SELECTION GUIDE

FIXED SPEED CONTROL


DIRECT ONLINE STARTERS SOFT STARTERS THE INTELLIGENT MOTOR CONTROL SOLUTION FOR YOUR APPLICATION REQUIREMENTS

Intelligent Motor Control Intelligent Motor Control with Fixed Speed Starters Product features

2 4 6

Product selection E1 Plus Electronic Overload Relays E3 and E3 Plus Electronic Overload Relays 825-P Modular Protection System SMC-Flex Smart Motor Controllers ArmorStart Distributed Motor Controllers 8 10 12 14 18

Short-Circuit Coordination Functionality Overview

24 26

Rockwell Automation, Allen-Bradley, PowerFlex, ArmorPoint, ArmorConnect, ArmorStart are registered trademarks of Rockwell Automation. DeviceLogix, DeviceNet are trademarks of Rockwell Automation.

AN INTEGRAL PART OF YOUR

INTEGRATED ARCHITECTURE

FIXED SPEED CONTROL

We understand that you need to control performance, reduce downtime, improve safety, increase productivity, perform diagnostics. Thats why weve combined leading-edge motor control and protection devices with the advanced networking and diagnostic capabilities of Rockwell Automations Integrated Architecture to provide you with Intelligent Motor Control.

Direct Online Starters

Soft Starters

With solutions for a variety of motor control requirements and devices hosting in-built intelligence, control of your motor applications can be truly integrated into your solution. Seamless integration allows your to monitor, control, program and interrogate your motor control solutions to achieve the efficiency, reliability and control you demand. With different levels of integration available, there is an integrated solution ideal for you.

WHAT YOU CAN ACHIEVE WITH INTEGRATED ARCHITECTURE AND INTELLIGENT MOTOR CONTROL SOLUTIONS...
Optimise motor performance through intelligent equipment and networks Reduce your energy consumption and increase efficiency Reduce downtime in the event of drive damage with automatic device replacement (ADR) Alerts you about motor problems before a failure occurs Embed safety functionality to protect your process, personnel and equipment health Achieve seamless communication and system visibility for increased system performance, simplified troubleshooting and reduced startup times and much more...

NetLinx
(EtherNet/IP, ControlNet, DeviceNet)

VARIABLE SPEED CONTROL

MOTION CONTROL

Low Voltage AC Drives

Medium Voltage AC Drives

Engineered Drive Solutions

Servo Drives

Servo Motors

FIXED SPEED CONTROL

Direct Online Starters

E1 PLUS ELECTRONIC OVERLOAD RELAYS


0.1...800 A Current Range Self-Powered Fast Phase Loss Protection Wide adjustment Range (5:1) Low Energy Consumption (150mW) Visible Trip Indication Side mount Communications Modules

E3 AND E3 PLUS ELECTRONIC OVERLOAD RELAYS


0.4...860 A Current Range 9...5000 A Current Range with Current Transformer DeviceNet Communication integrated Adjustable trip Class (530) Programmable trip and warning settings Diagnostic functions (History of last 5 trips) DeviceLogix component technology

825-P - MODULAR PROTECTION SYSTEM


0.55000 A Current Range Suitable for low- and medium- voltage applications Modular design with pluggable options - Voltage input cards, including DeviceNet communications - RTD scanner module Comprehensive protection functions Built-in keypad and backlit 2-Line LCD Status LEDs 3 Output relays 2 Configurable inputs

RELAYS E3
2 Inputs 1 Output

RELAYS E3 PLUS
4 Inputs 2 Outputs Built-in ground fault sensor (through 90 A rating) PTC thermistor input

Direct online Starting Rockwell Automation offers a complete portfolio of Allen-Bradley electronic motor protection relays with communications that allow you immediate access to status information, motor performance data, and diagnostics, as well as the capability to perform control functions.

Soft Starting Smart Motor Controllers (SMCs) minimize mechanical wear resulting from full-voltage starting of AC induction motors, enabling longer system life as well as limit line disturbances from inrush currents, resulting in reduced downtime.

Distributed Motor Control For your applications needing machine mounted motor control, the ArmorStart Distributed Motor Controllers offer a simple, cost-effective method of integrating motor control, I/O and network capabilities in your on-machine architecture. The ArmorStart is an integrated, pre-engineered combination starter for full voltage DOL, reversing, Soft starting and variable speed drive applications. The components are mounted closer to the application or on the machine reducing panel space as well as wiring and conduit requirements making it easier to install and start-up. Save more time by configuring intelligent devices via the network and reduce at the same time potential errors.

Soft Starters

ARMORSTART 280/281D DISTRIBUTED MOTOR CONTROLLERS


0.187.5 kW (400V) Full Voltage DOL and Reversing starting IP69K/NEMA Type 4X or IP67/ NEMA Type 4 enclosure ratings Modular plug and play design Network Communications with DeviceNet including DeviceLogix 4 Inputs and 2 Outputs Quick Disconnects for I/O, Communications, Motor Connection and Control Power

SMC-FLEX SMART MOTOR COTROLLERS


11250/1600 A Current Range Soft Start Current Limit Start Full Voltage Preset Slow Speed Soft Stop Options Pump Control Braking Control

ARMORSTART 283D DISTRIBUTED MOTOR CONTROLLERS


0.375.5 kW (400V) Current Limit Start, Soft Start, Soft Stop IP69K/NEMA Type 4X or IP67/ NEMA Type 4 enclosure ratings Modular plug and play design Network Communications with DeviceNet including DeviceLogix 4 Inputs and 2 Outputs Quick Disconnects for I/O, Communications, Motor Connection and Control Power

NETWORK COMMUNICATION

E1 Plus electronic overload relays are the industrys rst modular self-powered devices, setting a new standard for entry level motor protection. The network communications modules expand the functionality. Its compact, simplied control, and exibilitys allows you to network motor starters more cost efciently. Streamline processes with enhanced control, protection, monitoring, and diagnostic capability for improved operating efciency.

The unique line-side over molded power connections on the E1 Plus, on the E3, and E3 Plus make for a sturdy two-component starter assembly that is unmatched in the industry. The preformed power connections allow for easy starter assembly every time.

E3 Overload Relays control functions deliver effective motor management to help prevent and minimize production downtime. Critical protective functions can prevent motor damage and provide advance notication of a machines performance being outside the boundaries of normal operation. Network communication delivers immediate access to motor performance and diagnostic data in addition to seamless control. Integrated I/O provides convenient local termination of motor-related inputs and outputs, simplifying the control architecture. DeviceLogix component technology increases the control possibilities with function block programs that operate at the device level.

PROTECTION

CONTROL

COMMUNICATIONS

Delta Connections

Line Connection

The SMC-Flex is a compact and cost-effective package for your production applications. As standard, the SMC-Flex includes I/O, electronic overload, integral bypass, advanced communication capabilities, motor starting capabilities for both star-delta and standard squirrel-cage induction motors, advanced protection and diagnostics. The SMC-Flex is also available for medium voltage applications with the same features and benets for controlling motors rated up to 7.2 kV and 7500 hp (5600 kW).

1/L1

3/L2

5/L3

2/T1

4/T2

6/T3

M
3~

The SMC-Flex provides 3 Phase Control and excellent performance in a compact design for your standard squirrel cage or Star-Delta induction motors.

Benefits of using DeviceLogix Faster sense-to-actuate response Local processing Higher network performance Increased system reliability Improved diagnostics and reduced troubleshooting Reducing potential points of failure at system level Increasing uptime through distributing ControlLogic throughout system Enables reliability in operation under failures or during maintenance operations Increased system/machine modularity Distributing control on the machine Smaller programs in the master system scan and processing times

What is DeviceLogix? DeviceLogix is a stand-alone Boolean program that resides within the ArmorStart. DeviceLogix is programmed using Boolean math operations such as AND, OR, NOT, Timers, Counters, and Latches. RSNetWorx for DeviceNet Version 3.0 or later is required to program the device. IP69K Rated ArmorStart! The IP69K rated ArmorStart Distributed Motor Controller is suitable for harsh production environments. Rated for environment high pressure wash down with caustic chemicals used in the food and beverage industry (i.e. sodium hydroxide exposure). The IP69K rated ArmorStart offers the same features as the IP67 rated ArmorStart.

Peer to Peer Communications (ZIP) The new Zone Control capabilities of ArmorStart Distributed Motor Controller is ideal for large horsepower motored conveyors. The ArmorStart Distributed Motor Controller have built-in DeviceNet Communications, DeviceLogix technology and the added Zone Interlocking Parameters (ZIP) which allows one ArmorStart to consume data directly from up to four other DeviceNet nodes without going through the network scanner. These direct communications between conveyor zones are beneficial in merge, diverter and accumulation conveyor applications.

E1 PLUS
0.1...800 A Current Range Self-Powered Fast Phase Loss Protection Wide Adjustment Range (5:1) 1 N.O. and 1 N.C. Isolated auxiliary Contacts (B600, AC-15 Rated) Low Energy Consumption (150 mW) Ambient Temperature Compensation Visible Trip Indication Jam/Remote Reset optional accessoires Side-mount Modules for enhanced Motor Protection

Description Three-Phase Devices 193-ED

Mounts to Contactor

Adjustment Range [A] 0.10.5

Cat. No. 193-ED1AB 193-ED1BB 193-ED1CB 193-ED1DB 193-ED1EB 193-EEAB 193-EEBB 193-EECB 193-EEDB 193-EEEB 193-EEED 193-EEFD 193-EEGE 193-EEHF 193-EEJF 193-EEJG 193-EEKG 193-EELG 193-EEMH 193-EENH

0.127 A Current Range Fixed Trip Class 10 Manual Reset

0.21.0 100-C09100-C23 1.05.0 3.216 5.427

Three-Phase Devices 193-EE 100-C09100-C23 100-C09100-C23 100-C09100-C23 0.1800 A Current Range Selectable Trip Class (10, 15, 20 or 30) Selectable Manual/Auto-Manual Reset Single-Phase and Devices with Cage Clamp Control Terminals are also available, see publication 193-SG009_-EN-P. 100-C09100-C23 100-C09100-C23 100-C30100-C43 100-C30100-C43 100-C60100-C85 100-D95100-D180 100-D95100-D180 100-D210100-D420 100-D210100-D420 100-D210100-D420 100-D630100-D860 100-D630100-D860 0.10.5 0.21.0 1.05.0 3.216 5.427 5.427 945 1890 30150 40200 40200 60300 100500 120600 160800

Description DeviceNet Communications Module Integrated I/O allow simplification of the network architecture, providing local connection of motor starter related inputs and outputs. 2 Inputs 24V DC rated, module supplied 1 Output B300 rated Jam Protection Module with Remote Reset Side-mount module with trip level settings of 150, 200, 300 and 400% FLA, and delay time settings of 0.5, 1.0, 2.0 and 4 seconds. For remote resetting of a trip condition. Supply voltage required. Ground Fault Module with Remote Reset Side-mount module for core-balanced ground fault protection, adjustable trip level 20 mA...5 A. Supply voltage required. Ground Fault/Jam Module with Remote Reset Side-mount module for core-balanced ground fault protection, adjustable trip level 20 mA...5 A; Jam protection with fixed trip level setting of 400% FLA, fixed delay time setting of 0.5 seconds. Supply voltage required. Core Balance Ground Fault Sensors Max. 45 A; Window 19.1 mm Max. 90 A; Window 39.6 mm Remote Reset Module For remote resetting of a trip condition. Supply voltage required. DIN Rail/Panel Adapter For separate mounting can be mounted to top-hat rail EN 50 022-35. External Reset Button For enclosed, through-the-door reset applications. Metal construction IP66, non-illuminated with rod (length: 142 mm, adjustable range 141159 mm). Refer to the 800F catalog pages for additional types. Current Adjustment Shield Prevents inadvertent adjustment of the current setting. Must be ordered in multiples of package quantities. Package Quantity = 10 External Reset Adapter For enclosed, through-the-door reset applications. Use with External Reset Button.

For Use With

Cat. No.

193-EE

193-EDN

193-EE

193-EJM

193-EE

193-EGF

193-EE

193-EGJ

100-C09...C37 100-C09...C85

193-CBCT1 193-CBCT2

193-EE

193-ERR

193-ED1_B, 193-EE_B 193-ED1_B, 193-EE_B 193-EE_E 193-ED (all) 193-EE (all)

193-EPB 193-EPD 193-EPE 800FP-R611 800F-ATR08

193-ED (all) 193-EE (all) 592-EE (all) 193-ED (all) 193-EE_B, 193-EE_D, 193-EE_E 100-D140, 100-D180, 100-D95ED180E, 193-EC_F, 193-EE_F 100-D210...100-D420, 193-EC_G, 193-EF2C, 193-EE_G 100-D95100-D180, 193-EC_F, 193-EE_F 100-D210...100-D420, 193-EC_G, 193-EE_G 100-D630100-D860, 193-EC_H, 193-EE_H 100-D630D860, 193-EC_H, 193-EE_H

193-BC8

193-ERA

Terminal Lugs Set of 2 Protection class IP2X per IEC 60529 and DIN 40 050

100-DTB180

100-DTB420 100-DTC180 100-DTC420 100-DTC860 100-DPB860

Terminal Covers Protection class IP20 per IEC 60529 and DIN 40 050 For direct-on-line, reversing, two-speed, and wye-delta/star-delta assemblies Phase Barriers Set of 4

E3 & E3 PLUS
0.4...860 A Current Range 9...5000 A Current Range with Current Transformer DeviceNet communication integrated LED indicators Test / Reset button Adjustable trip Class (530) Integrated I/Os E3: 2 Inputs / 1 Output E3 Plus: 4 Inputs / 2 Outputs

Low-level ground (earth) fault protection 193-EC2 Ground fault range 15 A PTC thermistor input 193-EC2 Programmable trip and warning settings Diagnostic functions (History of last 5 trips) DeviceLogix (series B)

Relay 193-EC1 Mounts to Contactor Adjustment Range [A] 0.42 100-C09100-C23 15 315 525 15 100-C30100-C43 315 525 945 100-C60100-C85 100-D95100-D180 945 1890 28140 1 42210 1 42210 1 100-D210100-D420 60302 1 84420 1 100-D630100-D860
1 Does not include terminal lugs.

Relay 193-EC2 Cat. No. 193-EC2PB 193-EC2AB 193-EC2BB 193-EC2CB 193-EC2AD 193-EC2BD 193-EC2CD 193-EC2DD 193-EC2DE 193-EC2EE 193-EC2FF 193-EC2GF 193-EC2GG 193-EC2HG 193-EC2JG 193-EC2KH 193-EC2LH

Cat. No. 193-EC1PB 193-EC1AB 193-EC1BB 193-EC1CB 193-EC1AD 193-EC1BD 193-EC1CD 193-EC1DD 193-EC1DE 193-EC1EE 193-EC1FF 193-EC1GF 193-EC1GG 193-EC1HG 193-EC1JG 193-EC1KH 193-EC1LH

125630 1 172860 1

10

Description 2 Inputs 1 Output 4 Inputs 2 Outputs Ground fault sensor input PTC thermistor input DeviceLogix

Adjustment Range [A] 95000

Cat. No. 193-EC1ZZ

95000

193-EC2ZZ

Current transformers supplied by customer. Order panel adapter 193-ECPM2 separately. See table below for CT Ratio to FLA setting range correlation. Discount Schedule MPC

CT Ratio 50:5 100:5 150:5 200:5

FLA Setting Range (A) 945 1890 28140 42210

CT Ratio 300:5 500:5 600:5 800:5

FLA Setting Range (A) 60302 84420 125630 172860

CT Ratio 1200:5 2500:5 5000:5

FLA Setting Range (A) 2401215 4502250 10005000

Description

For Use With 193-EC__B

Cat. No. 193-ECPM1 193-ECPM2 193-ECPM3

DIN Rail/Panel Adapter 1

193-EC_D, 193-EC_ZZ 193-EC__E

AC Input Interface Module rated 110/120V AC, 50/60 Hz

193-EC all 592-EC all

193-EIMD

Core Balance Ground Fault Sensor

193-EC2_F, 193-EC2_G, 193-EC2_H, 193-EC2ZZ 100-D140, 100-D180, 100-D95ED180E, 193-EC_F, 193-EE_F 100-D210...100-D420, 193-EC_G, 193-EF2C, 193-EE_G 100-D95100-D180, 193-EC_F, 193-EE_F 100-D210...100-D420, 193-EC_G, 193-EE_G 100-D630100-D860, 193-EC_H, 193-EE_H 100-D630D860, 193-EC_H, 193-EE_H

825-CBCT

100-DTB180

Terminal Lugs Set of 2 Protection class IP2X per IEC 60529 and DIN 40 050

100-DTB420

100-DTC180 100-DTC420 100-DTC860

Terminal Covers Protection class IP20 per IEC 60529 and DIN 40 050 For direct-on-line, reversing, two-speed, and wye-delta/star-delta assemblies

Phase Barriers Set of 4 1 The electronic motor protection relay can be mounted separately to top-hat rail EN 50 02-35. 11

100-DPB860

825-P
0.55000 A Current Range Suitable for low- and medium-voltage applications Modular design with pluggable options - Voltage input cards - Expansion I/O cards - Communications cards, including DeviceNet - RTD scanner module Comprehensive protection functions Built-in keypad and backlit 2-Line LCD Test / Reset button Status LEDs 3 Output relays 2 Configurable inputs

Description

Cat. No.

Cat. No.

Basic Unit Note: The minimum requirements for a complete basic system are one Basic Unit and one Converter Module.

120240V AC/DC

825-PD

User Manual Ships separate from Basic Unit. Please consult your local sales office.

825-UM004_-EN-P

0.52.5 A Converter Module 2.520 A 20180 A 160630 A

825-MCM2 825-MCM20 825-MCM180 825-MCM630N

Core Balance Ground Fault Sensor

100:1

825-CBCT

RTD Scanner Module 12 RTD input channels with individual programming for 10 copper, 100 nickel, 120 nickel, or 100 platinum. Fiber optic connection to Basic Unit. Class I, Division 2, Group T48

120 / 240V AC

825-PR12D

1 Please consult your local sales office for factory configurated devices with option cards.

12

Description Voltage Input Card Monitoring of VA, VB, VC, and VN Expansion I/O Card (3) Inputs (4) Output Relays (1) 420 mA Analog Output 240V AC Max. 1 120V AC Rated Inputs 1 24V DC Rated Inputs 1

Cat. No. 825-PVS 825-PIOD

825-PIOR

DeviceNet Communication Card DeviceLogix technology, Node address selection switches, 1 ODVA conformance tested Modbus RTU Communication Card 1

825-PDN

825-PMB

M8 connections Set of 3 4 x 16 x 102 mm (1/8 x 5/8 x 4-1/64 in.) (125 A max.) Universally applicable Weight: 230 g M8 connections Set of 3 4 x 20 x 117 mm (180 A max.) Universally applicable M6 lower connections Set of 3 For mounting on 100-D95 and 100-D110 contactors with conventional coil M8 lower connections Set of 3 For mounting on 100-D140, 100-D180 conventional and 100-D95E100-D180E contactors with electronic coil 100-D95, 100-D110 Terminal Shields Set of 2 Protection class IP10 per IEC 60529 and DIN 40 050 For direct-on-line, reversing, two-speed, and wye-delta/star-delta assemblies 100-D140, 100-D180, 100-D95-E100-D180-E 100-D210...100-D420 100-D95, 100-D110 Terminal Lugs Set of 2 Protection class IP2X per IEC 60529 and DIN 40 050 100-D140, 100-D180, 100-D95ED180E, 193-EC_F, 193-EE_F 100-D210...100-D420, 193-EC_G, 193-EF2C, 193-EE_G For display of percent thermal capacity utilized Requires the use of an Expansion I/O Card

825-MVM

825-MVM2

825-MVS

825-MVS2

100-DTS110 100-DTS180

100-DTS420 100-DTB110 100-DTB180

100-DTB420

Thermal Utilization Meter

825-MTUM

Connection cable (replacement) 825-P to 825-MCM connection

825-MCA

13

SMC-FLEX
11250/1600 A Current Range Built-in Electronic Overload Protection Soft Start Current Limit Start Dual Ramp Full Voltage Linear Speed Acceleration Preset Slow Speed Soft Stop

Options Pump Control Braking Control

Rating for line connection ? Motor Current [A] 15 5...25 8.6...43 12...60 17...85 27108 34135 67201 84251 106317 120361 160480 208625 260780 323...970 4161250 400V [kW] 2.2 11 22 30 45 55 75 110 132 160 200 250 355 450 560 710

Rating for delta connection ? Motor Current [A] 1.78.7 8.743 14.974 20.8...104 29.4147 47187 59234 116348 145435 183549 208625 277831 283850 300900 4001200 5331600 400V [kW] 4 22 37 55 75 90 132 160 250 135 355 450 500 500 710 900 Control Voltage 100...240V AC 50/60 Hz 24V AC/DC  100...240V AC 50/60 Hz 24V AC/DC  100...240V AC 50/60 Hz 24V AC/DC  100...240V AC 50/60 Hz 24V AC/DC  100...240V AC 50/60 Hz 24V AC/DC  100...240V AC 50/60 Hz 24V AC/DC  100...240V AC 50/60 Hz 24V AC/DC  100...240V AC 50/60 Hz 24V AC/DC  100...240V AC 50/60 Hz 24V AC/DC  100...240V AC 50/60 Hz 24V AC/DC  100...240V AC 50/60 Hz 24V AC/DC  100...240V AC 50/60 Hz 24V AC/DC  110/120V AC 50/60 Hz 230/240V AC 50/60 Hz 110/120V AC 50/60 Hz 230/240V AC 50/60 Hz 110/120V AC 50/60 Hz 230/240V AC 50/60 Hz 110/120V AC 50/60 Hz 230/240V AC 50/60 Hz

Without Option Cat. No. 150-F5NBD 150-F5NBR 150-F25NBD 150-F25NBR 150-F43NBD 150-F43NBR 150-F60NBD 150-F60NBR 150-F85NBD 150-F85NBR 150-F108NBD 150-F108NBR 150-F135NBD 150-F135NBR 150-F201NBD 150-F201NBR 150-F251NBD 150-F251NBR 150-F317NBD 150-F317NBR 150-F361NBD 150-F361NBR 150-F480NBD 150-F480NBR 150-F625NBE 150-F625NBA 150-F780NBE 150-F780NBA 150-F970NBE 150-F970NBA 150-F1250NBE 150-F1250NBA

With Pump Control Option Cat. No. 150-F5NBDB 150-F5NBRB 150-F25NBDB 150-F25NBRB 150-F43NBDB 150-F43NBDR 150-F60NBDB 150-F60NBRB 150-F85NBDB 150-F85NBRB 150-F108NBDB 150-F108NBRB 150-F135NBDB 150-F135NBRB 150-F201NBDB 150-F201NBRB 150-F251NBDB 150-F251NBRB 150-F317NBDB 150-F317NBRB 150-F361NBDB 150-F361NBRB 150-F480NBDB 150-F480NBRB 150-F625NBEB 150-F625NBAB 150-F780NBEB 150-F780NBAB 150-F970NBEB 150-F970NBAB 150-F1250NBEB 150-F1250NBAB

With Braking Control Option Cat. No. 150-F5NBDD 150-F5NBRD 150-F25NBDD 150-F25NBRD 150-F43NBDD 150-F43NBDR 150-F60NBDD 150-F60NBRD 150-F85NBDD 150-F85NBRD 150-F108NBDD 150-F108NBRD 150-F135NBDD 150-F135NBRD 150-F201NBDD 150-F201NBRD 150-F251NBDD 150-F251NBRD 150-F317NBDD 150-F317NBRD 150-F361NBDD 150-F361NBRD 150-F480NBDD 150-F480NBRD 150-F625NBED 150-F625NBAD 150-F780NBED 150-F780NBAD 150-F970NBED 150-F970NBAD 150-F1250NBED 150-F1250NBAD

14

Rating for line connection ? Motor Current [A] 15 5...25 8.6...43 12...60 17...85 27108 34135 67201 84251 106317 120361 160480 208625 260780 323...970 4161250 400V [kW] 2.2 11 22 30 45 55 75 110 132 160 200 250 355 450 560 710

Rating for delta connection ? Motor Current [A] 1.78.7 8.743 14.974 20.8...104 29.4147 47187 59234 116348 145435 183549 208625 277831 283850 300900 4001200 5331600 400V [kW] 4 22 37 55 75 90 132 160 250 135 355 450 500 500 710 900

Without Option

With Pump Control Option

With Braking Control Option

Control Voltage 100...240V AC 50/60 Hz 24V AC/DC  100...240V AC 50/60 Hz 24V AC/DC  100...240V AC 50/60 Hz 24V AC/DC  100...240V AC 50/60 Hz 24V AC/DC  100...240V AC 50/60 Hz 24V AC/DC  100...240V AC 50/60 Hz 24V AC/DC  100...240V AC 50/60 Hz 24V AC/DC  100...240V AC 50/60 Hz 24V AC/DC  100...240V AC 50/60 Hz 24V AC/DC  100...240V AC 50/60 Hz 24V AC/DC  100...240V AC 50/60 Hz 24V AC/DC  100...240V AC 50/60 Hz 24V AC/DC  110/120V AC 50/60 Hz 230/240V AC 50/60 Hz 110/120V AC 50/60 Hz 230/240V AC 50/60 Hz 110/120V AC 50/60 Hz 230/240V AC 50/60 Hz 110/120V AC 50/60 Hz 230/240V AC 50/60 Hz

Cat. No. 150-F5NCD 150-F5NBCR 150-F25NCD 150-F25NCR 150-F43NCD 150-F43NCR 150-F60NCD 150-F60NCR 150-F85NCD 150-F85NCR 150-F108NCD 150-F108NCR 150-F135NCD 150-F135NCR 150-F201NCD 150-F201NCR 150-F251NCD 150-F251NCR 150-F317NCD 150-F317NCR 150-F361NCD 150-F361NCR 150-F480NCD 150-F480NCR 150-F625NCE 150-F625NCA 150-F780NCE 150-F780NCA 150-F970NCE 150-F970NCA 150-F1250NCE 150-F1250NCA

Cat. No. 150-F5NCDB 150-F5NCRB 150-F25NCDB 150-F25NCRB 150-F43NCDB 150-F43NCDR 150-F60NCDB 150-F60NCRB 150-F85NCDB 150-F85NCRB 150-F108NCDB 150-F108NCRB 150-F135NCDB 150-F135NCRB 150-F201NCDB 150-F201NCRB 150-F251NCDB 150-F251NCRB 150-F317NCDB 150-F317NCRB 150-F361NCDB 150-F361NCRB 150-F480NCDB 150-F480NCRB 150-F625NCEB 150-F625NCAB 150-F780NCEB 150-F780NCAB 150-F970NCEB 150-F970NCAB 150-F1250NCEB 150-F1250NCAB

Cat. No. 150-F5NCDD 150-F5NCRD 150-F25NCDD 150-F25NCRD 150-F43NCDD 150-F43NCDR 150-F60NCDD 150-F60NCRD 150-F85NCDD 150-F85NCRD 150-F108NCDD 150-F108NCRD 150-F135NCDD 150-F135NCRD 150-F201NCDD 150-F201NCRD 150-F251NCDD 150-F251NCRD 150-F317NCDD 150-F317NCRD 150-F361NCDD 150-F361NCRD 150-F480NCDD 150-F480NCRD 150-F625NCED 150-F625NCAD 150-F780NCED 150-F780NCAD 150-F970NCED 150-F970NCAD 150-F1250NCED 150-F1250NCAD

Controllers rated 108 A and greater are not equipped with line and load terminal lugs. ? Motor FLA and Motor Running Current must fall within the running current range of the device to operate properly. Utilization category: 5...480A AC-53b: 3-50: 1750  Separate 120V or 240V single phase is required for fan operation. 625...1250A AC-53b: 3-50: 3550

a Options B C Z b Options D R E A Voltage Range 100240V AC (5...480A units) 24 V AC/DC (5...480A units) 110/120V AC (625...1250A units) 230/240V AC (625...1250A units) Voltage Range Up to 480V AC Up to 600V AC Up to 690V AC ,

Optional Configurations

150-F108N

c
Options Blank B

, For controllers rated 108...1250A only

Description Standard Pump Control Provides smooth motor acceleration and deceleration, reducing surges caused by the starting and stopping of centrifugal pumps. Starting time is adjustable from 030 seconds, and stopping time is adjustable from 0120 seconds. Braking Control Provides Smart Motor Braking (SMB), Accu-Stop, and Slow Speed with Braking. Prices on request.

15

Description Protective Modules 1 480V Protective Module 600V Protective Module IEC Terminal Covers ? Terminal Cover IEC line or load terminal covers for 108...135 A devices. Dead front protection Terminal Cover IEC line or load terminal covers for 201251 A devices. Dead front protection Terminal Cover IEC line or load terminal covers for 317480 A devices. Dead front protection Human Interface Modules LCD Display, Full Numeric Keypad LCD Display, Programmer Only HIM LCD Display, Full Numeric Keypad (includes 3 m cable) HIM Interface Cable, 1 m (39 in.) Remote I/O RS-485/DF1 ProfiBUS Communication Modules (IP30/Type 1) ControlNet Interbus DeviceNet Ethernet/IP RS-485 HVAC ControlNet (Fiber) Core Balance Transformer Core Balance Ground Fault Sensor 100:1 585 A 1081250 A 585 A 1081250 A

Cat. No. 150-F84 150-F84L 150-F86 150-F86L

150-TC1

150-TC2

150-TC3

20-HIM-A3

Hand Held Human Interface Modules

20-HIM-A5

Door Mounted Human Interface Modules Human Interface Module Interface Cables Communication Modules

20-HIM-C3S

20-HIM-H10

20-COMM-R 20-COMM-S 20-COMM-P 20-COMM-C 20-COMM-I 20-COMM-D 20-COMM-E 20-COMM-H 20-COMM-Q

825-CBCT

1 The same protective module mounts on the line or load side of the SMC-Flex. For applications requiring both line and load side protection, two protective modules must be ordered. ? One terminal cover is shipped as standard with the SMC-Flex controllers. Requires a 20-HIM-H10 cable to connect to the SMC-Flex. Discount Schedule SOF (150-), Discount Schedule 23 (20-), Discount Schedule MPC (825-CBCT)

16

17

ARMORSTART
Bulletin 280/281 On-Machine starting solution Full-Voltage DOL and reversing starting Modular plug and play design Quick disconnect connections for I/O, communications, three phase motor connection and control power Gland plate entry: conduit entrance or ArmorConnect power media 4 Inputs and 2 Outputs (expandable with ArmorPoint) LED status indication DeviceNet communications DeviceLogix component technology Connectivity to ArmorPoint distributed I/O products ControlNet and EtherNet communications via ArmorPoint Factory Installed Options: - Hand/Off/Auto (HOA) keypad configuration - Safety monitor

Conduit Entrance for Control and 3-Phase Power, 3 m unshielded cordset male 90 Motor Cable Current Rating Max. Motor Power [kW] 400V AC 50 Hz 0.37 0.75 2.2 7.5 24V DC Control Voltage DeviceNet Communications Cat. No.
TM

240V AC Control Voltage DeviceNet Communications Cat. No.


TM

[A] 0.241.2 0.52.5 1.15.5 3.216

ArmorPoint Communications Cat. No. 280A-F12Z-10A-CR 280A-F12Z-10B-CR 280A-F12Z-10C-CR 280A-F23Z-25D-CR

ArmorPoint Communications Cat. No. 280A-F12B-10A-CR 280A-F12B-10B-CR 280A-F12B-10C-CR 280A-F23B-25D-CR

280D-F12Z-10A-CR 280D-F12Z-10B-CR 280D-F12Z-10C-CR 280D-F23Z-25D-CR

280D-F12B-10A-CR 280D-F12B-10B-CR 280D-F12B-10C-CR 280D-F23B-25D-CR

Version with quick disconnects for ArmorConnect power media for Control and 3-Phase Power: Replace -CR at the end of the Cat. No. with -RR (Example: 280D-F23Z-25D-RR)

for harsh production environments Conduit Entrance for Control and 3-Phase Power, 3 m unshielded cordset male 90 Motor Cable Current Rating Max. Motor Power [kW] 400V AC 50 Hz 0.37 0.75 2.2 7.5 24V DC Control Voltage DeviceNet Communications Cat. No.
TM

240V AC Control Voltage DeviceNet Communications Cat. No.


TM

[A] 0.241.2 0.52.5 1.15.5 3.216

ArmorPoint Communications Cat. No. 280A-S12Z-10A-CR 280A-S12Z-10B-CR 280A-S12Z-10C-CR 280A-S23Z-25D-CR

ArmorPoint Communications Cat. No. 280A-S12B-10A-CR 280A-S12B-10B-CR 280A-S12B-10C-CR 280A-S23B-25D-CR

280D-S12Z-10A-CR 280D-S12Z-10B-CR 280D-S12Z-10C-CR 280D-S23Z-25D-CR

280D-S12B-10A-CR 280D-S12B-10B-CR 280D-S12B-10C-CR 280D-S23B-25D-CR

Version with quick disconnects for ArmorConnect power media for Control and 3-Phase Power: Replace -CR at the end of the Cat. No. with -RR (Example: 280D-S23Z-25D-RR)

18

Conduit Entrance for Control and 3-Phase Power, 3 m unshielded cordset male 90 Motor Cable Current Rating Max. Motor Power [kW] 400V AC 50 Hz 0.37 0.75 2.2 7.5 24V DC Control Voltage DeviceNet Communications Cat. No.
TM

240V AC Control Voltage DeviceNet Communications Cat. No.


TM

[A] 0.241.2 0.52.5 1.15.5 3.216

ArmorPoint Communications Cat. No. 281A-F12Z-10A-CR 281A-F12Z-10B-CR 281A-F12Z-10C-CR 281A-F23Z-25D-CR

ArmorPoint Communications Cat. No. 281A-F12B-10A-CR 281A-F12B-10B-CR 281A-F12B-10C-CR 281A-F23B-25D-CR

281D-F12Z-10A-CR 281D-F12Z-10B-CR 281D-F12Z-10C-CR 281D-F23Z-25D-CR

281D-F12B-10A-CR 281D-F12B-10B-CR 281D-F12B-10C-CR 281D-F23B-25D-CR

Version with quick disconnects for ArmorConnect power media for Control and 3-Phase Power: Replace -CR at the end of the Cat. No. with -RR (Example: 281D-F23Z-25D-RR)

for harsh production environments Conduit Entrance for Control and 3-Phase Power, 3 m unshielded cordset male 90 Motor Cable Current Rating Max. Motor Power [kW] 400V AC 50 Hz 0.37 0.75 2.2 7.5 24V DC Control Voltage DeviceNet Communications Cat. No.
TM

240V AC Control Voltage DeviceNet Communications Cat. No.


TM

[A] 0.241.2 0.52.5 1.15.5 3.216

ArmorPoint Communications Cat. No. 281A-S12Z-10A-CR 281A-S12Z-10B-CR 281A-S12Z-10C-CR 281A-S23Z-25D-CR

ArmorPoint Communications Cat. No. 281A-S12B-10A-CR 281A-S12B-10B-CR 281A-S12B-10C-CR 281A-S23B-25D-CR

281D-S12Z-10A-CR 281D-S12Z-10B-CR 281D-S12Z-10C-CR 281D-S23Z-25D-CR

281D-S12B-10A-CR 281D-S12B-10B-CR 281D-S12B-10C-CR 281D-S23B-25D-CR

Version with quick disconnects for ArmorConnect power media for Control and 3-Phase Power: Replace -CR at the end of the Cat. No. with -RR (Example: 281D-S23Z-25D-RR)

Description

Cat. No. Modification

Hand Off-Auto Selector Keypad

-3

Example: 281D-S23Z-25D-RR-3

Hand Off-Auto Selector Keypad with Forward/Reverse Function

-3FR

Example: 281D-S23Z-25D-RR-3FR

Safety Monitor
For factory installed options, please contact your local sales office. Other ArmorStart versions available. Please consult publication 280-SG001_-EN-P for complete product information.

-SM

Example: 281D-S23Z-25D-RR-3FR-SM

19

ARMORSTART
Bulletin 283 On-Machine starting solution Soft Start motor control Modular plug and play design Quick disconnect connections for I/O, communications, three phase motor connection and control power Gland plate entry: conduit entrance or ArmorConnect power media 4 inputs and 2 outputs (expandable with ArmorPoint) LED status indication DeviceNet communications DeviceLogix component technology Connectivity to ArmorPoint distributed I/O products ControlNet and EtherNet communications via ArmorPoint Factory Installed Options: - Hand/Off/Auto (HOA) keypad configuration - Source brake contactor - Safety monitor

Conduit Entrance for Control and 3-Phase Power, 3 m unshielded cordset male 90 Motor Cable Current Rating Max. Motor Power [kW] 400V AC 50 Hz 1.1 2,2 3.0 5.5
TM

24V DC Control Voltage DeviceNet Communications Cat. No. 283D-FB3Z-10A-CR 283D-FB9Z-10B-CR 283D-FB16Z-10C-CR 283D-FB19Z-25D-CR ArmorPoint Communications Cat. No. 283A-FB3Z-10A-CR 283A-FB9Z-10B-CR 283A-FB16Z-10C-CR 283A-FB19Z-25D-CR
TM

240V AC Control Voltage DeviceNet Communications Cat. No. 283D-FB3B-10A-CR 283D-FB9B-10B-CR 283D-FB16B-10C-CR 283D-FB19B-25D-CR ArmorPoint Communications Cat. No. 283A-FB3B-10A-CR 283A-FB9B-10B-CR 283A-FB16B-10C-CR 283A-FB19B-25D-CR

[A] 1.1...3.0 3.0...5.5 5.5...7.6 6.316

Version with quick disconnects for ArmorConnect power media for Control and 3-Phase Power: Replace -CR at the end of the Cat. No. with -RR (Example: 283D-FB19Z-25D-RR)

for harsh production environments Conduit Entrance for Control and 3-Phase Power, 3 m unshielded cordset male 90 Motor Cable Current Rating Max. Motor Power [kW] 400V AC 50 Hz 1.1 2,2 3.0 5.5
TM

24V DC Control Voltage DeviceNet Communications Cat. No. 283D-SB3Z-10A-CR 283D-SB9Z-10B-CR 283D-SB16Z-10C-CR 283D-SB19Z-25D-CR ArmorPoint Communications Cat. No. 283A-SB3Z-10A-CR 283A-SB9Z-10B-CR 283A-SB16Z-10C-CR 283A-SB19Z-25D-CR
TM

240V AC Control Voltage DeviceNet Communications Cat. No. 283D-SB3B-10A-CR 283D-SB9B-10B-CR 283D-SB16B-10C-CR 283D-SB19B-25D-CR ArmorPoint Communications Cat. No. 283A-SB3B-10A-CR 283A-SB9B-10B-CR 283A-SB16B-10C-CR 283A-SB19B-25D-CR

[A] 1.1...3.0 3.0...5.5 5.5...7.6 6.316

Version with quick disconnects for ArmorConnect power media for Control and 3-Phase Power: Replace -CR at the end of the Cat. No. with -RR (Example: 283D-SB19Z-25D-RR)

20

Conduit Entrance for Control and 3-Phase Power, 3 m unshielded cordset male 90 Motor Cable Current Rating Max. Motor Power [kW] 400V AC 50 Hz 1.1 2,2 3.0 5.5 24V DC Control Voltage DeviceNet Communications Cat. No.
TM

240V AC Control Voltage DeviceNet Communications Cat. No.


TM

[A] 1.1...3.0 3.0...5.5 5.5...7.6 6.316

ArmorPoint Communications Cat. No. 283A-FC3Z-10A-CR 283A-FC9Z-10B-CR 283A-FC16Z-10C-CR 283A-FC19Z-25D-CR

ArmorPoint Communications Cat. No. 283A-FC3B-10A-CR 283A-FC9B-10B-CR 283A-FC16B-10C-CR 283A-FC19B-25D-CR

283D-FC3Z-10A-CR 283D-FC9Z-10B-CR 283D-FC16Z-10C-CR 283D-FC19Z-25D-CR

283D-FC3B-10A-CR 283D-FC9B-10B-CR 283D-FC16B-10C-CR 283D-FC19B-25D-CR

Version with quick disconnects for ArmorConnect power media for Control and 3-Phase Power: Replace -CR at the end of the Cat. No. with -RR (Example: 283D-FC19Z-25D-RR)

for harsh production environments Conduit Entrance for Control and 3-Phase Power, 3 m unshielded cordset male 90 Motor Cable Current Rating Max. Motor Power [kW] 400V AC 50 Hz 1.1 2,2 3.0 5.5
TM

24V DC Control Voltage DeviceNet Communications Cat. No. 283D-SC3Z-10A-CR 283D-SC9Z-10B-CR 283D-SC16Z-10C-CR 283D-SC19Z-25D-CR ArmorPoint Communications Cat. No. 283A-SC3Z-10A-CR 283A-SC9Z-10B-CR 283A-SC16Z-10C-CR 283A-SC19Z-25D-CR
TM

240V AC Control Voltage DeviceNet Communications Cat. No. 283D-SC3B-10A-CR 283D-SC9B-10B-CR 283D-SC16B-10C-CR 283D-SC19B-25D-CR ArmorPoint Communications Cat. No. 283A-SC3B-10A-CR 283A-SC9B-10B-CR 283A-SC16B-10C-CR 283A-SC19B-25D-CR

[A] 1.1...3.0 3.0...5.5 5.5...7.6 6.316

Version with quick disconnects for ArmorConnect power media for Control and 3-Phase Power: Replace -CR at the end of the Cat. No. with -RR (Example: 283D-SC19Z-25D-RR)

Description

Cat. No. Modification

Hand Off-Auto Selector Keypad

-3

Example: 283D-SC19Z-25D-RR-3

Source Brake Contactor Safety Monitor


For factory installed options, please contact your local sales office. Other ArmorStart versions available. Please consult publication 280-SG001_-EN-P for complete product information.

-SB -SM

Example: 283D-SC19Z-25D-RR-3-SB Example: 283D-SC19Z-25D-RR-3-SB-SM

21

ARMORSTART
Bulletin 284 On-Machine starting solution Variable frequency AC drive using PowerFlex technology Modular plug and play design Quick disconnect connections for I/O, communications, three phase motor connection and control power Gland plate entry: conduit entrance or ArmorConnect power media 4 Inputs and 2 Outputs (expandable with ArmorPoint) LED status indication DeviceNet communications DeviceLogix component technology Connectivity to ArmorPoint distributed I/O products ControlNet and EtherNet communications via ArmorPoint Factory Installed Options: - Hand/Off/Auto (HOA) keypad configuration - EMI filter - Dynamic brake connector - Output contactor - Source brake contactor - Shielded motor cable - Safety monitor - 0...10V analog input

Sensorless Vector Control and Volts per Hertz, with DeviceNet Communications, EMI-Filter, Conduit Entrance for Control and 3-Phase Power, 3 m unshielded cordset male 90 Motor Cable Output Current [A] 2.3 5 7.6 1.4 2.3 380...480V, 50/60 Hz 3-Phase 4 6 7.6 1.7 460600V, 50/60 Hz 3-Phase 3 4.2 6.1 3-Phase Rating [kW] 0.4 0.75 1.5 0.4 0.75 1.5 2.2 3 0.75 1.5 2.2 4 24V DC Control Voltage Cat. No. 284D-FVB2P3Z-10-CR-EMI 284D-FVB5P0Z-10-CR-EMI 284D-FVB7P6Z-25-CR-EMI 284D-FVD1P4Z-10-CR-EMI 284D-FVD2P3Z-10-CR-EMI 284D-FVD4P0Z-10-CR-EM 284D-FVD6P0Z-25-CR-EMI 284D-FVD7P6Z-25-CR-EMI 284D-FVE1P7Z-10-CR-EMI 284D-FVE3P0Z-10-CR-EMI 284D-FVE4P2Z-25-CR-EMI 284D-FVE6P6Z-25-CR-EMI 240V AC Control Voltage Cat. No. 284D-FVB2P3B-10-CR-EMI 284D-FVB5P0B-10-CR-EMI 284D-FVB7P6B-25-CR-EMI 284D-FVD1P4B-10-CR-EMI 284D-FVD2P3B-10-CR-EMI 284D-FVD4P0B-10-CR-EMI 284D-FVD6P0B-25-CR-EMI 284D-FVD7P6B-25-CR-EMI 284D-FVE1P7B-10-CR-EMI 284D-FVE3P0B-10-CR-EMI 284D-FVE4P2B-25-CR-EMI 284D-FVE6P6B-25-CR-EMI

Input Voltage 200...240V, 50/60 Hz 3-Phase

Version with ArmorPoint Communications: Replace 284D at the beginning of the Cat. No. with 284A (Example: 284A-FVE6P6Z-25-CR-EMI) Version with Quick Disconnects for ArmorConnect Power Media for Control and 3-Phase Power: Replace -CR at the end of the Cat. No. with -RR (Example: 284D-FVE6P6Z-25-RR-EMI)

22

Sensorless Vector Control and Volts per Hertz, with DeviceNet Communications, EMI-Filter, Conduit Entrance for Control and 3-Phase Power, 3 m unshielded cordset male 90 Motor Cable Output Current [A] 2.3 5 7.6 1.4 2.3 380...480V, 50/60 Hz 3-Phase 4 6 7.6 1.7 460600V, 50/60 Hz 3-Phase 3 4.2 6.1 3-Phase Rating [kW] 0.4 0.75 1.5 0.4 0.75 1.5 2.2 3 0.75 1.5 2.2 4 24V DC Control Voltage Cat. No. 284D-SVB2P3Z-10-CR-EMI 284D-SVB5P0Z-10-CR-EMI 284D-SVB7P6Z-25-CR-EMI 284D-SVD1P4Z-10-CR-EMI 284D-SVD2P3Z-10-CR-EMI 284D-SVD4P0Z-10-CR-EMI 284D-SVD6P0Z-25-CR-EMI 284D-SVD7P6Z-25-CR-EMI 284D-SVE1P7Z-10-CR-EMI 284D-SVE3P0Z-10-CR-EMI 284D-SVE4P2Z-25-CR-EMI 284D-SVE6P6Z-25-CR-EMI 240V AC Control Voltage Cat. No. 284D-SVB2P3B-10-CR-EMI 284D-SVB5P0B-10-CR-EMI 284D-SVB7P6B-25-CR-EMI 284D-SVD1P4B-10-CR-EMI 284D-SVD2P3B-10-CR-EMI 284D-SVD4P0B-10-CR-EMI 284D-SVD6P0B-25-CR-EMI 284D-SVD7P6B-25-CR-EMI 284D-SVE1P7B-10-CR-EMI 284D-SVE3P0B-10-CR-EMI 284D-SVE4P2B-25-CR-EMI 284D-SVE6P6B-25-CR-EMI

Input Voltage 200...240V, 50/60 Hz 3-Phase

Version with ArmorPoint Communications: Replace 284D at the beginning of the Cat. No. with 284A (Example: 284A-SVE6P6Z-25-CR-EMI) Version with Quick Disconnects for ArmorConnect Power Media for Control and 3-Phase Power: Replace -CR at the end of the Cat. No. with -RR (Example: 284D-SVE6P6Z-25-RR-EMI)

Description

Cat. No. Modification

Hand Off-Auto Selector Keypad with JOG Function Control Brake Contactor Dynamic Brake Connector Source Brake Contactor 0...10V Analog Input EMI Filter Output Contactor Safety Monitor
? The output contactor is included with the Safety Monitor option. For factory installed options, please contact your local sales office.

-3

Example: 284D-SVE6P6Z-25-CR-3-EMI

-CB -DB -SB -A10 -EMI -OC -SM ?

Example: 284D-SVE6P6Z-25-CR-3-CB-EMI Example: 284D-SVE6P6Z-25-CR-3-DB-EMI Example: 284D-SVE6P6Z-25-CR-3-SB-EMI Example: 284D-SVE6P6Z-25-CR-3-SB-A10 Example: 284D-SVE6P6Z-25-CR-3-SB-EMI Example: 284D-SVE6P6Z-25-CR-3-SB-OC Example: 284D-SVE6P6Z-25-CR-3-SB-SM

23

SHORT Direct-Online Class 10 Circuit Breaker 140M MCP (Magnetic Only) Contactor 100-C / 100-D Overload Relay E1Plus - 193-ED../193-EE.. Rated Operational Voltage 400V 50Hz Rated Conditional S-C Current (Iq) 50kA (rms sym) Type of Coordination (IEC 947-4-1) Type "2"

Motor 1500 rpm [kW] 0.06 0.09 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 10 11 15 18.5 22 30 37 45 55 75 90 110 132 160 200

Circuit Breaker Magnetic Setting [A] 3.3 5.2 8.2 8.2 13 20 20 32 52 52 82 130 130 208 208 325 325 416 585 585 210 - 770 210 - 770 300 - 1100 300 - 1100 1000 - 2000 1000 - 2000 1000 - 2000 1250 - 2500 1500 - 3000 2000-4000

Contactor

Overload Relay Thermal Setting [A] 0.10 - 0.50 0.10 - 0.50 0.10 - 0.50 0.20 - 1.0 0.20 - 1.0 1.0 - 5.0 1.0 - 5.0 1.0 - 5.0 1.0 - 5.0 1.0 - 5.0 1.0 - 5.0 3.2 - 16 3.2 - 16 3.2 - 16 3.2 - 16 5.4 - 27 5.4 - 27 9 - 45 9 - 45 9 - 45 9 - 45 18 - 90 18 - 90 40 - 200 40 - 200 40 - 200 40 - 200 60 - 300 60 - 300 100 - 500

[A] 0.24 0.33 0.43 0.61 0.80 1.1 1.5 1.9 2.7 3.5 5.0 6.6 8.5 11 15 20 22 29 36 41 56 68 81 99 135 162 196 232 281 350

Type 140M-C2N-A25 140M-C2N-A40 140M-C2N-A63 140M-C2N-A63 140M-C2N-B10 140M-C2N-B16 140M-C2N-B16 140M-C2N-B25 140M-D8N-B40 140M-D8N-B40 140M-D8N-B63 140M-D8N-C10 140M-D8N-C10 140M-D8N-C16 140M-D8N-C16 140M-D8N-C25 140M-D8N-C25 140M-F8N-C32 140M-F8N-C45 140M-F8N-C45 140M-H8P-C70 140M-H8P-C70 140M-H8P-D10 140M-H8P-D10 140M-J8P-D20 140M-J8P-D20 140M-J8P-D20 140M-J8P-D25 140M-L8P-D30 140M-L8P-D40

Type 100-C09 100-C09 100-C09 100-C09 100-C09 100-C09 100-C09 100-C09 100-C09 100-C09 100-C09 100-C09 100-C09 100-C12 100-C16 100-C23 100-C23 100-C30 100-C37 100-C43 100-C60 100-C72 100-C85 100-D210 100-D210 100-D210 100-D210 100-D250 100-D300 100-D420

Type (1) 193-ED1AB 193-ED1AB 193-ED1AB 193-ED1BB 193-ED1BB 193-ED1CB 193-ED1CB 193-ED1CB 193-ED1CB 193-ED1CB 193-ED1CB 193-ED1DB 193-ED1DB 193-ED1DB 193-ED1DB 193-EEED 193-EEED 193-EEFD 193-EEFD 193-EEFD 193-EEFD 193-EEGE 193-EEGE 193-EEJG 193-EEJG 193-EEJG 193-EEJG 193-EEKG 193-EEKG 193-EELG

(1) Use of current ajustment shield 193-BC8 is recommended to prevent inadvertent adjustment of the current setting

24

SHORT Direct-Online Class 10 Circuit Breaker 140M MCP (Magnetic Only) Contactor 100-C / 100-D Overload Relay E3 - 193-EC1 / 193-EC2 Rated Operational Voltage 400V 50Hz Rated Conditional S-C Current (Iq) 50kA (rms sym) Type of Coordination (IEC 947-4-1) Type "2"

Motor 1500 rpm [kW] 0.06 0.09 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 10 11 15 18.5 22 30 37 45 55 75 90 110 132 160 200

Circuit Breaker Magnetic Setting [A] 3.3 5.2 8.2 8.2 13 20 20 32 52 52 82 130 130 208 208 325 325 416 585 585 210 - 770 210 - 770 300 - 1100 300 - 1100 750 - 1500 1000 - 2000 1000 - 2000 1250 - 2500 1500 - 3000 2000-4000

Contactor

Overload Relay Thermal Setting [A] 0.4 - 2.0 0.4 - 2.0 0.4 - 2.0 0.4 - 2.0 0.4 - 2.0 0.4 - 2.0 0.4 - 2.0 0.4 - 2.0 1-5 1-5 1-5 3 - 15 3 - 15 3 - 15 3 - 15 5 - 25 5 - 25 9 - 45 9 - 45 9 - 45 18 - 90 18 - 90 18 - 90 28 - 140 28 - 140 42 - 210 42 - 210 60 - 302 60 - 302 84 - 420

[A] 0.24 0.33 0.43 0.61 0.80 1.1 1.5 1.9 2.7 3.5 5.0 6.6 8.5 11 15 20 22 29 36 41 56 68 81 99 135 162 196 232 281 350

Type 140M-C2N-A25 140M-C2N-A40 140M-C2N-A63 140M-C2N-A63 140M-C2N-B10 140M-C2N-B16 140M-C2N-B16 140M-C2N-B25 140M-D8N-B40 140M-D8N-B40 140M-D8N-B63 140M-D8N-C10 140M-D8N-C10 140M-D8N-C16 140M-D8N-C16 140M-D8N-C25 140M-D8N-C25 140M-F8N-C32 140M-F8N-C45 140M-F8N-C45 140M-H8P-C70 140M-H8P-C70 140M-H8P-D10 140M-H8P-D10 140M-J8P-D15 140M-J8P-D20 140M-J8P-D20 140M-J8P-D25 140M-L8P-D30 140M-L8P-D40

Type 100-C09 100-C09 100-C09 100-C09 100-C09 100-C09 100-C09 100-C09 100-C09 100-C09 100-C09 100-C09 100-C09 100-C12 100-C16 100-C23 100-C23 100-C30 100-C37 100-C43 100-C60 100-C72 100-C85 100-D110 100-D140 100-D180 100-D210 100-D250 100-D300 100-D420

Type (1) (2) 193-EC1PB 193-EC1PB 193-EC1PB 193-EC1PB 193-EC1PB 193-EC1PB 193-EC1PB 193-EC1PB 193-EC1AB 193-EC1AB 193-EC1AB 193-EC1BB 193-EC1BB 193-EC1BB 193-EC1BB 193-EC1CB 193-EC1CB 193-EC1DD 193-EC1DD 193-EC1DD 193-EC1EE 193-EC1EE 193-EC1EE 193-EC1FF 193-EC1FF 193-EC1GF 193-EC1GG 193-EC1HG 193-EC1HG 193-EC1JG

(1) Use of current ajustment shield 193-BC8 is recommended to prevent inadvertent adjustment of the current setting

(2) Overload Relay 193-EC2.. can also be used

25

Motor Protection Overload Underload Stall Jam Thermistor Input Earth Fault Input Phase loss Current Imbalance Short Circuit Phase Reversal Under Voltage Over Voltage Starts Per Hour 2 Speed Motor Stator RTD Bearing RTD Ambient RTD Trip class Manual reset Automatic reset Single phase Three phase Warnings Fault History General Features Communication Logic Functions Local display I/O Soft Starter Control Soft Start Kick Start Curent Limit Dual ramp Start Full Voltage Soft Stop Pump Control Preset Slow Speed Linear Speed Braking Accu-Stop Slow Speed with Braking Suitable for inside the delta wiring Variable Speed Control Variable Speed Flying Start S - Curve Process Control Loop (PID Fast Flux Up Fast Brake to Stop Flux Braking Speed Proles Close Loop Speed Control Close Loop Torque Control P-jump (Traverse Function) Pump/Fan Application Functions Lifting Application Functions Winder Application Functions Electronic Gearing/Line Shaft Motion Control Functions Safe-Off Mechanical Protection Overall Vibration level Unbalance Misalignment Flow problems Bearing Defects Mechanical Looseness Rubbing Drive Belt Problems

193-ED

193-EE
(1) (1) (1) (1)

193-EC1

193-EC2

825-P
(1) (1) (1) (1) (1) 1...600

SMC-3

SMC-FLEX

10

10...30

5...30

5...30

5...30

(1)

26

PF4M

PF4

PF40

PF40P

PF400

PF70

PF700

PF700H

PF700S

XM-16X

XM-12X

NA regulated

NA regulated

NA regulated

NA regulated

NA regulated

NA regulated

NA regulated

NA regulated

NA regulated

regulated

regulated

regulated

regulated

regulated

regulated

regulated

regulated

regulated

no limits NA

no limits NA

no limits NA

no limits NA

no limits NA

no limits NA

no limits NA

no limits NA

no limits NA

variable

variable

variable

variable

variable

variable
(1)

variable
(1)

variable
(1)

variable
(1) (1)

(1) (1) (1) (1) (1) (1) (1) (1) (1) (1)

(1)

(1)

(1)

(1) With add on Modules.

27

28

29

Rockwell Automation Services & Support


Assessment Services Baseline evaluations of plant floor technical skills, procedures, equipment operation, spare parts inventory, risk, safety and security as well as other automation-related assessments. Condition Monitoring Predictive Maintenance products and services for rotating equipment. Asset Management Services Maintenance Repair Operations (MRO) process and Spare Parts Management for automation assets. Remote Support Services Real-time troubleshooting and monitoring* of automation equipment and systems by off-site automation specialists. PREVENT REACT Safety, Network & Security Services Network design and evaluation, security policy development/deployment, and machine safety services. Training Services Instructor-led training, self-paced training and competency testing on automation and related topics. OnSite Support Services Startup, troubleshooting, repair, conversions and Preventive Maintenance for automation equipment and systems by Rockwell Automation Field Support Engineers. Repair Services & Renewal Parts Remanufacturing and exchange services for automation products and build-to-order legacy automation products.
*System monitoring not available at all service levels

Publication DOLSMC-SG001A-EN-P June 2007

PREDICT

For More Information For more information about Rockwell Automation Services and Support go to www.rockwellautomation.com/services. To learn which other Rockwell Automation Services and Support will be most beneficial to your maintenance strategy, contact your local authorised AllenBradley distributor or Rockwell Automation sales office.

Copyright 2007 Rockwell Automation, Inc. All Rights Reserved. Printed in Europe.