LSP 611
...\tables\Pen\BW_PENTABLE.TBL ...\STANDARD\Current\lsp611.dgn
SHEET NO. 1
Drawn: Checked: Approved: CAW
8"
Date:
5/9/2011
REINFORCING BARS @ 12" CENTERS WALL HEIGHT H 1 CUBIC FOOT OF COURSE GRAVEL ENCASED WITH FILTER FABRIC 1"-0" 1-6" 2-0" 2-6" 3-0" 3-6" 3-11" BASE LENGTH B 2-0" 2-0" 2-0" 2-6" 2-6" 3-0" 4-0"
QUANTITIES PER LINEAR FOOT OF WALL ADDITIONAL CONCRETE ONE WALL CORNER 0.53 0.58 0.64 0.79 0.84 1.01 1.33 DAMP PROOFING SQUARE YARDS
10/3/2011
USER:
PROJ:
DATE:
DGN:
PEN:
BAR SIZE
REINFORCING STEEL POUNDS 3.38 3.95 4.14 4.89 5.08 10.4 12.0
siecaw
NO 3 NO 3 NO 3 NO 3 NO 3 NO 4 NO 4
SIDEWALK
2-0" MINIMUM
CONSTRUCTION JOINT
8"
NOTE:
ALL EXPOSED EDGES OF CONCRETE SHALL BE CHAMFERED 3/4". MINIMUM COVERING, MEASURED FROM THE FACE OF THE CONCRETE TO THE SURFACE OF ANY REINFORCING BAR SHALL BE 3". EXPANSION JOINT SHALL BE PLACED IN RETAINING WALLS AT NOT MORE THAN 50-0" INTERVALS OR AT LOCATIONS TO BE DETERMINED BY THE ENGINEER, AND AT 4-0" FROM WALL CORNERS AND ENTRANCE CORNERS FOR TYPE C WALLS. LONGITUDINAL BARS SHALL BE CUT AT EXPANSION JOINTS. DUMMY JOINTS SHALL BE PLACED IN THE FACE OF WALLS AT LOCATIONS TO BE DETERMINED BY THE ENGINEER. A CONTROL JOINT SHALL BE PLACED MIDWAY BETWEEN EXPANSION JOINTS OR MIDWAY BETWEEN EXPANSION JOINT AND THE END OF THE RETAINING WALL, EXCEPT CONTROL JOINTS WHERE EXPANSION JOINT AND THE END OF THE RETAINING WALL IS 30-0" OR LESS. FIELD CUT ALTERNATE LONGITUDINAL BARS AT CONTROL JOINTS. TOP LONGITUDINAL BARS IS TO BE CONTINUOUS THROUGH CONTROL JOINT. THE BACK FACE OF ALL RETAINING WALLS OVER TWO FEET HIGH SHALL BE DAMP PROOFED ABOVE THE TOP OF THE FOOTING. WEEP HOLES SHALL BE PLACED AT 10-0" CENTERS IN ALL RETAINING WALL. ALL EXPOSED FACES OF RETAINING WALLS SHALL BE BUILT WITH FORMS TO SIMULATE A BRICK FACE.
WEEP HOLE
WALL DETAIL
EXPANSION JOINT
EXPANSION JOINT
END OF WALL
QUANTITIES
4-0"
2-6"
NO 4 HORIZONTAL BARS @ 12" CENTERS FULL HEIGHT OF WALL 2-6" WALL FOR STEPS NOT INCLUDED IN THIS PLAN
ALL REINFORCING STEEL SHALL BE EPOXY COATED. ALL CONCRETE SHALL BE L3500
DETAIL OF
ENTRANCE CORNER
SEE DETAIL A DETAIL OF 3/4"
2"
WALL CORNER
1 1/4"
1" PREFORMED EXPANSION JOINT FILLER 6" CENTER-BULB TYPE RUBBER WATER STOP 3" 1" 4"
1/4" FILL WITH APPROVED JOINT SEALER 1" PREFORMED EXPANSION JOINT FILLER
DETAIL A
3/4"
1/4" 3/4"
NOTE:
WATER STOP TO EXTEND FROM BOTTOM OF FOOTING TO 3" BELOW TOP WALL. ALL LONGITUDINAL STEEL SHALL BE CUT AT EXPANSION JOINTS. GROVE FRONT AND BACK FACE OF WALL.
PR OF E
V I AL CI L EN ON SI S
1 1/4"
1 1/4"
T AT E
A K AS OF NE BR
DETAIL OF
DETAIL OF
DETAIL OF
CONTROL JOINT
DUMMY JOINT
EXPANSION JOINT
EFFECTIVE JULY 1, 2011 REINFORCED CONCRETE RETAINING WALL TYPE C L.S.P. 611
This document was originally issued and sealed by Thomas S. Shafer, E-10679, on 3-1-10. This media should not be considered a certified document.
3/4"
LSP 611
R EE N I G
LSP 611