PLENUM FANS
Terminology, History, Testing,
Application and Trends
esented by:
hn Cermak, Acme Engineering &
anufacturing Corp.
The Air Movement and Control Association
International (AMCA), has met the standards and
requirements of the Registered Continuing
Education Providers Program. Credit earned on
completion of this program will be reported to the
RCEPP. A certificate of completion will be issued
to each participant. As such, it does not include
content that may be deemed or construed to be an
approval or endorsement by NCEES or RCEPP.
Learning Objectives
recognizes as centrifugal
fans also:
• In-line centrifugal fans
• Plug fans
• Plenum fans
SW CENTRIFUGAL
IMPELLERS
• With Airfoil Blades
SW CENTRIFUGAL
IMPELLERS
• With single thickness backward curved
blades
IN-LINE CENTRIFUGAL
FAN
• With cylindrical housing
IN-LINE CENTRIFUGAL
FAN
• With box housing
PLUG FAN
• Plug fan may or may have not scroll
housing (here without housing)
PLENUM FAN
• Horizontal Arr.3, Flanged Inlet
PLENUM FAN
• Horizontal Arr3. With Upper Frame
ARRANGEMENT 1
Can include
vibration
islolators
ARRANGEMENT 3
Can include
vibration
islolators
ARRANGEMENT 4
TESTED AUXILIARY
FAN FAN
AIR TEST
CHAMBER FLOW
SOUND TESTING
Testing of outlet sound
SOUND TEST
CHAMBER
SILENCERS
FLOW
TESTED
FAN
SOUND TESTING
Testing of inlet sound
SOUND TEST
CHAMBER
TESTED
FAN
SILENCERS
FLOW
APPLICATION
• Important condition for successful
application of plenum fans is the
knowledge of:
• Test configuration
• Test uncertainties and tolerances
• Application uncertainties
• O.E.M applications are generally safer
since the equipment is tested as a part of
R&D process
APPLICATION OF TEST
DATA
Stall
3
0
0 2000 4000 6000 8000 10000 12000 14000 16000
Flow (cfm)
AIR PERFORMANCE
Centrifugal vs. Plenum Fan (same size and
speed)
100
Max Efficiency Centrifugal Fan
90
Plenum Fan
80
BHP Up By 15%
Static Efficiency (%)
70
60
50
40
30
55% 100%
20
70%
10
0
0 2000 4000 6000 8000 10000 12000 14000 16000
Flow (cfm)
AIR PERFORMANCE
Centrifugal vs. Plenum Fan (same size and
speed)
5
Centrifugal Fan
Plenum Fan
4
Static Pressure (in.wg)
Max Efficiency
Stall
3
BHP Up By 15%
0
0 2000 4000 6000 8000 10000 12000 14000 16000
Flow (cfm)
IMPELLER
DISCHARGE VELOCITY
Absolute Velocity
Radial
Tangential
CCW
Rotation
FAN DISCHARGE
VELOCITY
Centrifugal vs. Plenum Fan (same size
and speed) Best Efficiency
Discharge
Velocity (fpm)
4000
3500
3000
2500
2000
1500
1000
500
0
Flow (cfm)
PLENUM AS MIXING
DEVICE
• Well designed plenum and the
position of the plenum fan inside
the plenum can enhance the fan
performance
• Mixing process of the flow from the
wheel and the air inside of the
plenum improves usage of filters
and or coils located downstream of
the fan
PRINCIPLE
APPLICATION
• Plenum fans are mostly, but not
exclusively used in air handling units
• Plenum fans are short in length
compared to vane-axial or centrifugal
fans
• On the down-stream side of the fan the
plenum fans allow length saving
installation of the equipment requiring
good air velocity distribution across
their face area
IMPACT OF MIXING
INLET vs. DISCHARGE
SOUND
SWL (dB)
92
90
88
86
7 dB
84
82
80
78
76
1
2
3
4
Octave Bands 5
6
Outlet
7
Inlet
8
SOUND vs.
PERFORMANCE
SWL (dB)
97
96
95
94
93
92
91
90
89
14000
88
13640
1
2 12000
3
4 10000
Flow (cfm)
5 8000
6
Octave Bands 7
8
SPECIFIC SWL
Specific SWL
Lowest Sound
55.0 Highest Efficiency
50.0
45.0
40.0
35.0
Free Deliv
Low
30.0
Mid
1 Mid
2
3 Best SE Position on
4
5 Top Pressure Curve
6
Octave Bands 7
8
PLENUM FAN
APPLICATION
5
Stall Max Efficiency
Low Sound
4
Static Pressure (in.wg)
3
Good For Application BHP Up By 15%
50% 100%
1
70%
0
0 2000 4000 6000 8000 10000 12000 14000 16000
Flow (cfm)
CLASSES FOR PLENUM
FANS