PROJECT NO.

LSP 611
...\tables\Pen\BW_PENTABLE.TBL ...\STANDARD\Current\lsp611.dgn

SHEET NO. 1
Drawn: Checked: Approved: CAW

8"

700028 OLD AS OF 070610.cfg

Date:

5/9/2011

REINFORCING BARS @ 12" CENTERS WALL HEIGHT H 1 CUBIC FOOT OF COURSE GRAVEL ENCASED WITH FILTER FABRIC 1"-0" 1-6" 2-0" 2-6" 3-0" 3-6" 3-11" BASE LENGTH B 2-0" 2-0" 2-0" 2-6" 2-6" 3-0" 4-0"

QUANTITIES PER LINEAR FOOT OF WALL ADDITIONAL CONCRETE ONE WALL CORNER 0.53 0.58 0.64 0.79 0.84 1.01 1.33 DAMP PROOFING SQUARE YARDS

10/3/2011

USER:

PROJ:

DATE:

DGN:

PEN:

1" PREFORMED EXPANSION JOINT FILLER SIDEWALK

REINFORCING BARS @ 12" CENTERS

2" PIPE AT 10-0" SPACING

BAR SIZE

CONCRETE CUBIC YARDS

REINFORCING STEEL POUNDS 3.38 3.95 4.14 4.89 5.08 10.4 12.0

siecaw

ADDITIONAL STEEL ONE WALL CORNER 55 58 66 72 81 88 107 1-ENTRANCE CORNER 11 12 16 17 21 22 26

NO 3 NO 3 NO 3 NO 3 NO 3 NO 4 NO 4

0.107 0.119 0.132 0.156 0.169 0.193 0.230

SIDEWALK

2-0" MINIMUM

0.43 0.48 0.54 0.59

CONSTRUCTION JOINT

8"

B SECTION AT SECTION PART ELEVATION

NOTE:
ALL EXPOSED EDGES OF CONCRETE SHALL BE CHAMFERED 3/4". MINIMUM COVERING, MEASURED FROM THE FACE OF THE CONCRETE TO THE SURFACE OF ANY REINFORCING BAR SHALL BE 3". EXPANSION JOINT SHALL BE PLACED IN RETAINING WALLS AT NOT MORE THAN 50-0" INTERVALS OR AT LOCATIONS TO BE DETERMINED BY THE ENGINEER, AND AT 4-0" FROM WALL CORNERS AND ENTRANCE CORNERS FOR TYPE C WALLS. LONGITUDINAL BARS SHALL BE CUT AT EXPANSION JOINTS. DUMMY JOINTS SHALL BE PLACED IN THE FACE OF WALLS AT LOCATIONS TO BE DETERMINED BY THE ENGINEER. A CONTROL JOINT SHALL BE PLACED MIDWAY BETWEEN EXPANSION JOINTS OR MIDWAY BETWEEN EXPANSION JOINT AND THE END OF THE RETAINING WALL, EXCEPT CONTROL JOINTS WHERE EXPANSION JOINT AND THE END OF THE RETAINING WALL IS 30-0" OR LESS. FIELD CUT ALTERNATE LONGITUDINAL BARS AT CONTROL JOINTS. TOP LONGITUDINAL BARS IS TO BE CONTINUOUS THROUGH CONTROL JOINT. THE BACK FACE OF ALL RETAINING WALLS OVER TWO FEET HIGH SHALL BE DAMP PROOFED ABOVE THE TOP OF THE FOOTING. WEEP HOLES SHALL BE PLACED AT 10-0" CENTERS IN ALL RETAINING WALL. ALL EXPOSED FACES OF RETAINING WALLS SHALL BE BUILT WITH FORMS TO SIMULATE A BRICK FACE.

WEEP HOLE

WALL DETAIL

EXPANSION JOINT

EXPANSION JOINT

END OF WALL

QUANTITIES

NOTE: RETAINING WALL AND WALL FOR STEPS TO BE POURED INTEGRALLY.

NO 4 VERTICAL BARS PLACED AS SHOWN EXPANSION JOINT

FACE OF WALL 4-0" NO 4 VERTICAL BARS PLACED AS SHOWN

4-0"

FACE OF WALL 2-6" 2-6"

NO 4 HORIZONTAL BARS @ 12" CENTERS FULL HEIGHT OF WALL

2-6"

END OF WALL QUANTITIES 2-6"

NO 4 HORIZONTAL BARS @ 12" CENTERS FULL HEIGHT OF WALL 2-6" WALL FOR STEPS NOT INCLUDED IN THIS PLAN

ALL REINFORCING STEEL SHALL BE EPOXY COATED. ALL CONCRETE SHALL BE L3500

DETAIL OF

ENTRANCE CORNER
SEE DETAIL A DETAIL OF 3/4"

2"

WALL CORNER
1 1/4"

1" PREFORMED EXPANSION JOINT FILLER 6" CENTER-BULB TYPE RUBBER WATER STOP 3" 1" 4"

SPONGE RUBBER JOINT FILLER

1/4" FILL WITH APPROVED JOINT SEALER 1" PREFORMED EXPANSION JOINT FILLER

DETAIL A

3/4"

1/4" 3/4"

NOTE:
WATER STOP TO EXTEND FROM BOTTOM OF FOOTING TO 3" BELOW TOP WALL. ALL LONGITUDINAL STEEL SHALL BE CUT AT EXPANSION JOINTS. GROVE FRONT AND BACK FACE OF WALL.

PR OF E

V I AL CI L EN ON SI S

THOMAS S. SHAFER E-10679

1 1/4"

1 1/4"

T AT E

A K AS OF NE BR

DETAIL OF

DETAIL OF

DETAIL OF

CONTROL JOINT

DUMMY JOINT

EXPANSION JOINT

EFFECTIVE JULY 1, 2011 REINFORCED CONCRETE RETAINING WALL TYPE C L.S.P. 611

This document was originally issued and sealed by Thomas S. Shafer, E-10679, on 3-1-10. This media should not be considered a certified document.

3/4"

LSP 611

R EE N I G