Professional Documents
Culture Documents
Sizing Cables Conduit and Trunking Vvgud
Sizing Cables Conduit and Trunking Vvgud
Table of Contents
Foreword ........................................................................................................4 Sizing Cables, Conduit and Trunking Unit Overview..................................6
Practical Skills .................................................................................................... 6 Knowledge Requirements .................................................................................. 6
Correction Factors.......................................................................................15
Ambient temperature - Ca ................................................................................ 16 Thermal Insulation - Ci ..................................................................................... 17 Thermal Insulation - Ci ..................................................................................... 18 Grouping circuits - Cg....................................................................................... 20 Protection by BS3036 semi-enclosed (re-wireable) fuses - Cc ......................... 22
Shock protection..........................................................................................27
Earth fault loop impedance and fault current .................................................... 27 Earth Loop Impedance ..................................................................................... 28 The earth fault loop path .................................................................................. 29 What value is acceptable? ............................................................................... 29 How is earth loop impedance calculated? ........................................................ 31 Earth fault current............................................................................................. 34 Time / current characteristics and disconnection times..................................... 36
Foreword
When trying to determine the size of conductors necessary for the safe working of a circuit many factors need to be considered. It is not acceptable to guess or to use cable sizes that are in common usage just because someone may say that you should use 1.5mm twin and earth. They may just be wrong! If you get cable sizes wrong, then there may be a fire risk, a load that wont function properly, or you may be wasting money on excessive material. All cables have electrical resistance, so there must be an energy loss when they carry current. This loss appears as heat and the temperature of the cable rises. As it does so, the heat it loses to its surroundings by conduction, convection and radiation also increases. The rate of heat loss is a function of the difference in temperature between the conductor and the surroundings, so as the conductor temperature rises, so does its rate of heat loss. As we have already discovered previously copper is a very good electrical conductor. This means that the resistance of a length of copper cable is relatively low. An aluminium cable would have nearly twice the resistance of a copper cable with the same dimensions. Therefore the energy losses in the aluminium cable will be higher than in the copper cable. The copper cable is more energy efficient. To make an aluminium cable with the same energy losses as a copper cable, we have to make it larger. The larger cross sectional area reduces its resistance and brings the energy losses down to the same as a narrower copper cable.
The two cables in the photograph have similar current-carrying capacity. They are each designed to be able to carry up to 500A without the conductor going above 90 The copper cable (on the right) is thinner than the aluminium one, because C. copper is a better conductor. Its cross sectional area is 300mm2 as opposed to 500mm2 for the aluminium.
LEARNER WORK BOOK Cables are designed to be able to withstand a certain amount of heat, and this ability depends on the type of insulation that is used and how the cables are installed into a wiring system. When we consider the current carrying capacity we have to ensure that the cable wont overheat when the normal current is flowing. If conductors are
installed into wiring systems that are incorrectly sized they will not be able to lose enough heat and could have an affect on the insulation properties.
This will be looked at in more detail when we take a look at cable calculations and sizing of conduit and trunking. Cable calculation is the method used to ensure that all the factors of a circuit have been taken into consideration, in particular, the operating current of a cable that is determined by how hot the cable gets. This is affected by a number of variables:
The resistance of the cable - a higher resistance cable will get hotter at a given current. The insulation on the cable - this will tend to keep it warm like a jacket. The environment of the cable - if it is in a duct with other cables (especially with no airflow) it will tend to get hotter.
Knowledge Requirements
To achieve the learning outcome the candidate must know: How to select a suitably sized cable including: How to calculating the current demand of single and three line circuits Select the correct rating of protective device How to allow and apply factors for: Grouping Thermal insulation Ambient temperature Protective device type How to check that the voltage drop is not excessive Establishing circuit disconnections times are met Thermal constraints are satisfied How to determine the size of conduit and trunking appropriate to the size and number of cables Methods used of establishing a circuits maximum demand after diversity is applied
Size and number of cores 4 core 1.5mm XLPE / SWA 4 core 2.5mm XLPE / SWA 4 core 4.0mm XLPE / SWA 4 core 6.0mm XLPE / SWA 4 core 10.0mm XLPE / SWA 4 core 16.0mm XLPE / SWA Cable prices as of JULY 2008
- Price per 100 metres 93.99 126.00 179.99 251.99 385.00 550.00
Complete the following exercise. The following lengths of XLPE/ SWA are required for a job. Your job as the companys buyer is to process this order form from the site supervisor. The client has requested a price of the materials before they will let the job go ahead. Work out the prices using the table above Price () 1. 50M of 4 core 1.5mm XLPE / SWA in one coil 2. 200M of 4 core 1.5mm XLPE / SWA in two coils 3. 100M of 4 core 16.0mm XLPE / SWA in five coils 4. 100M of 4 core 16.0mm XLPE / SWA in one coil How might the price be reduced to add a further saving in cost to the job?
External influences If the circuit is to be installed in a hot or wet environment then the cable has to be suitably rated and sealed from any affecting factors. If the environment carries a high risk of mechanical damage the cable or installation will have to be sufficiently protected form danger. Once you have decided on the type of cable suitable for the environmental conditions, you must choose the size of conductor to be used. In order to gain appreciation for cable selection will only take a look at the various current ratings of various sizes of XLPE armoured cable.
The Basics So that we can understand a full cable calculation we must first understand the basics. Listed below are four terms that describe vital information used in the calculation process. Try to remember them, as they will appear frequently throughout this course.
I b - term used to describe a circuits design current in amps i.e. the load. I n - term used to describe a circuits protection size in amps i.e. the fuse size. I z - term used to describe a circuits value, in amps, once all de-rating factors have been considered I t - term used to describe the tabulated current rating of a cable in amps i.e. the current a cable can safely carry.
Ib
In
Iz
It
The formula above states the underlying principle of the calculation of a circuits cable size. The first factor you need to consider is design current.
Design Current I b
The first stage of the design process is to determine how much current will flow in the circuit. This current is known as the design current and is the full load current of the circuit. It is calculated using one of the formulae below depending on the type of load. You need to ensure all units have to be calculated at the same value (i.e. kW have to be divided by kV; W have to be divided by V) Where: I = the design current in amps (A) P = the circuit power in watts (W) V = the circuit voltage in volts (V) Cos = the power factor
Resistive loads The following formulae apply to single and three line supplies:
P I= V
Single-line 230v Resistive
I=
P 3 V
Inductive and / or capacitive loads The following formulae apply to single and three line supplies:
P I= V cos
Single-line 230v Inductive and or Capacitive
I=
P 3 V cos
In a.c. circuits, the effects of either highly inductive or highly capacitive loads can produce a poor power factor (cos ) (inductive and capacitive loads will be explained later). For now it is satisfactory to know that in circuits where there are inductive and electronic components such as coils and capacitors there are losses. These losses slightly increase the amount of current the equipment uses. You will have to allow for this in such circuits. Note 3 = 1.732
LEARNER WORK BOOK Example 1. A single-line lighting circuit has a total power consumption of 2000 watts using 100watt filament lamps. Calculate the design current. i) Select the correct formula. (Single line; 230v, resistive)
I=
P V
ii) Input the data into the formula and work it out to two decimal places and be sure to add the unit (A).
I=
Example 2. A three-line inductive load has a total power consumption of 30,000 watts (30kW) with a power factor of 0.95. Calculate the design current. i) Select the correct formula. (Three line; 400v, inductive)
I=
P 3 V cos
ii) Input the data into the formula and work it out to two decimal places and be sure to add the unit (A).
I=
There are a few examples for you to calculate for yourself shortly.
10
Ib
I n then I z
It
You can see from this that: The over-current protective device must be equal to or greater than the design current.
11
LEARNER WORK BOOK What reasons can you state for the protective device being equal to or slightly larger than the design current? You may be required to read your reasons to the class.
There are many protective devices in existence and these will be looked at in more detail in Unit 4.4. What is important for now is to realise that these devices all have different ratings or current ratings. Shown below is part of BS7671 that shows the different ratings of BS88 fuses from 6A to 200A. Fuse sizes of BS88 over-current protective devices (Amps) 6 10 16 20 25 32 40 50 63 80 100 125 160 200
Using the table above and a calculator see if you can work out the design currents and overcurrent protection size (BS88) of each of the circuits listed.
Ib 1. A single line, resistive lighting circuit with a total power of 1200 watts
In
3. A single line, inductive lighting circuit with a total power of 1200 watts and power factor of 0.85
12
Reference Methods
Table 4A2 from the IEE Wiring Regulations lists the common methods that can be used to install a cable. You need to decide at this stage in the cable selection process which method of installation to use. This will make sure that the correct cable column is chosen in the later stages of cable selection. This choice is also important when you calculate correction factors for thermal insulation. Using the table (4E4A) from BS7671 on the next page, see if you can determine the basic current ratings (tabulated current ratings I t) of the cables below. Be sure to fully observe the details so you choose the correct column. NB: This exercise displays how different sizes of cables can carry different amounts of current. Also considered are the circuits installation types.
It
1. A 4.0mm, two core cable, carrying alternating current that has been clipped to a wall. 2. A 10.0mm, four core cable, carrying A.C current ran on a cable tray 3. A 16.0mm, single line cable supplying a consumer unit, clipped direct 4. A 25.0mm, three line and neutral supply for an uninterruptible power supply unit in an office block clipped direct to a wall. 5. A 25.0mm, three line and neutral (TP&N) supply to a control panel, ran on a cable tray Consider your findings and try to explain the reasons why we sometimes need to select different sized cables. You may be required presenting your reasons to the class
13
Appendix 4 of BS7671 contains tables for each type of conductor type from single core PVC to multi-core paper insulated lead steel wire armoured. Please refer to BS7671 for more information.
14
Correction Factors
You, as the designer of the installation, need to know the different correction factors, know where they are required and then apply these to the nominal rating of the protection (In) to obtain a value for Iz. Once Iz is calculated we then refer to the correct cable tables from BS7671and select the size based upon the next highest tabulated value (It). Temperature can have a serious effect on a circuit. It can increase the risk of a fault, can cause a cables insulation to melt and can even cause an electrical fire. There are various factors that form a circuits temperature and we will look at these in more detail below. It is essential to follow the correct design procedures and apply the correct correction factors to ensure that the many effects of temperature do not affect the normal operation of a circuit. We will look at these factors individually below but remember there may be more than one factor present in one installation. Ca Ambient Temperature (the surrounding temperature the circuit will operate in) Ci Thermal Insulation (the existence and contact of thermal insulation with the cct) Cg Grouping of ccts (whether or not the circuit is bunched with other circuits) Cc Protection type (whether or not the circuit is supplied with a BS3036 fuse or not.
What If More Than One Factors Are Present? If more than one correction factor is present they can be considered in one calculation shown below
Iz =
Example
In Ca Ci Cg Cc
A three line, 32A circuit is to be installed using XLPE SWA. It will run through a boiler house clipped direct to a wall where the ambient temp will be 40C. It is not grouped nor does it come into contact with any thermal insulation. Discover the de-rated value i.e. the minimum permissible rating of cable. i) Establish all the correction factors present and obtain the values from the tables in the regulations. Ca=0.91; Ci=n/a; Cg=n/a; Cc=n/a (Where there is no factor present we assume a value of one). ii) Input the values into the formula and work out Iz to two decimal places and include the value (A)
Iz =
32 = 35.16 A 0.91 Ci Cg Cc
iii) Select the correct cable table then select the correct column based upon the reference method and select the next highest value (or equal) to Iz. Table 4E4A; column 3; value of 42 amps corresponds to a 4mm XLPE SWA cable.
15
Ambient temperature - Ca
This is the temperature of the surroundings of the cable, often the temperature of the air in a room or building in which the cable is installed. When a cable carries current, it gives off heat. Therefore the hotter the surroundings of the cable, the more difficult it is for the cable to get rid of this heat. But if the surrounding temperature is low, then the heat given off could be easily let out and the cable could carry more current. Cables must give off this heat safely or they could be damaged and there is a risk of a fire. You can find the correction factor for ambient temperature in Tables 4B1 and 4B2 of the IEE Wiring Regulations. These tables are based on an ambient temperature of 30 This means that any C. cables installed in an ambient temperature above this will need the correction factor applying to them. This is because the cable will not be able to get rid of the heat it gives off safely when carrying current. When a cable runs through areas having different ambient temperatures, correction factors should be applied to the highest temperature only. The most common of the correction factors are given in the Tables 4B1 and 4B2 from BS7671 Correction factors for ambient temperature and are given in your Tables from BS7671 and the Onsite Guide. Complete the questions on the nest page to understand how ambient temperature affects minimum cable ratings.
16
LEARNER WORK BOOK Here you will see how ambient temperature can affect the selection of cable. The perfect situation is 30 therefore Ca = 1.0. C
In Iz = Ca
I n - term used to describe a circuits protection size in amps i.e. the fuse size. I z - term used to describe a circuits value, in amps, once all de-rating factors have been considered. C a term for the correction factor of ambient temperature.
Using the table 4E4A and the Ca correction factors in your essential tables determine the minimum size of XLPE cable for each of the circuits below. Make note of the cable insulation type before you proceed with your calculations. You must write down: In (fuse size), Ca (correction factor), Iz (de-rated CCC), cable size (mm), It (tabulated CCC) and your working out. 1. A single-line supply to a DB with a design current of 50A and a MCCB size of 100A, clipped direct at 30 C.
2. A single-line supply to a DB with a design current of 50A and a MCCB size of 100A clipped direct and ran through a boiler house at 50 C.
3. A three line supply to a DB with BS88 fuses 50A and a maximum demand of 45A, clipped direct and ran near to hot machinery at 40 C
4. A three line supply to a DB with BS88 fuses 50A and a maximum demand of 45A, clipped direct but re-routed to 30 C
In your own words how does ambient temperature affect the selection of cable? You may be required to read you answer out to the class.
17
Thermal Insulation - Ci
The use of thermal insulation in buildings, in the forms of cavity wall filling, roof space blanketing, and so on, is now standard. Since the purpose of such materials is to limit the transfer of heat, they will clearly affect the ability of a cable to dissipate the heat build up within it when in contact with them. Thermal insulation has the effect of wrapping a cable in a fur coat on a hot summers day. The heat produced when the cable carries current cannot escape.
Loft insulation
The cable rating tables of the regulations as the one you have already used (Table 4E4A) allow for the reduced heat loss for a cable which is enclosed in an insulating wall and is assumed to be in contact with the insulation on one side. In all other cases, the cable should be fixed in a position where it is unlikely to be completely covered by the insulation. Where this is not possible and a cable is buried in thermal insulation for 0.5 m (500 mm) or more, a rating factor of 0.5 is applied. This means that the current rating is halved or in other words the Iz value will be doubled. If a cable is totally surrounded by thermal insulation for only a short length (for example, where a cable passes through an insulated wall), the heating effect on the cable insulation will not be that significant. This is because heat will be conducted away from the short high-temperature length through the cable conductor. Clearly, the longer the length of cable enclosed in the insulation the greater will be the de-rating effect. Table 52.2 (BS7671) shows the de-rating factors for lengths in insulation of up to 400 mm and applies to cables having cross-sectional area up to 10 mm. Table 52.2 from BS7671 De-rating factors for cables up to 10mm in crosssectional area buried in thermal insulation. Is given in your Tables from BS7671 and the Onsite Guide. The Regulations use the symbol Ci to represent this correction factor. Complete the questions on the next page to understand how thermal insulation affects minimum cable ratings.
18
LEARNER WORK BOOK Here you will see how thermal insulation can affect the selection of cable. The perfect situation is no insulation therefore Ci = 1.0.
In Iz = Ci
I n - term used to describe a circuits protection size in amps i.e. the fuse size. I z - term used to describe a circuits value, in amps, once all de-rating factors have been considered. C i term for the correction factor of thermal insulation.
Using the table 4E4A and the Ci correction factors in your essential tables determine the minimum size of XLPE cable for each of the circuits below. Make note of the cable insulation type before you proceed with your calculations. You must write down: In (fuse size), Ci (correction factor), Iz (de-rated CCC), cable size (mm), It (tabulated CCC) and your working out.
1. A single-line supply to a load with a design current of 13A and a MCB size of 16A, reference method C with no thermal insulation.
2. A single-line supply to a load with a design current of 13A and a MCB size of 16A, reference method C with 3000mm thermal insulation.
3. A three-line supply to a DB with BS88 fuses 32A and a maximum demand of 27A, reference method E with 600mm of thermal insulation.
4. A three-line supply to a DB with BS88 fuses 32A and a maximum demand of 27A, reference method E without any thermal insulation.
In your own words how does thermal insulation affect the selection of cable? You may be required to read you answer out to the class
19
Grouping circuits - Cg
If a number of cables are installed together and each is carrying current, they will all warm up. Those which are on the outside of the group will be able to transmit heat outwards, but will be restricted in losing heat inwards towards other warm cables. Cables 'buried' in others near the centre of the group may find it impossible to shed heat at all, and will rise further in temperature. Due to this, cables installed in groups with others (for example, if enclosed in a conduit or trunking) are allowed to carry less current than similar cables clipped to, or lying on, a solid surface that can dissipate heat more easily. If surface mounted cables are touching the reduction in the current rating is, as would be expected, greater than if they are separated. The picture below illustrates the difficulty of dissipating heat in a group of cables.
A closely packed cable cannot easily dissipate heat and so its temperature rises
The symbol Cg is used to represent the factor used for de-rating cables to allow for grouping. Table 4C4 from BS7671 Correction factors for groups of more than one circuit shows some of the most common values of Cg. The grouping factors are based on the assumption that all cables in a group are carrying rated current. Note: If a cable is expected to carry no more than 30% of its grouped rated current, it can be ignored when calculating the group-rating factor. For example, if there are four circuits in a group but one will be carrying less than 30% of its grouped rating, the group may be calculated on the basis of having only three circuits.
Complete the questions on the next page to understand how grouping affects minimum cable ratings.
20
LEARNER WORK BOOK Here you will see how grouping circuits can affect the selection of cable. The perfect situation is no circuits grouped therefore Cg = 1.0.
In Iz = Cg
I n - term used to describe a circuits protection size in amps i.e. the fuse size. I z - term used to describe a circuits value, in amps, once all de-rating factors have been considered. C g term for the correction factor of grouping of circuits.
Using the table 4E4A and the Cg correction factors in your essential tables determine the minimum size of XLPE cable for each of the circuits below. Make note of the cable insulation type before you proceed with your calculations. You must write down: In (fuse size), Cg (correction factor), Iz (de-rated CCC), cable size (mm), It (tabulated CCC) and your working out.
1. A three-line supply to a socket with a design current of 32A and a MCB size of 32A, reference method E not grouped.
2. A three-line supply to a socket with a design current of 32A and a MCB size of 32A, reference method E (touching) and grouped with 7 circuits.
3. A single-line circuit with a 63A BS88 fuse protecting it, reference method E grouped with one other circuit.
4. A single-line circuit with a 63A BS88 fuse protecting it, reference method E and not grouped with any other circuit.
In your own words how does grouping circuits affect the selection of cable? You may be required to read you answer out to the class
21
In Iz = Cc
I n - term used to describe a circuits protection size in amps i.e. the fuse size. I z - term used to describe a circuits value, in amps, once all de-rating factors have been considered. C c term for the correction factor for the use of BS3036 fuses.
Using the table 4E4A in your essential tables determine the minimum size of XLPE cable for each of the circuits below. You must write down your formulas. Note that this only applies to circuits that use BS3036 fuses. You must write down: In (fuse size), Iz (de-rated CCC), cable size (mm), It (tabulated CCC) and your working out. 1. A three-line supply to a socket with a design current of 25A and a BS3036 size of 30A, reference method E.
2. A three-line supply to a socket with a design current of 25A and an MCB size of 32A, reference method E.
3. A single-line circuit with a 60A BS3036 fuse protecting it, reference method C.
4. A single line circuit with an old 60A BS88 fuse protecting it, reference method C
22
6%
8%
Public supplies are those that are supplied by the local authority (from the National Grid) where the consumer pays a bill for energy used. Private supplies are those where the consumer generates their own electricity (E.g. An onsite power generation plant such as a combined heating and power plant).
Public Supplies For lighting If the supply is single-line at the usual level of 230 V, this means a maximum volt drop of 3% of 230 V, which is 6.9 V. This means the voltage at the load is as low as 223.1 V. For a 400 V three-line system, allowable volt drop will be 12 V with a line load voltage as low as 388 V. For other uses (power, motors etc) If the supply is single-line at the usual level of 230 V, this means a maximum volt drop of 5% of 230 V, which is 11.5 V. This means the voltage at the load is as low as 218.5 V. For a 400 V three-line system, allowable volt drop will be 20 V with a line load voltage as low as 380 V.
23
Voltdrop =
Where:
Ib (mV / A / m ) L 1000
Ib = the design current in amps mV/A/m = the milli volts per amp per metre dropped L= the circuit length in metres 1000 = converts the millivolts into volts
Example A 4 mm p.v.c. sheathed circuit feeds a 6 kW shower and has a length of run of 16m. Find the total voltage drop. i) Work out the design current.
I=
ii)
From Table 4D5A the volt drop figure for 4 mm two-core cable is 11 mV/A/m. iii) Input all the values into the formula and work out the volt drop to two decimal places and add the value (V).
Voltdrop =
Since the permissible volt drop in this instance is 5% of 230 V, which is 11.5 V, the cable in question meets volt drop requirements.
24
Bigger cables
Smaller cables
D B 1
1.5 volts
D B 2
2.0 volts
D B 3
LOAD
4.4 volts
Ways that too much volt-drop can affect equipment can be seen as follows. While for a light bulb a large voltage drop will result in a harmless condition of slightly less bright light being produced, incorrect voltages supplied onto delicate circuitry (as for example in a DVD player, computer, and so forth) may quite easily result in an electrically damaging condition. It is quite easy to have a circuit well within the tabulated (I t) guidelines for its wiring, but whose voltage drop is too large. For these reasons we are required to size wiring not only for the total current to be drawn, but also to ensure that the total voltage drop shall not exceed the maximum percentage (%). This is particularly the case when running long lengths of cable from one end of a large building to another. A consumer unit at 60 meters from a main distribution board to which is intended to supply 30 amps should not necessarily be supplied with a 30 A cable. It may be found that the resistance per metre of the cable is of such a value that the load voltage would be below the required level.
Complete the questions on the next page to understand how voltage drop affects minimum cable ratings.
25
LEARNER WORK BOOK Using the tables in your Tables from the regulations and On-site Guide notes calculate the volt drops of the various circuits below. Make note of the cable insulation type before you proceed with your calculations. You must write down your formulas. You must record the table number, show your calculations and state whether the cable passes or fails the voltage drop requirement. 1. 20 metres of 1.5mm cable supplying a line line machine which carries 14 amps using Multi core 70 armoured C thermoplastic (p.v.c) insulated cable
2. 4.0mm three line supply, 40 metres in length to a 32A socket used for resistive loads only using Multi core 90 armoured thermosetting (x.l.p.e) C insulated cables
3. A single line lighting circuit to supply 10 x 100w lamps with 60 metres of 1.0mm using 70 thermoplastic (p.v.c) insulated and sheathed flat cable with protective conductor.
4. 80 metres of 1.5mm cable for a 10KW, three line load that has a power factor of 0.90 using Multi core 90 armoured C thermosetting (x.l.p.e) insulated cables
In your own words how does voltage drop affect the selection of cable? Look at the It values and compare them with the Ib / In values. Analyse your findings. You may be required to read you answer out to the class
26
Shock protection
Protection against shock is a massively important factor to consider when designing a circuit. A person in contact with a supply voltage for any length of time can be very harmful, as we have previously seen. We as designers need to ensure that this potential is limited to a very small amount of time by ensuring a faulty circuit disconnects automatically.
Note that there is no such thing as a three-line line/earth fault, although it is possible for three faults to occur on the three lines to earth simultaneously. As far as calculations for fault current are concerned, the voltage to earth for standard UK supplies is always 230 V, for both single-line and three-line systems. Thus the tables of maximum earth-fault loop impedance, which are given in the appendices, apply both to single- and to three-line systems.
27
1. A 230v supply is connected to a resistance of 20 ohms. What is the current? 2. A 230v supply with 3 amps of current flows in a circuit. What is the resistance? 3. A current of 12.5 amps flows through a resistance of 18 ohms. What is the supply voltage? 4. A 230v supply is connected to a resistance of 50 ohms. What is the current? 5. A 230v supply with 5 amps of current flows in a circuit. What is the resistance?
Q. Why is it called impedance when it clearly is just resistance? A. It is termed impedance because part of the circuit is the transformer or generator winding, which is inductive. This inductance, along with the resistance of the cables to and from the fault, makes up the impedance.
28
1. The circuit protective conductor 6. The line conductor supply from the transformer to the consumer unit
7. The final circuit live conductor 5. The supply transformer winding 3. The suppliers return path, either combined, separate or the general mass of earth 4. The earthed neutral of the supply transformer 2. The main earthing conductor and the consumers earthing terminal
29
LEARNER WORK BOOK Maximum values of earth loop impedance for various over-current protective devices are shown in Table 41.2, 41.3 & Table 41.4 in your Tables from the regulations and On-site Guide. Once the Zs has been established these tables are referred to ensure the designed circuit is in compliance. Turn to these tables now to get familiar with them. What is the maximum Zs allowable for a 6 amp BS EN60898 Type D device?
Complete the following exercise to determine whether the Zs values of the circuits listed comply with BS7671. You will need your Tables from BS7671 and the on-site guide appendices. You must state the maximum disconnection time for the circuit; record the maximum Zs and the table number; and state whether the cable passes or fails the shock protection requirement 1. A calculated value of earth loop impedance (Zs) equating to 8.5 for a circuit supplying portable equipment. With BS88 circuit protection rated at 6A. 2. A calculated Zs value of 1.2 for a circuit supplying portable equipment. With BS3036 circuit protection rated at 30A 3. A calculated calculated Zs value of 3.2 for a circuit supplying fixed equipment. With BS88 circuit protection rated at 16A 4. A calculated Zs value of 0.5 for a circuit supplying fixed equipment. With BS88 circuit protection rated at 100A 5. A calculated Zs value of 5.0 for a circuit supplying portable equipment. With BSEN60898 Type B circuit protection rated at 6A 6. A calculated Zs value of 5.0 for a circuit supplying portable equipment. With BSEN60898 Type C circuit protection rated at 6A 7. A calculated Zs value of 0.36 for a circuit supplying fixed equipment. With BSEN60898 Type D circuit protection rated at 32A 8. A calculated Zs value of 1.25 for a circuit supplying fixed equipment. With BSEN60898 Type B circuit protection rated at 40A Sizing Cables Conduit and Trunking REV4.1 30
Zs = Ze + (R1 + R 2 )
where
Zs - term used to describe a circuits earth fault loop impedance, in ohms. Ze - term used to describe part of the earth loop impedance that is external to the installation. R1 term used to describe the impedance of the line conductor, in ohms found in Table 9A R2 term used to describe the impedance of the circuit protective conductor, in ohms found in Table 9A Length length of circuit from supply to furthest point, in metres Table 9B or 9C Multiplier factor applied to allow for expected ambient temperature or conductor resistance at maximum operating temperature respectively
Zs = Ze + (R1 + R2) R1 Ze
R2
The actual Zs is the sum of all the impedances that are present in a circuits earth fault path. The Ze is something that we can either measure or obtain from our electricity provider and is expressed in ohms. Typical maximum values are: TN-C-S (PME) system 0.35 ohms, TN-S (cable sheath) 0.8 ohms, TT system 21 ohms
The R1 and R2 values are calculated in the following way. Table 9A from the On-site guide lists the resistances in milli-ohms per metre of all sizes of cables up to 25mm. Note that the values are in milli-ohms per metre. Table 9A values need to be converted into ohms (by dividing by 1000) so you can add it to Ze. Table 9B and 9C are multipliers that take into account the expected ambient temperature at the time of test or maximum operating temperature of conductors.
31
LEARNER WORK BOOK Multipliers are used by the designer and are required to allow for one of the following: Table 9B Used so the designer can give values of resistance at the ambient temperature expected during the tests (200C is classed as 1) Table 9C Used so the designer can give values of resistance at the conductors maximum operating temperatures
Example A circuit supplying a DB where a multi core armoured cable is clipped direct using 50 metres of multi core 25.0mm 70 armoured thermoplastic insulated cable. The C bunched CPC conductor size is 16.0mm. The Ze is 0.5 . Calculate the earth loop impedance in Ohms at the maximum operating temperature. i) Write down the formulas and obtain the values for each part.
Zs = Ze + (R1 + R 2 )
Ze = 0.5 ; R1+R2 must be calculated; L = 50m ii) Obtain the value for R1 and R2 in Ohms
Using Table 9A we can see that the resistance, in milli-ohms per metre, of 25.0mm and 16.0mm is 1.877m /m. iii) Obtain the multiplier value from table 9C
The line and earth conductors are part of a thermoplastic multicore cable so are classed as incorporated in a cable or bunched giving us a value of 1.20. Input all values into the R1+R2 formula
R1 + R 2 =
iv)
Input the values into the main Zs formula and calculate Zs at the maximum conductor operating temperature
Turn to Table 9A of your Tables from BS7671 and Onsite Guide and complete the questions on the next page to gain some understanding of earth loop impedance calculations.
32
LEARNER WORK BOOK Complete the following exercise to determine the earth loop impedance (Zs) of the circuits. Assume in all cases that the Ze = 0.3 . You will need your Tables from BS7671 and the onsite guide appendices. You must show all working out and state the R1 and R2 values and show what Zs is for each circuit.
1. A circuit supplying a DB using 50 metres of multi core 70 C armoured thermoplastic insulated cable. The line and earth conductors are both 25.0mm. What is the expected Zs at the maximum operating temperature?
2. A motor circuit where single core conductors are installed in p.v.c conduit using 40 metres of 90 thermosetting single core. C The line and earth conductors are both 4.0mm. What is the expected Zs at the maximum operating temperature? 3. A cooker circuit where 10m of cable is installed in building fabric using 70 thermoplastic (p.v.c) insulated and sheathed flat cable with protective conductor. The line and earth conductors are 6.0mm and 4.0mm respectively. What will be the expected Zs at 10oC? 4. A power circuit where a 2.5 mm cable is installed on a tray using multi core 90 armoured C thermosetting insulated cable. The circuit length is 80 metres. What will be the expected Zs at 5oC?
33
Uo If = Zs
I f - term used to describe a circuits earth fault current, in amps. U o - term used to describe the nominal voltage to earth, in volts. Z s term used to describe the earth fault loop impedance, in ohms.
Example A 230 V circuit is protected by a 15 A semi-enclosed (BS3036) fuse and has an earth-fault loop impedance of 1.6 Ohms. What will be the maximum earth fault current?
If =
This level of earth-fault current will cause the fuse to operate quickly. From the time / current trip curves in BS7671, Fig 3.2A (more on these next) the time taken for the fuse to operate will be about 0.15 s. Any load current in the circuit will be additional to the fault current and will cause the fuse to operate slightly more quickly. However, such load current must not be taken into account when deciding disconnection time, because it is possible that the load may not be connected when the fault occurs. Therefore if the earth loop impedance is higher this will restrict the flow of fault current meaning the protective device will take longer to operate. To gain some appreciation of fault current calculations complete the questions on the next page.
34
Complete the following exercise to determine the maximum earth fault current (If) of the circuits. Assume in all cases that the Ze = 0.3 . You must show all working out.
1. A circuit with a BS3036 overcurrent protective device rating of 30A has an R1+R2 value measured at 0.79 .
2. A power circuit with a BS88 overcurrent protective device rating of 32A has an R1+R2 value measured at 0.56 .
3. A BS88 63A fuse protects a feed to a three-line socket. The measured R1+R2 value is 0.2 .
4. A lighting circuit is protected by a BSEN60898 10amp Type B MCB. The measured R1+R2 value is 1.5 .
5. A radial power circuit is protected by a BSEN60898 32amp Type C MCB. The measured R1+R2 value is 0.8 .
35
Remember: Any circuit rated at 32A or less must disconnect within 0.4 seconds A distribution circuit or circuit exceeding 32A must disconnect within 5s
If you look at Fig.3.2A in your Tables from BS7671 and the on-site guide appendices you can see that current, in amps, is represented along the bottom (axis) and along the side (Y axis) is the time in seconds.
Each line between two points represents a value in the lower of the two units
Also available on each graph is a quick reference table that displays the main disconnection times and the required amount of current to achieve those times.
36
LEARNER WORK BOOK Example Find out the expected disconnection time of a circuit that is protected by a 30A BS3036 fuse when 70 amps of fault current flows. i) Obtain the correct time/current graph for the selected protective device from Appendix 3 of BS7671.
Look at Fig.3.2A. Find the 30amp BS3036 fuse trip characteristic line. ii) Identify the fault current value on the axis and follow it to the point where it crosses the selected fuse rating curve.
Identify 70 amps on the -axis. Follow 70 amps upwards until it crosses the 30amp curve. iii) At the point where the fault current crosses the fuse rating curve follow the line across to the Y axis. Identify the value of time in seconds.
Follow the point where 70amps crosses the fuse line and track it (left) to the Y axis and obtain the time. The disconnection time is expected to be 20 seconds. Complete the exercise below using the Tables from BS7671 and the on-site guide appendices to determine the operation times of different devices. Over-current device and rating BS3036 - 30 amp BS3036 - 20 amp BS88 32 amp BS88 63 amp BSEN60898 10amp Type B BSEN60898 32amp Type C BSEN60898 32amp Type D BS88 100 amp BS88 6 amp Prospective current (Amps) 100 70 260 450 300 300 300 400 18 Disconnection time (seconds)
What if the disconnection time is higher than the maximum allowed? What can the designer do to ensure that shock protection is afforded? You should now have a good grasp of the way we determine the disconnection times of a few devices based upon fault current levels.
37
Thermal Constraints
Now that you have chosen the type and size of cable to suit the conditions of the installation, we must look at thermal constraints. This is a check to make sure that the size of the c.p.c, the earth conductor, complies with the IEE Wiring Regulations. If there is a fault on the circuit, which could be a short circuit, or earth fault, a fault current of hundreds or thousands of amperes could flow. Imagine that this is a 1 mm or 2.5 mm cable; if this large amount of current was allowed to flow for a short period of time, i.e. a few seconds, the cable would melt and a fire would start. The c.s.a of the circuit protective conductor (c.p.c) is of great importance since the level of possible shock in the event of a fault depends on it. We need to check that the c.p.c will be large enough to be able to carry this fault current without causing any heat/fire damage. The formula that is used to check this situation is the adiabatic equation. The c.p.c will only need to carry the fault current for a short period of time, until the protective device operates. The cable calculation process at this point has ensured the selected cable will safely carry the design current and will disconnect in the required time therefore protecting the circuit from danger. The final stage of the calculation process is to confirm that the circuit protective conductor can withstand the fault current for a short space of time, for example 0.4 or 5 seconds at 230 volts. In very many cases, calculation of the CPC size will show that a smaller size than that detailed in is perfectly adequate. The adiabatic equation is:
I 2 t S= k
S - term used to describe the c.s.a of the circuit protective conductor, in mm. I - term used to describe the earth fault current, in amps. t term used to describe the time earth fault current will be present in the circuit, in seconds. k term used to describe the factor which takes into account the resistivity, temperature coefficient and heat capacity of the conductor material, and the appropriate initial and final temperatures. (See tables 54.1 to 54.6)
By using Ohms law the earth loop impedance value and the supply voltage are used to calculate how much fault current (I) will flow. The disconnection time of protective device is determined by using the fault current value and the correct time/current curve table from Appendix 3 of BS7671. K is determined by assessing what the CPC material is and how it is installed in relation to the line conductors.
38
LEARNER WORK BOOK Example Find out the minimum size of c.p.c in mm so that the 50A BS88 circuit complies with BS7671. The protective conductor is a copper conductor incorporated in a 90 C Thermosetting conductor cable. The calculated fault current is 300 amps.
S=
i)
I2 t k
Obtain all values for the adiabatic equation. I is either worked out as shown previously or declared t-is established using the graphs in Appendix 3 of BS7671 k- is established using the tables from Section 5 of BS7671
I is 300amps; t is 1 second (fig.3.3A); k is 100 (table 54.3) ii) Work out I x t first; then square root; then divide by the k value
Safety could always be assured if we assessed the size using Table 54.7 as a basis. However, this could result in a more expensive installation than necessary because we would often use protective conductors which are larger than those found to be acceptable by calculation So you can gain some more understanding complete the exercise on the next page to calculate the minimum size of C.P.Cs. You will need your Tables from BS7671 and the on-site guide appendices.
39
Once the cable calculation process has reached this stage the entire process is complete and the requirements of BS7671 have been met
40
1. Write down the formula to establish the total design current I b of in two types of circuit.
3. What four correction factors need to be taken into account when calculating the minimum size of a circuit conductor? Write down their symbols and descriptions
4. Once all these factors have been taken into consideration and we obtain I z what needs to be established next and what do we use to achieve it?
5. Once the circuit conductor has been selected we need to ensure that is complies with volt drop? Write down the formula and explain its parts.
6. Explain what shock protection is and state how we ensure it is adhered to. Write down the formula
7. Explain what thermal constraints are and state how we ensure it is adhered to. Write down the formula.
41
LEARNER WORK BOOK Full cable calculation Now complete a cable calculation and decide what cable size should be installed based upon a complete installation decided by the group. Make sure you consider all factors before you begin and write them in the boxes below. Then use the space below to carry out the calculations. Load details Type: Rating: Voltage: Supply details DB type: Ze value Cable Type Installation details
42
LEARNER WORK BOOK This page is for you the continuation of your calculation
1.
I=
2. 3.
P V
Select the protective device size Ib In Obtain all correction factors Find the values so they can be used in the next calcualion Ca, Cc, Cg, Ci Calculate Iz In divided by all factors
4.
Iz =
5.
In Ca Ci Cg Cc
Select conductor sizes With Iz use the tables in Appendix 4 and choose. Iz It Calculate volt drop Use design current, mV/A/m value from cable table, the circuit length then 1000
6.
Voltdrop =
7.
Ib (mV / A / m ) L 1000
Calculate R1+R2 Using table 9A, 9B and 9C find the m /m value 1000 then apply multipliers
R1 + R 2 =
8. 9. Calculate Zs
9A 9 B 9C = 1000
Zs = Ze + R1 + R 2 =
Verify Zs value with BS7671 Using the tables in Section 41 ensure calculated value is less than the tabulated value to ensure shock protection
10. Calculate the fault current Using nominal voltage and Zs Uo I= =A Zs 11. Establish the disconnection time Using the fault current, device type and time / current graphs in Appendix 3 obtain the expected disconnection time 12. Calculate minimum size of CPC Using the adiabatic formula, input all values (including k factor) and work out min. size of cpc. Then compare with our chosen cpc size
S=
I2 t k
13. Once all above has been verified the process is complete
43
Cables in conduit
Conduit Capacities
To calculate the number of cables that may be drawn into a conduit, we make use of four tables below. These have been adapted from the on-site guide to show the two most common conduit sizes used today. The conduit terms are shown in your Tables from BS7671 and the Onsite Guide.
Table 5A (Onsite guide) - Cable factors for conduit in short straight runs up to 3m Table 5B (Onsite guide) - Conduit factors for use in short straight runs up to 3m Table 5C (Onsite guide) - Cable factors for long straight runs over 3m, or runs of any length incorporating bends. Table 5D (Onsite guide) - Conduit factors for conduit incorporating bends and long straight runs
The number of cables that can be drawn into or laid in any enclosure of a wiring system must be such that no damage can occur to the cables or the enclosure during installation. The number of cables that can be used is the overall sum of the cables cross-sectional area (c.s.a) compared to the overall c.s.a of the trunking. This is expressed as a percentage and should not exceed 45 per cent. To calculate the required size of conduit we must first establish the amount of conductors to be installed. We must then obtain the individual terms for individual conductors and multiply them together. If we have 5 cables of one size we multiply the term for that cable by 5. We treat each size of conductor as an individual sum. Once we have obtained all the calculated terms we add them all together to give one total. We then refer to the relevant table and discover which conduit term is compatible. Bear in mind that the conduit term shown is the upper limit of spacing and should not be exceeded under any circumstances.
44
LEARNER WORK BOOK Complete the following conduit sizing exercise using the four tables listed above. You must record the cable factors, show your calculations and select the correct size conduit. All cables are stranded. See if you can make a guess before you calculate the answers. E.g Conduit 2.5 metres long without bends with 3 x 1.5mm and 3 x 2.5mm stranded conductors i) Select the correct table for the cable factors and conduit (5A) ii) Obtain the cable factors for each size of cable (1.5mm =31 and 2.5mm =43) iii) Multiply the number of cables by the factors (3x31)+(3x43)=222 iv) Select the correct table for the conduit factors and length of run (5B) v) Obtain the factor which is greater than the sum of cable factors (20mm=420) vi) The conduit size is 20mm 1. Conduit 2.5 metres long without bends with 6 x 1.5mm and 6 x 2.5mm
3. Conduit 6.0 metres long with one bend with 5 x 1.5mm and 3 x 4.0mm
7. Conduit 8.0 metres long with two bends with 5 x 1.5mm and 1 x 4.0mm
8. Conduit 2.0 metres long with one bend with one ring main and a single line 6.0 mm cooker supply
45
Trunking capacities
Minimum trunking size is calculated in much the same way as conduit although trunking has its own table of terms for single core cable. No consideration though, is paid to the length of run. The sizes should ensure an easy pull, with low risk of damage to cables and enclosures. The electrical effects of grouping are not taken into account. Therefore, as the number of circuits increases, the current-carrying capacity of the cables will decrease. Cable sizes would have to be increased with a consequent increase in cost of cable and trunking. It may therefore be more economical to divide the circuits concerned between two or more enclosures.
100x100
The tables show the factors for trunking having taken into consideration the maximum allowable 45% space factor. Sizes in bold are the most common trunking sizes available. The trunking terms are shown in your Tables from BS7671 and the Onsite Guide.
Table 5E (Onsite guide) - Cable factors for trunking Table 5F (Onsite guide) - Factors for trunking E.g. Trunking with 100 x 1.5mm and 100 x 2.5mm i) Obtain the cable factors for each size and type of cable (1.5mm =8.6 and 2.5mm =12.6) ii) Multiply the number of cables by the factors (100x8.6)+(100x12.6)=2120 iii) Obtain the factor which is greater than the sum of cable factors (75x75=2371) iv) The trunking size is 75mmx75mm
46
Complete the following trunking sizing exercise using the two tables above. You must record the cable factors, show your calculations and select the correct size trunking. All cables are stranded to BS6004.
2. A trunking installation with 12 x 1.5mm, 12 x 2.5mm, 9 x 4.0mm, 3 x 6.0mm , 3 x 10.0mm , 1 x 16.0mm and 2 x 25.0mm conductors.
3. A trunking installation with 18 x 1.5mm, 24 x 2.5mm, 12 x 4.0mm, 20 x 6.0mm , 12 x 10.0mm , 20 x 16.0mm and 15 x 25.0mm conductors.
4. A trunking installation with 10 single-line lighting circuits, 10 ring mains, 8 x A2 radial circuits (32A), 10 x 6.0mm SP&N circuits, 5 x 10.0mm TP&N circuits, 8 x 16.0mm TP&N circuits, 5 x TP&N DB supplies with 25.0mm conductors 1 x 25mm earthing conductor and 6 x 16.0mm Main equipotential bonding conductors
47
In most cases main or sub-main cables will supply a number and/or variety of final circuits. Use of the various loads must now be considered, otherwise if all the loads are totalled, a larger cable than necessary will be selected at considerable extra cost. Therefore a method of assessing the load must be used. This method is called applying diversity.
Maximum Demand
Maximum demand is the largest current normally carried by circuits, switches and protective devices under normal operating conditions. Assessment of maximum demand is sometimes straightforward. For example, the maximum demand of a 230V single-line 8 kW shower heater can be calculated by dividing the power (8 kW) by the voltage (230 V) to give a current of 34.78 A. There are times, however, when assessment of maximum demand is less obvious. For example, if a ring circuit with 15 x 13A sockets, the maximum demand clearly should not be 195A (15 x 13A). Some 13A sockets may feed table lamps with 60 W lamps fitted, whilst others may feed 3 kW washing machines; others again may not be loaded at all. Lighting circuits pose a special problem when determining maximum demand. Each lamp-holder must be assumed to carry the current of 0.43A per lamp (100 W per lamp holder). Discharge lamps are particularly difficult to assess, and current cannot be calculated simply by dividing lamp power by supply voltage. We have to multiply the total lamp power by 1.8 to allow for some losses. The reasons for this are: Control gear losses result in additional current, The power factor is usually less than unity so current is greater When assessing maximum demand, account must he taken of the possible growth in demand during the life of the installation. As a rule of thumb this is generally 20%. The maximum demand is the expected current that a circuit will carry.
When calculating the maximum demand of an installation of three ring mains what do you expect the value of current to be? Explain the reasoning behind your answer
48
Diversity
Diversity is defined as making a realistic estimate as to how much the maximum demand will be under an installations normal operating conditions. Appendix 1, Table 1B, of the IEE On-Site Guide contains the recommended diversity allowances, which allows diversity to be applied depending upon the type of load and installation premises. The individual circuit / load figures are added together to determine the total Assumed Current Demand for the installation. This value can then be used as the starting point to determine the rating of a suitable protective device and the size of cable, considering any influencing factors in a similar manner to that applied to final circuits. Please remember that the calculation of maximum demand is not an exact science and a suitably qualified electrical engineer may use other methods of calculating maximum demand. A domestic ring circuit feeds a large number of 13A sockets and is protected by a 32A fuse. If all sockets were feeding 13A loads, more than two of them in use at the same time would overload the circuit and its protective device would disconnect it. In practice, the chance of all domestic ring sockets feeding loads taking 13 A is small. Most sockets feed small loads such as table lamps, vacuum cleaner, television or audio machines and so on. The chances of all the sockets being used simultaneously are remote. The consideration that only a few sockets will be in use at the same time is called diversity.
By making allowance diversity, the number of circuits and their rating can be reduced, with a consequential financial saving. However, if diversity is over-estimated, the normal current demands will exceed the ratings of the protective devices, which will disconnect the circuits. Overheating may also result from overloading which exceeds the rating of the protective devices.
The sensible application of diversity to the design of an installation calls for experience and a detailed knowledge of the intended use of the installation. Future possible increase in load should also be taken into account. Diversity relies on a number of factors that can only be properly assessed by having a detailed knowledge of the type of installation and the habits and practices of the users. Not knowing how an installation is to be used could mean that installation conductors and equipment is under or over-rated We will now take a look at how diversity is implemented.
49
Point of utilization or current using equipment 2 amp sockets Lighting outlet Shaver outlet, bell transformer or any equipment rated 5 watts of less Household cooking appliance
Current demand to be assumed At least 0.5A Connected load, minimum 100 W May be neglected The first 10 A of the rated current plus 30% of the remainder plus 5A if the control unit incorporates a socket Rated current
All other stationary equipment Table 1A On site guide Current Demand to be assumed for points of utilization and current using equipment
Note 1 See Table 1B in your Tables from BS7671 and Onsite Guide for the design of other socket outlets. Note 2 Final circuits for discharge lighting take into to account harmonic currents and control gear losses. Where the exact manufacturers information for gear losses is not available the maximum demand shall be assumed to be 1.8 x the lamp rating. Work out the following current demands with and without diversity using table 1A above. Then in pairs discuss the implications of diversity both when done correctly and incorrectly.
Household cooker
Apart from indicating that diversity and maximum demand must be assessed, the Regulations themselves give little help. Suggestions of values for the allowances for diversity are given in Table 1B in your Tables from BS7671 and Onsite Guide.
50
LEARNER WORK BOOK Example diversity calculation We will now take a look at diversity on a larger scale by considering the example below. A shop has the following single-line loads, which are balanced as evenly as possible across the 400 V three-line supply.
Example Small Shop 1. 2. 3. 4. 5. 2 x 6 kW and 7 x 3kw thermostatically controlled water heaters 2 x 3 kW instantaneous water heaters 2 x 6 kW and 1 x 4 kW cookers 12 kW of discharge lighting (Sum of tube ratings) 8 x 32 A ring circuits feeding 13 A sockets.
Q. Calculate the total demand of the system, assuming that diversity can be applied. Calculations will be based on Table 1B. The single-line voltage for a 400V three-line system is 400 / 3 = 230 V. All loads with the exception of the discharge lighting can be assumed to be at unity power factor, so current may be calculated from:
P I= V
Where:
I P V
= the design current in amps = the circuit power in watts = the circuit voltage in volts
1. Water heaters (thermostatic) 2 x 6 kW and 7 x 3kw Table 1B states No diversity is allowable, so the total load will be:
P = (2 6 ) + (7 3)kW = 12 + 21 = 33kW
I=
2. Water heaters (instantaneous) 2 x 3 kW Table 1B states 100% of the largest and 100% of 2nd largest. So the total load will be:
51
3. Cookers 2 x 6 kW and 1 x 4 kW Table 1B states 100% of the largest and 80% of 2nd largest. 60% of remainder So the total load will be: First cooker
I=
I=
Second cooker
6000 80 = 26.08 A = 20.86 A 230 100 4000 60 = 17.39 A = 10.43 A 230 100
=57.37A
Third cooker
I=
4. Discharge lighting 12 kW Table 1B states 90% of total current demand So the total load will be:
I=
5. Ring circuits 8 x 32 A Table 1B states 100% of the largest and 50% of remainder So the total load will be: First ring main Remaining Ring mains
52
LEARNER WORK BOOK Total current demand after diversity is applied. Thermostatically controlled water heaters Instantaneous water heaters Cookers Discharge lighting Ring circuits feeding 13A sockets TOTAL
Therefore the switchgear we select can be rated to take 151.81 amps. In this instance we would select the next largest size of switchgear, which is 160 Amps.
If diversity hadnt been applied explain what would happen to the maximum demand and state the implications?
53
LEARNER WORK BOOK Now answer the question on diversity below A small hotel has the following single-line loads, which are balanced as evenly as possible across the 400 V three-line supply. EXAMPLE - SMALL HOTEL a. b. c. d. e. f. g. h. 10 kW of discharge lighting (Sum of tube ratings) 6 kW of low voltage lighting (cos = 0.95) 5 x 3kW thermostatically controlled water heaters 2 x 3 kW instantaneous water heaters 5 x 8.5 kW shower units 3 x 6 kW and 1 x 3 kW cookers 6 x 32A ring circuits feeding 13A sockets. 1 x 8 kW Under-floor heating
Calculate the total demand of the installation, assuming that diversity can be applied and work out the approximate balanced load across three lines. Calculations will be based on Table 1B. Use this and the next page for your working out.
54
LEARNER WORK BOOK This page has been left intentionally blank
55
3. Write down the formula for working out the current for a single-line discharge lighting circuit.
4. Explain what diversity is and how it is used with the maximum demand of a circuit.
6. Why is it important to have a good understanding of an installation when making allowances for diversity?
56