/100m²) x Build up Area /100 (m²)
For villa
According to Egyptian Code, we will take The load density for ground floor plan = ground floor
plan for first floor plan = 10 (KVA/100m²)
Connect load (kVA)
The ground=20.95
The first =20.92
The floor =19.63
Demand load /Bu (KVA)= Demand factor* Max Demand with spare
(KVA)
The ground=17.74
The first =17.71
The floor =16.33
Total Demand load =51.17