Model 485 Annubar

Based Flowmeters
Best-in-CIass Performance
Revolutionary shape and measuring technology improve the accuracy and
repeatability of APT measurements to 0.75%
Conserves Energy
Permanent pressure loss reduced
by minimal flow blockage
485 Annubar

Averaging Pitot Tube
Rosemount Revolutionizes APT Measurement
485 Annubar

Averaging Pitot Tube
Rosemount Revolutionizes APT Measurement
Maintenance Free
nsusceptibility of the sensor to
wear, warp, and plug provide low
maintenance costs
Specifications
Line size: 2 to 72 (50mm to 1800mm)
Direct mount pressure Iimit: 1440 psi (100 bar)
IdeaI fIuids: Liquids, Gases & Steams
Direct mount temp: 500F (260C)
Remote mount temp: 1250F (675C)
Sensor materiaI: 316SS & Hastelloy
Comprehensive FIuid Measurement
Frontal slot integrates at least 70% of the
flow profile to improve averaging
ReaI-Time Measurements
Patented integral temperature
design available in all line sizes
enables mass flow output
Best-in-CIass Performance
Highest DP SignaI
485 Annubar

Averaging Pitot Tube
The Key to Success is the T-Shaped Sensor
485 Annubar

Averaging Pitot Tube
The Key to Success is the T-Shaped Sensor
Highest Accuracy
Specifications
Line size: 2 to 72 (50mm to 1800mm)
Direct mount pressure Iimit: 1440 psi (100 bar)
IdeaI fIuids: Liquids, Gases & Steam
Direct mount temp: 500F (260C)
Remote mount temp: 1250F (675C)
Sensor materiaI: 316SS & Hastelloy
Comprehensive FIuid Measurement
ReaI-Time Measurements
Flow
Velocity
Profile
Low
Pressure
Signal
Blockage and
Suction Pressure
High
Pressure
Signal
(Stagnation
Pressure)
Pipe Static
Pressure
mpact Pressure 40%
60%
DP
LOW HIGH
Frontal Slot Design
DP DP
(h (h
ww
) )
= P = P
H(avg.) H(avg.)
- - PP
L(avg.) L(avg.)
ModeI 485 Annubar FIowmeter Series
How the Model 485 Annubar Generates DP
ModeI 485 Annubar FIowmeter Series
How the Model 485 Annubar Generates DP
ModeI 485 Annubar FIowmeter Series
Builds on the Way Flow is Measured
ModeI 485 Annubar FIowmeter Series
Builds on the Way Flow is Measured
P
H
P
L
P
H
= Impact Pressure + Pipe Static Pressure
P
L
P
L
Operates by sensing a high pressure
and a low pressure. The resultant is the
differential pressure signal.
Flow
I
m
p
a
c
t

P
r
e
s
s
u
r
e
S
u
c
t
.
P
r
e
s
s
P
L
= Suction Pressure - Pipe Static Pressure
DP
(h
w
)
= P
H(avg.)
- P
L(avg.)
S
u
c
t
.
P
r
e
s
s
ModeI 485 Annubar FIowmeter Series
Low Pressure Measured in Stagnation Zones
ModeI 485 Annubar FIowmeter Series
Low Pressure Measured in Stagnation Zones
Provides a more accurate
measurement over traditionaI APTs
Stagnation zones reduce noise - increase repeatabiIity
Low sensing
pressure
ports are
positioned
on the
backside of
the Annubar
sensor in
the Iess
turbuIent
zones
Annubar FIowmeter Series
485 Annubar is the Most Linear APT
Annubar FIowmeter Series
485 Annubar is the Most Linear APT
-6%
-4%
-2%
0%
2%
4%
6%
0.0E+00 2.5E+05 5.0E+05 7.5E+05 1.0E+06
ReynoIds Number
D
e
v
i
a
t
i
o
n

f
r
o
m

A
v
e
r
a
g
e

K
B
atural Gas, 6" sch 40, 300 PSIG, 50F
I
Diamond II
485
ModeI 485 Annubar FIowmeter Series
T-Shape Design Promotes Fixed Separation Points
ModeI 485 Annubar FIowmeter Series
T-Shape Design Promotes Fixed Separation Points
Linear fIow coefficient over entire ReynoIds number range
Higher veIocities in Red
Lower veIocities in BIue
T-Shape controIs the
separation point
StabiIizes the Iow
pressure measurement
Best-in-CIass Performance
Highest DP SignaI
485 Annubar

Averaging Pitot Tube
The Key to Success is the T-Shaped Sensor
485 Annubar

Averaging Pitot Tube
The Key to Success is the T-Shaped Sensor
Highest Accuracy
Specifications
Line size: 2 to 72 (50mm to 1800mm)
Direct mount pressure Iimit: 1440 psi (100 bar)
IdeaI fIuids: Liquids, Gases & Steam
Direct mount temp: 500F (260C)
Remote mount temp: 1250F (675C)
Sensor materiaI: 316SS & Hastelloy
Comprehensive FIuid Measurement
ReaI-Time Measurements
ModeI 485 Annubar FIowmeter Series
ntegrating Slot Measures High Side Pressure
ModeI 485 Annubar FIowmeter Series
ntegrating Slot Measures High Side Pressure
Measures at Ieast
10X more
of
the fIow profiIe
Provides a more accurate
measurement over traditionaI APTs
Patented sIot design integrates veIocity profiIe
Pipe Size SingIe
Port
MuIti-Port SIot
4" 1.58% 6.30% 75.00%
8" 1.16% 6.98% 78%
12'' 0.78% 4.65% 85%
16" 0.78% 6.25% 84.50%
36" 0.52% 6.26% 88.50%
ModeI 485 Annubar FIowmeter Series
Percentage of Flow Profile Coverage
ModeI 485 Annubar FIowmeter Series
Percentage of Flow Profile Coverage
Best-in-CIass Performance
Highest DP SignaI
485 Annubar

Averaging Pitot Tube
The Key to Success is the T-Shaped Sensor
485 Annubar

Averaging Pitot Tube
The Key to Success is the T-Shaped Sensor
Highest Accuracy
Specifications
Line size: 2 to 72 (50mm to 1800mm)
Direct mount pressure Iimit: 1440 psi (100 bar)
IdeaI fIuids: Liquids, Gases & Steam
Direct mount temp: 500F (260C)
Remote mount temp: 1250F (675C)
Sensor materiaI: 316SS & Hastelloy
Comprehensive FIuid Measurement
ReaI-Time Measurements
DP Primary SignaI LeveI Comparison
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4
EIIipse
BuIIet
ScaIIoped
Round
Diamond
485 Annubar
ReIative DP SignaI LeveI (DCR+25 = 1.0)
ModeI 485 Annubar FIowmeter Series
485 Annubar Generates the Strongest Signal
ModeI 485 Annubar FIowmeter Series
485 Annubar Generates the Strongest Signal
ModeI 485 Annubar FIowmeter Series
What is Signal Noise?
ModeI 485 Annubar FIowmeter Series
What is Signal Noise?
C TotaI dp Average 16.72 inWC
C 3.17% of value 29 1.97 inWC 11.79% of value
Front Average 5.73 inWC
29 0.37 inWC 6.50% of value
Back Average 10.95 inWC
29 1.95 inWC 17.80% of value
O-PIate vs DCR+25 Noise Comparison
oise Test / Water
ne1998 / 500gpm
40 60 80
e (sec)
DCR+25 Noise Test / Water
DSI FIowLab / 7May1998 / 500gpm
0
5
10
15
20
25
0 10 20 30 40 50 60 70 80
Time (sec)
D
P

(
i
n
W
C
)
TotaI
Front
Back
%he scatter about the average is the
precision error," or signal noise
Miller 4.2
hile the average is centered, the inability to
read values close to each other. the device
would not be considered accurate." Miller 4.3
Noise Comparison Test / NaturaI Gas
SwRI / 20Jan1999 / 500acfm
3.0
3.5
4.0
4.5
5.0
5.5
6.0
0 500 1000 1500
Data Point (15 Hz Acq Rate)
D
P

(
i
n
W
C
)
T Shape
DII+ Shape
ModeI 485
Other APT
ModeI 485 Annubar FIowmeter Series
Model 485 Annubar Produces Minimal Signal Noise
ModeI 485 Annubar FIowmeter Series
Model 485 Annubar Produces Minimal Signal Noise
Minimal Signal Noise Allows Usage of Model
485 Annubar in Control Applications
Best-in-CIass Performance
Highest DP SignaI
485 Annubar

Averaging Pitot Tube
The Key to Success is the T-Shaped Sensor
485 Annubar

Averaging Pitot Tube
The Key to Success is the T-Shaped Sensor
Highest Accuracy
Specifications
Line size: 2 to 72 (50mm to 1800mm)
Direct mount pressure Iimit: 1440 psi (100 bar)
IdeaI fIuids: Liquids, Gases & Steam
Direct mount temp: 500F (260C)
Remote mount temp: 1250F (675C)
Sensor materiaI: 316SS & Hastelloy
Comprehensive FIuid Measurement
ReaI-Time Measurements
0
2
4
6
8
10
12
14
Diamond EIIipse BuIIet Round ScaIIoped 485 Annubar
D
P

(
i
n
.

H
2
0
)
Minimum FIow = 5,000 Nm3/H
NormaI FIow = 10,000 Nm3/H
Maximum FIow = 15,000 Nm3/H
Annubar Flowmeter Series
485 Annubar Generates Strongest Signal
Annubar Flowmeter Series
485 Annubar Generates Strongest Signal
atural Gas, 6" sch 40, 300 PSIG, 50F
Low Flow Applications
IntegraI Temperature
Measurement
Small Line Sizes
w/ ntegral Temp.
Measurement
Noise Comparison Test / NaturaI Gas
SwRI / 20Jan1999 / 500acfm
3.0
3.5
4.0
4.5
5.0
5.5
6.0
0 500 1000 1500
Data Point (15 Hz Acq Rate)
D
P

(
i
n
W
C
)
T Shape
DII+ Shape
Control Applications
Annubar FIowmeter Series
ncreased Market Potential
Annubar FIowmeter Series
ncreased Market Potential
Best-in-CIass Performance
Highest DP SignaI
485 Annubar

Averaging Pitot Tube
The Key to Success is the T-Shaped Sensor
485 Annubar

Averaging Pitot Tube
The Key to Success is the T-Shaped Sensor
Highest Accuracy
Specifications
Line size: 2 to 72 (50mm to 1800mm)
Direct mount pressure Iimit: 1440 psi (100 bar)
IdeaI fIuids: Liquids, Gases & Steam
Direct mount temp: 500F (260C)
Remote mount temp: 1250F (675C)
Sensor materiaI: 316SS & Hastelloy
Comprehensive FIuid Measurement
ReaI-Time Measurements
ModeI 485 Annubar FIowmeter Series
Maintenance Free Design
ModeI 485 Annubar FIowmeter Series
Maintenance Free Design
Non-pIug Design
Stagnation pressure exerted
on front of sensor defIects
particuIates frontaI sIot
Less turbuIent region on
backside of Annubar prevents
particuIates from entering
sensing ports
No-Wear Design
No sharp edges to
check for wear
FIow
0
1
2
3
4
5
6
7
8
9
P
P
L

C
o
e
f
f
i
e
c
i
e
n
t
Orifice NozzIes Venturi 15 Venturi 7 New
Annubar
DII
Annubar
Turbine CorioIis Vortex
Annubar FIowmeter Series
Lowest PPL Compared to Other Technologies
Annubar FIowmeter Series
Lowest PPL Compared to Other Technologies
0%
1%
2%
0 5 10 15 20
Orientation (Degrees MisaIignment)
K

S
h
i
f
t

w
/

M
i
s
a
I
i
g
n
m
e
n
t
Water Lab Test 10"Sch40 Water Lab Test 10"Sch40
ModeI 485 Annubar FIowmeter Series
Low Probe Orientation Effects
ModeI 485 Annubar FIowmeter Series
Low Probe Orientation Effects
ModeI 485 Annubar FIowmeter Series
Allowable Misalignment Visible to Naked Eye
ModeI 485 Annubar FIowmeter Series
Allowable Misalignment Visible to Naked Eye
% K Shift vs. Mounting HoIe Size
0%
1%
1%
2%
2%
3%
3%
4%
0% 10% 20% 30% 40% 50% 60%
% Oversized Mounting HoIe
%

K

S
h
i
f
t
T1 Summary
T2 Summary
ModeI 485 Annubar FIowmeter Series
Less Sensitive to nstallation Errors
ModeI 485 Annubar FIowmeter Series
Less Sensitive to nstallation Errors
Best-in-CIass Performance
Revolutionary shape and measuring technology improve the accuracy and
repeatability of APT measurements to 0.75%
Conserves Energy
Permanent pressure loss reduced
by minimal flow blockage
485 Annubar

Averaging Pitot Tube
Rosemount Revolutionizes APT Measurement
485 Annubar

Averaging Pitot Tube
Rosemount Revolutionizes APT Measurement
Maintenance Free
nsusceptibility of the sensor to
wear, warp, and plug provide low
maintenance costs
Specifications
Line size: 2 to 72 (50mm to 1800mm)
Direct mount pressure Iimit: 1440 psi (100 bar)
IdeaI fIuids: Liquids, Gases & Steams
Direct mount temp: 500F (260C)
Remote mount temp: 1250F (675C)
Sensor materiaI: 316SS & Hastelloy
Comprehensive FIuid Measurement
Frontal slot integrates at least 70% of the
flow profile to improve averaging
ReaI-Time Measurements
Patented integral temperature
design available in all line sizes
enables mass flow output
ModeI 485 Annubar FIowmeter Series
Pak-Lok Design Available as Quick Ship
ModeI 485 Annubar FIowmeter Series
Pak-Lok Design Available as Quick Ship
Direct Mount
IntegraI 3-vaIve
ManifoId
Direct mounting
reduces leak points,
eliminates impulse
lines, and reduces
overall cost
SST Sensor for
Iine sizes 2"
(50mm) to 12"
(300mm)
Covers about 80
percent of Annubar
applications
3051S or 3095MV
IntegraIIy Mounted
Provides either a
volumetric or mass flow
output
Improved Pak-Lok
Design
Facilitates simple
installation and is widely
accepted
DeIivery in Same
Time as Transmitter
30 percent of our customer
order a transmitter in 2
weeks or less- now we can
deliver a flowmeter in that
period of time!
ModeI 485 Annubar FIowmeter Series
Expected Lead Time By Annubar Type
ModeI 485 Annubar FIowmeter Series
Expected Lead Time By Annubar Type
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
DELIVERY TIME (DAYS)
Pak-Lok, Flanged, Flange-Lok, Flo-Tap
Pak-Lok, Flanged, Flange-Lok
Pak-Lok
Pak-Lok*
50mm) to 1 00mm); Stainless Steel Sensor; Sensor
sizes 1 and ; Direct Mount Integral valve manifold
Pak-Lok Design Now AvaiIabIe
in Same Time as Transmitter!
ModeI 485 Annubar Primary EIement
ModeI 3051S
ModeI 3095MV
ModeI 3051SFA
ProBar
ModeI 3095MFA
Mass ProBar
Annubar FIowmeter Series
485 Annubar Based Flowmeters
Annubar FIowmeter Series
485 Annubar Based Flowmeters
ModeI 3051S F A ProBar fIowmeter
3051S: Rosemount's new pressure
transmitter modeI number
F: FIow AppIication
A: Annubar primary
Annubar FIowmeter Series
Model 3051SFA ProBar flowmeter
Annubar FIowmeter Series
Model 3051SFA ProBar flowmeter
Best-in-CIass Performance
Combines Rosemount's premier Annubar APT with the scalability platform of
the 3051S pressure transmitter for flowmeter accuracy of 0.90% of flow rate
3051SFA ProBar

FIowmeter
Standard Offering for nsertion Applications
3051SFA ProBar

FIowmeter
Standard Offering for nsertion Applications
EasiIy AccessibIe Operator Interface
3051S transmitter allows direct mounting with
'at-grade' electronics capability that
incorporates LCD meter, communications
port and field wiring terminations
MuIti-bus Output
Digital HART

, analog 4-20 ma and built-in


high speed digital bus for fieldbus
communications and advanced PlantWeb
diagnostic, measurement and control
functionality
Reduced Maintenance Costs
10-year 'set and forget' electronics
combined with Annubar

sensor improves
reliability and long-term stability
Reduced TotaI InstaIIed Cost
Ordered from a single vendor and arrives
pre-assembled, ready to install into a single
pipe penetration
Specifications
Line size: 2 to 72 (50mm to 1800mm)
Pressure rating: 1440 psi (100 bar)
IdeaI fIuids: Liquids
Direct mount temp: 550F (285C)
Remote mount temp: 850 F (450C)
MateriaI: 316SS & Hastelloy
ModeI 3095M F A Mass ProBar fIowmeter
3095M: Rosemount's new pressure
transmitter modeI number
F: FIow AppIication
A: Annubar primary
Annubar FIowmeter Series
Model 3095MFA Mass ProBar flowmeter
Annubar FIowmeter Series
Model 3095MFA Mass ProBar flowmeter
Best-in-CIass Performance
Combines Rosemount's premier APT with the 3095MV Multivariable mass flow
transmitter for flowmeter accuracy of 1.0% of flow rate
3095MFA MassProBar

FIowmeter
High Accurate Measurement in Gas & Steam
3095MFA MassProBar

FIowmeter
High Accurate Measurement in Gas & Steam
Three Measurements in One Device
Differential pressure, static pressure, and
process temperature are all measured with a
single pipe penetration
Reduced TotaI Cost
Reduced maintenance, easier installation,
and lower installed cost due to reduced
hardware and single pipe penetration
Greatest DP FIow Accuracy
High accuracy over the widest flow
range by dynamically calculating all flow
coefficients real-time
Easy Configuration
Engineering Assistant software
performs configuration, maintenance,
and diagnostic functions
Specifications
Line size: 2 to 72 (50mm to 1800mm)
Pressure rating: 1440 psi (100 bar)
IdeaI fIuids: Gas and Steam
Direct mount temp: 550F (285C)
Remote mount temp: 850 F (450C)
MateriaI: 316SS & Hastelloy
The integraI temperature measurement in smaII Iine sizes is
fantastic!" -BechteI Engineering
We tested this bar against competition APTs and other
technoIogies and it surpassed them by far! We want 21 FIotaps..
NOW!!!" -Eastman ChemicaI
We currentIy use Annubars and if we can get an even better one,
we wouId be thriIIed!" -EI Dupont
We wouId definiteIy use the new T-Shape over the current
design." -DOW
I wouId Iike to expIore the use of this bar in custody transfer
appIications." -Koch Refinery
New Annubar FIowmeter Series
What are Customers Saying?
New Annubar FIowmeter Series
What are Customers Saying?