Professional Documents
Culture Documents
INTERCEPTORS
SERVICE AND
MAINTENANCE
Part - I
Section 1001 – TRAPS REQUIRED
It is provided, however, that one trap may serve a set of not more
than three (3) single compartment sinks or laundry tubs of the same
depth or three (3) lavatories immediately adjacent to each other and
in the same room if the waste outlets are not more than 0.75 meter
apart and the trap is centrally located when three (3) compartments
are installed. The depth requirement may be waived if approved-
type pump discharge the fixtures or appliances.
Each fixture trap shall have a protecting vent so located that the
developed length of the trap arm from the trap weir to the inner edge
of the vent shall be within the distance given in Table 10-1, but in no
case less than two times the diameter of the trap arm.
A trap arm may change direction without the use of a cleanout when such change of
direction does not exceed ninety (90) degrees.
Exception: For trap arms 76 mm in diameter and larger, the change of direction
not exceeding 22 ½o no cleanout is required and for change of direction greater
than 22 ½ o a cleanout is required at the bend.
The vent pipe opening from a soil or waste pipe, except for water closets and similar
fixtures, shall not be below the weir of the trap.
TABLE 10-1
Horizontal Distance of Trap Arms
(Except for water closets and similar fixtures)
Slope 2% or 20 mm/meter
* The developed length between the trap of a water closet or similar
fixture measured from the top of closet ring (closet flange) to inner
edge of vent shall not exceed 1.8 meters.
No form of trap which depends for its seal upon the action of
movable parts or concealed interior partitions shall be used. “S”,
Bell and Crown-vented traps are prohibited. No fixture shall be
double trapped. Drum traps may be installed only when permitted
by the Administrative Authority for special condition. No drum trap
shall be installed without a vent.
Each fixture trap shall have a water seal of not less than 51 mm and
not more than 102 mm deep except where a deeper seal is found
necessary by the Administrative Authority for special conditions.
Traps shall be set erect and true with respect to their water seals.
Every fish, fowl and animal slaughter house or establishments and every
fish, fowl and meat packing or curing establishments, or any other
establishment from which considerable amounts of grease, hairs, feathers,
etc., are likely to be discharged with the wastewater into the plumbing
system, sewer system, or private sewage disposal system shall be
connected to and shall drain or discharge through a screening device and
thence into a grease interceptor (clarifier) of an approved design for the
proper disposal of effluents.
Each grease trap required by this Section shall have an approved rate of
flow which is not less than that given in Table 10-2 for the total number of
connected fixtures. The total capacity of fixtures discharging into any such
grease trap shall not exceed two and one-half (2–½) times the certified liters
per minute flowrate of the grease trap as per Table 10-2.
Any grease trap installed with inlet more than 1.2 meters lower in elevation
than the outlet of any fixture discharging into such grease trap shall have an
approved rate of flow which is not less than fifty (50) percent greater than
that given in Table 10-2 nor more than four (4) separate fixture shall be
connected to or discharged into any one grease trap.
For the purpose of this Section, the term “fixture” shall mean and include
each plumbing fixture, appliance, apparatus or other equipment required to
be connected to or discharged into a grease trap by any provision of this
Section.
Each fixture discharging into a grease trap shall be individually trapped and
vented in an approved manner. An approved-type grease trap may be used
as a fixture outlet and the grease trap for a single fixture when the horizontal
distance between the fixture outlet and the grease trap does not exceed 1.2
meters and the vertical tailpipe or drain does not exceed 0.75 meters.
Each grease trap shall have an approved water seal of not less than
51 mm in depth or the diameter of its outlet, whichever is greater.
TABLE 10-2
Grease Traps Capacity
Total Number of Required Rate of Grease Retention
Fixture Connected Flow Capacity, Kilogram
Liters Per Minute
1 76 18
2 95 23
3 132 32
4 189 45
The vent pipe opening from a soil or waste pipe, except for water closets and similar
fixtures, shall not be below the weir of the trap.
TABLE 10-3
Horizontal Distance of Trap Arms
(Except for water closets and similar fixtures)*
1. 32 762
2. 38 1067
3. 51 1524
4. 76 1829
5. 102 & Larger 3048
Slope one-fourth (1/4) inch per foot (20.9 mm/m), s = 0.2
* The developed length between the trap of a water closet or similar fixture
(measured from the top of the closet ring [closet flange] to the inner edge of
the vent) and its vent shall not exceed six (6) feet (1829 mm).
TABLE 10-4
* MINIMUM TRAP DIAMETERS AND DRAINAGE FIXTURE UNIT VALUES
1 Bathtubs 38 2
2 Bidets 38 2
3 Clotheswashers* 51 2
4 Dental units or cuspidors 32 1
5 Drinking fountains 31 1
6 Floor drains 51 2
7 Interceptors* for grease, oil, etc. 51 3
8 Interceptors* for sand, auto wash, etc. 76 6
9 Laundry tubs 38 2
10 Mobile home park traps (one for each trailer) 76 6
11 Receptors* (floor sinks), indirect waste 38 1
receptors for refrigerators, coffee urns, water
station, etc.
12 Receptors*, indirect waste receptors for 51 3
commercial sinks, dishwashers, air washers,
etc.
13 Shower, single stall 51 2