Professional Documents
Culture Documents
Fault Level Calculation
Fault Level Calculation
EAOC Standard
– Electrical Products
Standard (ESP)
Products Study Material
Study Material
Control & Automation
tomation
•IMS2 Product
TYPES OF FAULTS
•IMS2 Product
SYMMETRICAL ASYMMETRICAL
THREE PHASE FAULT LINE TO LINE
DOUBLE LINE TO
EARTH
LINE TO EARTH
• •
X 3 Un = 415V
MCC
M1
50 HP M2
100 HP M3
30 HP M4
150 HP
•for internal use only
•
EAOC – Electrical Standard Products Study Material
tomation OTHER ASSUMPTIONS
1 . 05 * LINE VOLTAGE
I S/C = •IMS2 Product
3 * (Z TR + Z CABLE )
% Z * 10 * KV 2
Z TR =
KVA
DATA AVAILABLE
Line Voltage = 433
KVA =2000 •IMS2 Product
%Z = 6.25
6.25 * 10 * (.433) 2
Z TR = = 0.005859ohms
2000
1 . 05 * 433
I S/C = = 44.8KA
3 * (0.005859 )
• Fault at Point 1= 44.8 KA
• DATA AVAILABLE
• ZTR =0.005859 ohms
• Zcable(400 Sqmm) =0.0778Ohms/KM
•
•IMS2 Product
No of Runs = 7
• Distance Pt. 1 to 2 =20 m
1 . 05 * 433
I S/C =
3 * ( 0.005859 + 20*(((0.0778/1000)/7)))
• I S/C =43.16 KA
DATA AVAILABLE
ZTR =0.005859 ohms
Zcable Pt1 to Pt2 =7*(400 Sqmm) =0.0002223 ohms •IMS2 Product
Zcable Pt 2 to Pt 3 =1*(400 Sqmm) =0.0000778 ohms
Distance Pt. 2 to 3 =30 m
1 . 05 * 433
I S/C =
3 * ( 0.005859 + 0.0002223 + 0.002334)
I S/C = 31.19 KA