Item Curve Formular Service Setting Pick-Up Time multiplier Time at Specifix current Current Seconds Current at Specifix time Seconds Current Remark
1..
kxb ( I/I>) - 1
a
0.2
2.006
2.49
1.749
2..
Very Inverse
t(s) =
kxb ( I/I>) - 1
a
0.1
0.675
3.375
1.400
3..
0.5
20
2.667
2.667
19.999
4..
0.5
40
8.571
8.571
40.002
Where : t = Operation time Seconds k = time multiplier I = measured current value I> = set start current value
Note: The relationship between current and time complies with the BS 142.1966 and IEC 255-4 standard.
1..
0.5
15
0.556
0.556
15.014
2..
0.44
6.6
1.602
1.07
16.423
3..
0.5
15
4.060
4.06
15.000
4..
Very Inverse**
0.24
25
0.135
3.375
1.960
5..
0.5
15
5.000
15.000
6..
0.5
15
30.000
30
15.000
a = constant
TMS = time multiplier Note: ** IEC standard characteristic