Professional Documents
Culture Documents
Authorised By
SANTOSH BHARADWAJ REDDY
Email: help@matlabcodes.com
Engineeringpapers.blogspot.com
More Papers and Presentations available on above site
INTRODUCTION :
The problem of operation and safety posed by a Recovery Boiler is much
more than a conventional utility/Industrial Boiler. It is basically a chemical
recovery process unit where the organic material in the black liquor is burnt,
while the sodium salt is reduced and drained as molten smelt from the
furnace bottom. At the same time, the heat released is utilized for steam
generation.
Though predominantly the heat for the process is obtained from the
burning of the black liquor, supplementary heat from oil fired auxiliary fuel
burners is required to start up the unit, regulate the charbed , avoid blackouts
and to augment additional steam.
FEATURES :
Auxiliary fuel system is comprised of one level of starting burners (4
burners Oil fired with oil ignitors) at the hearth and one level of load
carrying burners at the secondary(famous)air registors.
The BMS provides for the proper sequencing of equipment during the
normal startup operating and shut down procedures and provides for an
auxiliary fuel trip and/or an alarm during an adverse burner or unit operating
condition. This is accomplished through the use of pre-wired logic and
various Interlocks.
FUNCTION :
The following operations of the function are achieved in the BMS.
1. Boiler purge.
2. Main oil header trip valve open/close operation.
3. Ignitor oil header trip valve open/close operation.
4. Auxiliary fuel burner ignitor ‘ON/OFF’ operation.
5. Ignitor Flame scanning.
6. Auxiliary fuel burner start/stop operation.
7. Auxiliary fuel trip production.
8. Emergency drain trip protection.
The BMS is a local-manual relay system. Starting burners are started and
stopped locally from their associated local switch boxes while the various
header trip valves are opened and closed remotely from associated Push
Buttons on BOILER CONTROL DESK(BCD).All the commands of
BMS are given from BCD and all the feed-back from BMS are indicated
in BCD.
FURNACE PURGE :
Before any auxiliary fuel can be introduced in the unit(initial or after an
auxiliary fuel trip)a satisfactory furnace purge cycle must first be
completed. To start a furnace purge cycle, proceed as follows:
1. Establish an (I.D. Fan Start,Permissive)by completing all of the
following conditions.
*1A. All Emergency drain valves are closed.
*1B. Main oil header trip valve and ignitor trip valve closed.
*1C. Feed Water shut off valve is open.
1D. Evaporator outlet temperature less than 525oF.
1E. Precipitator outlet temperature less than 525oF.
(*) Conditions preceded by an asterish are not required once the ID fan is
running.
2. Place I.D. Fan in service.
3. Place the F.D. Fan in service.
4. Adjust the primary air flow to maintain a minimum of 30% of full load
air flow.
5. See that all of the starting and all of the load carrying burner valves are
fully closed.
6. Reset the boiler trip by depressing the BOILER TRIP RESET Push
Button.
7. When the purge ready light comes on indicating that all of the purge
requirements have been completed depress the PURGE START PUSH
BUTTON.
Depressing the main oil header trip valve close push button will close the
main oil header trip valve.
BOILER TRIP :
Depressing the two emergency drain push buttons results in an instantaneous
boiler trip. The feed water supply valve will not close, however, until the
following conditions are also satisfied.
1. All trip valves closed OR
2. Ignitor trip valve closed and
All oil scanner valves closed.
The emergency drain valves should not open until the feed-water valve is
closed (This is an externally interlocked circuit).
The emergency drain condition will remain, “Scaled in ” until the circuit is
reset by means of a reset push button on the BCD panel. This action is to be
taken by responsible personnel after assessing the particular situation which
warranted the emergency drain trip initially.
Alarms :
The following alarm conditions will cause an annunciator alarm to sound if
the appropriate terminals on the BCD panel are connected to the customers
annunciators. The contacts are normally open for the alarm conditions.
1. Furnace pressure greater than +4”W.G.
2. Air flow less than 30%.
3. Ignitor oil pressure less than 75%.
4. Ignitor air pressure less than 75%.
5. Main oil pressure less than 75%.
6. Starting Burner Oil pressure greater than 125%.
7. Boiler trip.
8. Auxiliary fuel trip.
9. I.D. Fan not running.
10.F.D. Fan not running.
11.Precipitator outlet temperature greater than 525oF.
12.Feedwater shut off valve not open.
13.Emergency drain valves not closed.
14.Evaporator outlet temperature greater than 525oF.
15.Emergency drain and trip.
ECONOMIZER:
In boilers, economizers are heat exchange devices that heat fluids,
usually water, up to but not normally beyond the boiling point of that
fluid.
Economizers are so named because they can make use of the enthalpy
in fluid streams that are hot, but not hot enough to be used in a boiler,
thereby recovering more useful enthalpy and improving the boiler's
efficiency. They are a device fitted to a boiler which saves energy by
using the exhaust gases from the boiler to preheat the cold water used
to fill it (the feed water).
DIGITAL I/P’s :
1. OIL GUN ENGAGED
2. HOBV CLOSED
3. SCNR FLM
4. IGNITOR
5. FURNACE PRESSURE
6. HO PRESSURE
7. ATOM STEAM PRESSURE
8. HO TEMPERATURE
9. HORV OPEN
10.HORV CLOSE
11.HOTV OPEN
12.HOTV CLOSE
13.EP O/L TEMP
14.AIR FLOW
15. DRUM LEVEL
16. SA/TA FAN RUNNING
17. ID FAN RUNNING
18. PA FAN RUNNING
19. FW SHUT OFF VLV OPEN
20. FW SHUT OFF VLV CLOSE
21. EMERGENCY TRIP
22. EM DRAIN & TRIP
23. AUXILIARY FUEL TRIP
24. PURGE START
25. SCANNER FAN-A ST/SP
26. SCANNER FAN-B ST/SP
DIGITAL O/P’s :
1. ATOMISING STEAM V/V
2. HOBV OPENED
3. SCAVENGE V/V
4. HEA IGNITOR
5. HOTV OPEN CMD
6. HOTV CLOSE CMD
7. HORV OPEN CMD
8. HORV CLOSE CMD
9. SCANNER FAN-A START
10.SCANNER FAN-B START
11.NO BOILER TRIP
12.SA/TA FAN START PMT
13.PA FAN START PMT
14.ID FAN START PMT
15.BL PMP
16.EP ASH PUMP
17.AFT
18.PURGE COMPLETE NO AFT
19.EP O/L TEMP
20.FW SHUT OFF V/V CLOSE
21. TRIP SA/TA FAN
22.TRIP PA FAN
23.STM-BL V/V
24.STARTUP V/V
25.EMRG DRN V/V
PLC used in BMS :
INDUSTRIAL SPECIFICATIONS :
Conclusion:-
• The main theme of this project is Purging the Furnace at initial stage
and activating the Emergency Trip and Drain valves during abnormal
conditions while continuous running of process.
• This project can be used for better functioning of Boiler plant without
any malfunctions by continuously monitoring the Industrial
parameters and protecting the Boiler from destruction
• Authorised By
• SANTOSH BHARADWAJ REDDY
• Email: help@matlabcodes.com
• Engineeringpapers.blogspot.com
• More Papers and Presentations available on above site