07 TT 01 Earth-Current
07 TT 01 Earth-Current
Grid potential rise (GPR) gets worse as the fault current and earth impedance increases. One way of limiting the GPR in high fault current substations is by adding more copper in the earth mat, thus reducing the earth impedance. This however, is an expensive approach. An overstated fault current can result in an uneconomical substation earth mat design. It is therefore very important to know the maximum current that will flow to earth via the grid for various possible earth-fault locations.For the design and specification of power system equipment, it is necessary to know what the maximum system fault currents will be at the specific location. It is normal practice to compile databases of maximum earth fault levels, using specialised power flow software. However the maximum earth current required in order to calculate the GPR in a substation applies strictly to the current that flows into the earth itself. In most cases a lower level of resistance is effective due to the presence of parallel earth paths through shield wires of overhead lines, tower footing resistances, etc. These parallel paths cause the fault current to divide into multiple paths to complete the return path to the source. In such cases, the calculated level of fault current may well be considerably greater than the actual current that will flow through the earth grid. Ignoring the parallel paths and only considering these high fault current levels could result in an over design of the substation earth grid. In this paper, different transformer configurations and fault locations are analysed. Each analysis is approached by drawing the phasesequence network based on the single line diagram of the faulted circuit. The actual phase currents and grid current are then calculated from the per unit values and shown on the three-phase circuits. Finally the rise in grid potential and the step and touch potentials may be calculated using the maximum grid current values. Configurations considered The following transformer configurations within substations are considered:
Fig. 1a: Single line diagram: HV line terminated on Dyn transformer (HV fault shown).
Fig. 2a: Single line diagram: HV line terminated on YNd transformer (HV fault shown).
Fig. 1b: Actual phase currents in the three phase network.(HV fault).
Fig. 2b: Actual phase currents in the three phase network.(HV fault).
Fig. 1c: Phase sequence network: HV line terminated on Dyn transformer, earth fault on HV side of transformer.
Fig. 2c: Phase sequence network: HV line terminated on YNd transformer, earth fault on HV side of transformer.
The following abbreviations are used in the diagrams: R g : Equivalent earth resistance of all parallel paths T: Transformer H: High voltage winding M: Medium voltage winding L: Low voltage winding (tertiary) Configuration 1: Dyn, HV/MV transformer The simplest case is that of a single line feeding a substation containing a Dyn, HV/MV transformer where the MV neutral is earthed via a resistor (Fig. 1a). In the case of an HV earth fault within the substation, fault current flows down the line from the remote source. All of the current returns to the source neutral via Rg . If the earth fault level is high, coupled with a significant value of Rg , the GPR may be excessive. energize - Jan/Feb 2012 - Page 30
The phase sequence networks for HV earth faults are straight forward (Fig. 1b). I F flows through Rg , which is series-connected in the fault path. GPR, E g , is the product of R g and the current in it. In this case the current is 3 I 0 , therefore the zero sequence voltage, Eg , is: Eg = 3I 0Rg (p.u.) E g = I 0Rg0 (p.u.) where R g0 = 3Rg Eg = I 0Rg0 E base kV It is clear that I 0 is equal to I 0S . The zero sequence voltage over Rg is given by: Eg = I 0Rg0 3I 0SRg (p.u.) For this scenario, the earth fault current is equal to the total fault current. In the case of an MV earth fault outside the substation, the fault current is limited by the MV earthing impedance ZN in series (1) (2)
Dyn, HV/MV transformer YNd, HV/MV transformer YNa(d), auto-transformer with delta connected tertiary windings.
Fig. 3a: Single line diagram: Auto-transformer with delta connected tertiary windings.
Fig. 3b: Three-phase currents for earth fault on primary side of auto-transformer.
with Rg . (A similar phase sequence network can be derived for this scenario). A low ZNO in series with high earth resistivity, or Rg0 , may result in increased problems with step and touch voltages. In such cases special attention may be necessary. Configuration 2: YNd, HV/MV transformer Now consider a substation containing a YNd, HV/MV transformer where the HV neutral is solidly earthed (see Fig. 2a), with an HV earth fault applied. Fig. 2b shows the paths for actual phase currents. The total earth fault current is 3 I Y + I X (p.u.), while the GPR is given by I X Rg (p.u.). In order to calculate the GPR, it is necessary to consider the phase-sequence networks (Fig. 2c). R g0 is connected such that only I 0S flows through it. R g0 must neither be connected between F0 and N1 , nor between Z 0T and F0 . On the rare occasion that the source earth resistance, RS , is significantly high, its value can be added to Rg , then the total resistance = Rg + RS. Similar to Eqn. 2, GPR is the product of Rg and the current flowing in it. In this case the current is 3I0S , therefore the zero sequence voltage, Eg , is: Eg = 3I 0SRg (p.u.) (3) Eg = I 0SRg0 (p.u.) where Rg0 = 3Rg (4)
Example The earth current (4 p.u.) in Fig. 4c is therefore less than the total fault current (4,9 p.u.). Conclusions It is clear from the analysis that the earth current is often less than the total fault current as may be obtained using fault calculation software. It is therefore necessary to get a clear understanding of the specific substation configuration in order to design a safe and economical earth grid. References The books listed refer to various aspects in this paper such as sequence component models and earth currents.
[1] CHW Lackey: Fault Calculations, Oliver & Boyd, Edinburgh, 1st edition, pp. 139 147, 1962. (Power transformer sequence impedances). Areva: Network Protection & Automation Guide, Areva T&D, Paris, 1st edition, pp. 57 60, July 2002. (Transformer zero sequence equivalent circuits). [2] J L Blackburn: Symmetrical Components for Power Systems Engineering, Marcel Dekker Inc., New York, pp. 236 243, 1993. (Autotransformer fault calculation).