Professional Documents
Culture Documents
Beam-Column
Connections
Performance and design of joints subjected to seismic lateral load reversals
C
bb e bc C
Column centerline
T
hc
(a) Offset side (b)
Fig. 1: (a) Plan view; and (b) isometric view of typical eccentric RC beam-column connection (floor slab not shown)
Teng and S3 7.9 15.7 0.25 161 15.9 2.02 1.64 1.61 1.34
Zhou8 S6 7.9 15.7 0.25 87.9 12.5 1.56 1.36 1.25 1.04
Burak and 2-S* 10 21 0.26 194 15.4 1.54 1.27 1.23 0.99
Wight10 3-S* 10 21 0.26 186 17.1 1.71 1.42 1.37 1.10
UM-60 7.9 17.7 0.13 175 20.7 1.59 1.81 1.27 1.62
Goto and Joh11
UM-125 7.9 17.7 0.28 148 17.3 2.20 1.79 1.76 1.35
Kamimura,
Takimoto, and NN.2 7.1 13.8 0.16 94.2 11.0 1.17 1.13 0.93 1.06
Tanaka12
Kusuhara JE-55 7.1 12.6 0.17 104 12.6 1.53 1.35 1.22 1.28
et al.13 JE-55S 7.1 12.6 0.17 105 12.7 1.54 1.36 1.23 1.29
The relatively flexible joints observed with eccentric reduced the connection eccentricity and aided in the
RC beam-column connections were found to contribute resistance mechanisms.9,10 Both eccentric and concentric
about 1/6 to 1/4 of the overall story displacements at edge connections typically exhibited greater effective
low to moderate subassembly drifts (approximately 1 to slab widths than those commonly prescribed for use
2%). The contribution increased to about 1/3 to 1/2 of in design.17
the overall subassembly drift at larger displacements
(when significant joint damage had occurred).4,5,8,9,12,14,15 EFFECTIVE JOINT WIDTHS
Finally, the presence of a floor slab was observed to To better evaluate the joint shear capacity of eccentric
add to the total possible joint shear demand in an RC beam-column connections, a detailed examination was
eccentric connection, but it also appears that the slab conducted of all 16 eccentric connection subassemblies
(along with the transverse beam, when present) effectively found in the literature that were reported to have failed
RECOMMENDATIONS
where ƒ′c is the actual measured concrete compressive Based on the preceding information, it is recommended
strength (psi) and hc is the column depth (in.), with bj,est that an effective joint width (bj) equal to the average of the
in inches, Vj,m in lb, and √ƒ′c in psi. The joint shear stress beam and column widths [(bb + bc )/2] can be used to estimate
factor specified by ACI 352R-02 and ACI 318-05 (γn = 12) is the joint shear strength of eccentric RC beam-column
used to place eccentric connections on an equal basis for connections for design. This recommendation should be
comparison with similar concentric connections. (If Eq. (1) considered in conjunction with the other design provisions
were used with Vj,m in N, ƒ′c in MPa, and hc and bj,est in mm, of ACI 352R-02 such as using a design yield stress multiplier
then γn would be 1.0.) For the 16 specimens, ƒ′c ranged of at least 1.25 and including the contribution to joint
from about 2800 to 5600 psi (19 to 39 MPa), and the shear forces (“demand”) of slab reinforcing steel within
column cross-sectional aspect ratio (hc /bc) ranged from an appropriate effective tension flange width.
0.50 to 1.00.
Table 1 also contains ratios of the estimated effective Acknowledgments
joint width bj,est to the effective joint widths computed The authors would like to thank fellow members of Joint ACI-ASCE
following ACI 318-05 (bj,318) and ACI 352R-02 (bj,352). Per Committee 352, Joints and Connections in Monolithic Concrete
ACI 318-05, bj,318 = bb + 2x, where x is the smaller distance Structures, for their constructive comments and suggestions
between the beam and column edges. Most of the regarding the subject of this article.
connections tabulated are one-sided (flush) eccentric
connections where the bj,318 value is by definition simply References
equal to the beam width (bb). Per ACI 352R-02, 1. Joint ACI-ASCE Committee 352, “Recommendations for Design
bj,352 = bb + Σmhc /2, where m is 0.3 when e is greater than of Beam-Column Connections in Monolithic Reinforced Concrete
bc /8 and m is 0.5 otherwise. The ACI 318-05 effective joint Structures (ACI 352R-02),” American Concrete Institute, Farmington
width definition could be conservative (simply representing Hills, MI, 2002, 37 pp.
the width of the eccentric beams in most of the tabulated 2. ACI Committee 318, “Building Code Requirements for Structural
cases). Such a narrowly defined joint region might be Concrete (ACI 318-05) and Commentary (ACI 318R-05),” American
considered as effectively confined on at least two Concrete Institute, Farmington Hills, MI, 2005, 430 pp.
opposite vertical faces, a case where γn is typically taken 3. Ohno, K., and Shibata, T., “On the Damage to the Hakodate
as 15 in design (1.25 if N and mm units are used). The b ′j,est College by the Tokachioki Earthquake, 1968,” Proceedings of the U.S.-
values used in the table were computed using Eq. (1) with Japan Seminar of Earthquake Engineering with Emphasis on the Safety
γn = 15. Finally, the estimated experimental effective joint of School Buildings, Sendai, 1970, pp. 129-144.