Professional Documents
Culture Documents
Table of Contents
FD, DFD, SSFD, SSDFD, & KFD Models Installation, Operation and Maintenance Instructions
11/2 and 3 Hour Curtain Fire Dampers Vertical and Horizontal Mount
FD, DFD, SSFD, & KFD models are intended for installation in accordance with fire damper requirements established by: National Fire Protection Association NFPA Standard 80, 90A, & 101 IBC International Building Code CSFM California State Fire Marshal Fire Damper Listing (#3225-0981:102) New York City (BSA/MEA listing #260-91-M)
UL CLASSIFIED (see complete marking on product) UL CLASSIFIED to Canadian safety standards (see complete marking on product) UL Standard 555 (Listing #R13317)
SAFETY WARNING:
Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment.
WARRANTY
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the shipment date. Any units or parts which prove to be defective during the warranty period will be repaired or replaced at our option. Greenheck shall not be liable for damages resulting from misapplication or misuse of its products. Greenheck will not be responsible for any installation or removal costs. Greenheck will not be responsible for any service work or backcharges without prior written authorization.
Refer to the appropriate Greenheck installation supplements for special requirements: Close Indicator Switch Concrete Floor with Steel Deck Drive Slip Breakaway Connection Fire Resistant Ventilated Duct Assembly Firestop Material Greenheck Test Switch Grille Installation Metal Stud in Shaftwall Quick Connect Breakaway Connections Sealant Supplement Single Side Retaining Angle Single 3-Sided Retaining Angle - Vertical Mount Sleeve Extension Support Mullions Note: Refer to Greenheck IOM, Part #461335, for CFSD models to be installed in corridor ceiling applications. These instructions apply to 11/2 and 3 hour rated fire dampers mounted (blades must be horizontal) in masonry, block or stud walls and concrete floors. Specific requirements in these instructions are mandatory. These instructions meet the requirements of UL 555. Installation shall comply with the requirements of NFPA 90A Standard for the Installation of Air Conditioning and Ventilating Systems. UL listing R13317, California State Fire Marshal listings 3225-0981:102, and New York City BSA/MEA listing 260-91-M apply to these dampers. Note: Fire dampers are manufactured and labelled for either vertical or horizontal installation. The dampers must be installed in accordance with the labelling.
Installation Supplements
Due to continuing research, Greenheck reserves the right to change specifications without notice.
This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the job is complete.
Table of Contents
Pre-Installation Guidelines..............................................................................................................................................................3 Installation ...................................................................................................................................................................................3-8 Clearances Required Between Fire Damper Sleeves and Wall/Floor Openings............................................................3 Sleeve Length and Wall Thickness .............................................................. .............................................................4-5 Duct to Sleeve Connections ..........................................................................................................................................6 Securing the Damper/Sleeve Assembly to Wall and Floor Openings ....................................................... .....................6 Installing Multiple Damper Section Assemblies ...........................................................................................................7 Recommended Preparation of Openings in Wood and Metal Stud Walls ......................................................................8 Breakaway Connections .................................................................... ...........................................................................8
Pre-Installation Guidelines
The basic intent of a proper installation is to secure the fire damper in, not to, the opening in such a manner as to prevent distortion and disruption of damper operation. This is accomplished by allowing the fire damper in rated separation openings to expand and for the connecting duct to separate in the event of the collapse of the hanging system. The following items will aid in completing the damper installation in a timely and effective manner. 1) Check the schedules for proper damper locations within the building. Visually inspect the damper for damage and verify that the fusible link is in place or has not activated. Never install a fire damper without the proper UL approved fusible link in place. If damper is furnished with fusible link, visually inspect the link to verify its not missing or broken. Replace link as necessary. Lift or handle damper using sleeve or frame. Do not lift damper using blades. Damper has label on outside of sleeve indicating a No Screw area. Do not install screws into this area as screws may interfere with unexposed blade linkage and prevent damper blades from opening and/or closing. Damper has label indicating position of damper and sleeve assembly in the wall. Install accordingly to comply with manufacturers appropriate UL Classification file number. Damper must be installed into duct or opening square and free of twist or other misalignment. Damper must not be squeezed or stretched into duct or opening. Out of square, racked, twisted or misaligned installations can 8) 6)
cause excessive leakage and/or torque requirements to exceed damper/actuator design. Damper must be kept clean and protected from dirt, dust and other foreign materials prior to and after installation. Examples of such foreign materials include but are not limited to: a) Mortar dust b) Drywall dust c) Firesafing materials d) Wall texture e) Paint overspray 7) Damper should be sufficiently covered as to prevent overspray if wall texturing or spray painting will be performed within 5 feet of the damper. Excessive dirt or foreign material deposits on damper can cause excessive leakage and/or torque requirements to exceed damper/ actuator design. Caulking is not necessary, nor is it allowed, between the damper sleeve and the wall or floor opening (annular space). However, caulking may be applied to the retaining angles. ACCESS: Suitable access (such that fusible links can be maintained, etc.) must be provided for damper inspection and servicing. Where it is not possible to achieve sufficient size access, it will be necessary to install a removable section of duct. (Refer to NFPA 90A).
2) 3)
4)
9)
5)
10) The Code Authority Having Jurisdiction (AHJ) must evaluate and provide approval of final installation where variations to these instructions are necessary.
Fire damper and sleeve assemblies expand during periods of intense heat. Therefore it is essential that openings in walls or floors be larger than the fire damper and sleeve assembly to allow for this expansion. Minimum clearances required between the outside of fire damper sleeve assemblies and wall/floor openings are: alvanized steel fire dampers and sleeves: 1/8 in. G (3mm) per foot of damper width and 1/8 in. (3mm) per foot height with a minimum clearance of 1/4 in. (6mm) Recommended clearances, for width and/or height dimensions of: 1) 48 in. (1219mm) or less: 1/2 in. (13mm) clearance 2) More than 48 in. (1219mm) and 96 in. (2438mm) or less: 1 in. (25mm) clearance
3) More than 96 in. (2438mm): 11/2 in. (38mm) clearance tainless steel fire dampers and stainless steel or S galvanized sleeves: 3/16 in. (4.8mm) per foot of damper width and height with a minimum clearance of 1/4 in. (6mm), maximum of 2 in. (51mm). Recommended clearances, for width and/or height dimensions of: 1) 48 in. (1219mm) or less: 3/4 in. (19mm) clearance 2) More than 48 in. (1219mm) and 96 in. (2438mm) or less: 1 1/2 in. (38mm) clearance 3) More than 96 in. (2438mm): 2 in. (51mm) clearance These are total clearances (ignoring fastener heads) and do not need to be equally spaced around the damper. Refer to Section 4 and Figure 6 for additional installation considerations.
Example:
A 12 in. x 12 in. (305mm x 305mm) damper would require a minimum clearance of 1/4 in. (6mm) on width and 1/4 in. (6mm) on height A 48 in. x 12 in. (1219mm x 305mm) damper would require a minimum clearance of 1/2 in. (13mm) on width and 1/4 in. (6mm) on height.
Wall or oor
See Section 2
See Section 2
All fire dampers must be installed in a steel sleeve of the required gauge and length. See Table 1 for required minimum sleeve gauges. Maximum sleeve thickness is 10 gauge (3.5mm). Sleeve inside dimensions must equal damper outside dimensions. Sleeves shall extend a maximum of 6 in. (152mm) beyond the wall or floor opening on each side ( see Figure 1). When an access door is incorporated as a part of sleeve, the sleeve may extend a maximum of 16 in. (406mm) beyond the wall or floor opening on the access door side.
Damper
1 t (S
Type A
Sleeve Gauge
14 ga. (0.075 in.) - 10 ga. (0.138 in.) [2mm - 3.5mm] 16 ga. (0.060 in.) [1.5mm] 16 ga. (0.060 in.) [1.5mm] 18 ga. (0.048 in.) [1.2mm] 20 ga. (0.036 in.) [0.9mm] 22 ga. (.030 in.) [0.76mm] 24 ga. (0.024) [0.6mm] 26 ga. (0.018 in.) [0.46mm]
Duct Dimension
Wall or oor
Sleeve
All duct sizes 36 in. (914mm) max. width 24 in. (610mm) max. width 24 in. (610mm) diameter All duct sizes 85 in. (2159mm) wide and over 55 in. - 84 in. wide (1397mm - 2134mm) 31 in. - 54 in. wide (787mm - 1372mm) 13 in. - 30 in. wide (330mm - 762mm) 12 in. wide and under (305mm)
Damper
Duct
Type B
Breakaway only
On types R & CR factory furnished duct collar qualies as breakaway conneciton (See Section 5)
Wall or oor
Damper
Sleeve thickness must not be less than the gauge of the connecting duct. UL Standard 555 requires all ducts to terminate at fire damper sleeves.
When dampers installed vertically, the blade stack must be on the top..
Figure 1
1/4 in. minimum Vertical mount with factory total clearance mounted sleeve
Wall or Floor
See Section 2
See Section 2
Duct
Duct
Damper
Damper
Type A
Maximum 6 in.
Damper
Retaining angles (See Section 4)
See Section 2
K side
Wall or Floor
Duct
Duct
Duct
See Section 2 Damper Duct Sleeve (See Sections 2 & 3)
Type B
Damper
Type B
Type A
On types R, CO & CR factory Type furnished duct collar qualies as breakaway connection.
Wall or Floor
Wall or Floor Damper
Damper
Type B
Damper
Damper
Damper
Wall or Floor
Duct
Duct
Damper
Duct
Type C, CO, CR, & R
Sleeve
Sleeve
Sleeve
Sleeve
Wall or oor
Type B
Type B2
K side Wall or oor
Wall or oor
Wall or oor
Duct
Type B2 Damper Duct On types R, CO & CR factory furnished duct collar qualies as breakaway Wall or Floor connection. Type C, CO, CR, & R
Sleeve
K side Wall or oor
On types R & CR factory furnished duct collar qualies as breakaway connection, see Section 5 Type C, CO, CR, & R
Sleeve
On types R & CR factory furnished duct collar qualies as breakaway connection, see Section 5
Duct
Damper
Type C, CO, CR, & R
When dampers installed horizontally, the ramp must be positioned up as shown in above drawings.
Figure 1
When dampers installed vertically, the blade stack must be on the top.
When dampers installed horizontally, the ramp must be positioned up as shown in above drawings.
Fire dampers must be attached to sleeves as shown in Figure 3. All four sides of the damper frame must be attached to the sleeve with one row of attachments on each side of the blade channel. Attachments must be spaced a maximum of 6 in. (152mm) on centers and a maximum of 2 in. (51mm) from corners. A minimum of 4 attachments (2 on each side of the blade channel ) per side ( 16 per damper) are required. One of the methods of attachment shown below must be used. tack or spot welds #10 sheet metal screws 1/4 in. (6mm) bolts and nuts 3/16 in. (4.7mm) steel pop rivets
The fire damper must be installed such that the centerline of the blades are mounted in the plane of the wall or floor. Fire damper and sleeve assemblies must be installed in wall and floor openings using retaining angles on each side of the wall or floor as described below: Retaining angles for 11/2 hour rated dampers with a width and height 48 in. (1219mm) or less must be a minimum of 20 ga. (1mm). Retaining angles for all 3 hour rated dampers and all dampers with a width or height greater than 48 in. (1219mm) must be a minimum of 16 gauge (1.5mm). The leg of the retaining angle on the damper sleeve shall be a minimum of 11/4 in. (32mm). The leg of the retaining angle on the wall/floor shall be long enough to cover the annular space and overlap the wall/floor by a minimum of 1 in. (25mm). (See Figure 4). Retaining angle legs may be reversed with leg of retaining angle with annular space of opening so angle and sleeve is flush against barrier. etaining angles must be attached to the sleeve using R the procedures and methods described in Section 3. The angles must be attached to all 4 sides of the sleeve with butt joints at each corner. A minimum of two attachments are required on each side, top and bottom. The angles need not be attached to each other at the corners. etaining angles should not be fastened to the wall / R floor material. The angles should only sandwich the wall /floor and allow for damper/sleeve expansion during periods of intense heat. For single retaining angle applications, see Single Side Retaining Angle Supplement (#474015).
Blade Channel
Retaining Angle
Openings where duct does not attach on either side will not require a breakaway connection. Transfer openings are typical of a non-ducted installation (see Figure 2). leeve may end flush with the rated wall/floor on both S sides efer to Section 4 for securing retaining angles to R sleeves.
2 in. Max .
Duct
6 in. M
ax.
Damper
5. CONNECTING DUCTS TO FIRE DAMPER SLEEVE Any duct connection other than breakaway is considered rigid. The connections shown on this page are considered breakaway. Factory furnished duct collars on type R and CR fire dampers are also considered breakaway (see Figure 1).
6 in. M
ax.
2 in.
Max
6. MULTIPLE SECTION FIRE DAMPERS When multiple sections are shipped unassembled, installer shall fasten dampers together as described in Section 3. Table 2 shows maximum sizes for multiple section dampers. Dampers that are two or more sections tall must be factory assembled.
Damper Model FD-110 (H or V), FD-300/350 (V) FD-310/355 (V) FD-150/155 (V) KFD-110 (H or V) FD-150/155 (H or V), SSFD-150/155 (V) KFD-150 SSFD-150/155 (H) SSFD-355 (V) FD-350/355 (H) KFD-350 (H) KFD-310/350 (V) SSKFD-350/355 FD-150/155 (V) FD-100 (V), SSFD-350 (V) DFD-150/155 (V) DFD-150/155 (V) DFD-110 (V) DFD-310/350/355 (V) DFD-150/155 (V) DFD-110 (H), SSDFD-X5X (V) DFD-350/355 (V) DFD-150/155 (H), DFD-350/355 (H) DFD-150/155,(H), DFD-350/355 (H) Maximum Damper Single Section Sizes* 48 X 48 (1219mm x 1219mm) 48 X 48 (1219mm x 1219mm) 36 X 16 (914mm x 406mm) 48 X 48 (1219mm x 1219mm) 36 X 16 (914mm x 406mm) 36 X 36 (914mm x 914mm) 40 X 40 (1016mm x 1016mm) 36 X16 (914mm x 406mm) 36 X 16 (914mm x 406mm) 37 X 37 (940mm x 940mm) 48 X 48 (1219mm x 1219mm) 24 X 24 (610mm x 610mm) 30 X 30 (762mm x 762mm) 36 X 36 (914mm x 914mm) 30 X 30 (762mm x 762mm) 24 X 24 (610mm x 610mm) 30 X 30 (762mm x 762mm) 24 X 18 (610mm x 457mm) Maximum Overall Size for Multi-Section Dampers* 96 X 48 (2438mm x 1219mm) 96 X 48 (2438mm x 1219mm) or 120 X 40 (3048mm x 1016mm) 96 X 48 (2438mm x 1219mm )or 120 X 40 (3048mm x 1016mm) 80 X 40 (2032mm x 1016mm) 80 X 40 (2032mm x 1016mm) 74 X 74 (1880mm x 1880mm) 72 X 48 (1829mm x 1219mm) 60 X 60 (1524mm x 1524mm) 48 X 48 (1219mm x 1219mm) 48 X 36 (1219mm x 914mm) 48 X 36 (1219mm x 914mm)
Note: V=Vertical Mount and H=Horizontal Mount. All dimensions shown are in inches. * Sizes listed is the damper size not transition size.
Table 2:
Maximum section sizes and overall sizes for multiple section dampers.
DUCT-SLEEVE CONNECTIONS
Traditional Breakaway Style Transverse Joints
Transverse joints illustrated in Figure 5 have always been approved as breakaway connections. SMACNA testing has also approved the following variations as breakaway connections. he breakaway connections shown to the right can be T applied with maximum of (2) #10 sheet metal screws on each side and on the bottom located in the center of the slip pocket and penetrating both sides of the slip pocket. ransverse joints illustrated can T be applied as top and bottom joints with Drive Slip - side joints in duct heights up to 20 inches Drive Slip Joint (508mm). Round ducts connected to factory supplied Type R or CR damper collars may use #10 sheet metal screws as follows: ucts 22 in. (559mm) wide (or dia.) and smaller may use 3 D screws. ucts larger than 22 in. (559mm) wide (or dia.) may use 5 D screws. NOTE: All breakaway connections described may have duct sealant applied, PA2084T duct sealant adhesive manufactured by Precision or DP1010 water base duct sealant by Design Polymetrics, Grey Pookie or Ductmate PROseal in accordance with SMACNA recommendations.
Plain S Slip Hemmed S Slip Double S Slip
Standing S
Standing S (Alt.)
Standing S (Alt.)
Figure 5:
Fire Damper Sleeve 6 in. long 1/16 in. max. thickness plastic cleats; 12 in. c-c (min. 1 per side) Flanged system angles
Flanged connection systems manufactured by Ductmate, Ward, and Nexus are approved as breakaway connections when installed as illustrated in Figure 6.
Clip Spacing
6 in. 60 in. Duct 4 Reqd. 48 in. Duct 3 Reqd. Sleeve Duct 36 in. Duct 3 Reqd. 24 in. Duct 2 Reqd. 18 in. Duct & Smaller 1 Reqd. 7 in.
5 in.
5 in.
5 in.
5 in.
C L Duct
Recommended Preparation of Openings in Wood and Metal Stud Walls Frame wall openings as shown in Figure 8. Double vertical studs are not required for openings 36 in. x 36 in. (914mm x 914mm) or smaller. Double horizontal studs may be used to frame opening. Gypsum wall board must be fastened 12 in. (305mm) on center to all stud and runner flanges surrounding opening (see Figure 11). All construction and fasteners must meet the requirements of the appropriate wall design. (See UL Fire Resistance Directory)
24 in. o.c. Maximum (metal studs) 24 in. o.c. Maximum (metal studs) Ceiling Runner
12 in.
Stud or Runner
2 in. (51mm) 2 Panhead Screws
Retaining Angle
2 in. (51mm)
Damper Sleeve
Floor Runner
In metal stud construction, exposed steel surfaces need not be covered with gypsum wallboard.
Damper Sleeve
In metal stud construction, exposed steel surfaces need not be covered with gypsum wallboard.
Damper Sleeve
In wood stud construction, gypsum wallboard must cover all wood stud surfaces.
Figure 9: Detail of retaining angles and gypsum board application for metal and wooden stud construction.
Wooden Stud Construction
Gypsum Wallboard
Copyright 2011 Greenheck Fan Corporation 452763 FD/DFD Rev. 14 Sept 2011
Stud or Runner
Table of Contents
FD and DFD 150X Series models are intended for installation in accordance with fire damper requirements established by: National Fire Protection Association S T ING LI NFPA Standard 80, 90A, & 101 IBC International Building Codes SE CSFM California State Fire Marshal R VIC E Fire Damper Listing (#3225-0981:102) New York City (BSA/MEA listing #260-91-M)
E
CALIFOR OF
NIA
S TAT
FI
RE
M AR S H
UL CLASSIFIED (see complete marking on product) UL CLASSIFIED to Canadian safety standards (see complete marking on product) UL Standard 555 (Listing #R13317)
INSTALLATION SUPPLEMENTS
Refer to the appropriate Greenheck installation supplements for special requirements: Support Mullions Shaftwall Supplement Drywall Supplement Grille Installation Supplement Drive Slip Supplement Sealant Supplement Sleeve Extension Supplement Single sinde Retaining Angles Supplement Note: Refer to Greenheck IOM, Part #461335, for CFSD models to be installed in corridor ceiling applications. Refer to Greenheck IOM, Part # 452763 for standard DFD and FD models.
SAFETY WARNING:
Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment.
WARRANTY
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the shipment date. Any units or parts which prove to be defective during the warranty period will be repaired or replaced at our option. Greenheck shall not be liable for damages resulting from misapplication or misuse of its products. Greenheck will not be responsible for any installation or removal costs. Greenheck will not be responsible for any service work or backcharges without prior written authorization.
This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the job is complete. Due to continuing research, Greenheck reserves the right to change specifications without notice.
AL
S TAT
Table of Contents
Pre-Installation Guidelines .........................................................................................................................................9 Installation ...........................................................................................................................................................10-12 Breakaway Connections ..........................................................................................................................................13 Damper Maintenance ...............................................................................................................................................15 Damper Troubleshooting..........................................................................................................................................15 Installation for Steel Stud Connection Option ...................................................................................................14-15
Pre-Installation Guidelines
The basic intent of a proper installation is to secure the fire damper in, not to, the opening in such a manner as to prevent distortion and disruption of damper operation. This is accomplished by allowing the fire damper in rated separation openings to expand and for the connecting duct to separate in the event of the collapse of the hanging system. The following items will aid in completing the damper installation in a timely and effective manner. 1. Check the schedules for proper damper locations within the building. Visually inspect the damper for damage and verify that the fusible link is in place or has not separated. If fusible link is not present or has separated, replace link. Never install a fire damper without the proper UL approved fusible link in place. (Fusible link is standard control option. An electric link may have been provided.) 2. Lift or handle damper using sleeve or frame. 3. Install damper accordingly to comply with manufacturers appropriate UL procedure file number. 4. Damper must be installed into duct or opening square and free of twist or other misalignment. Damper must not be squeezed or stretched into duct or opening. 5. Damper must be kept clean and protected from dirt, dust and other foreign materials prior to and after installation. Examples of such foreign materials include, but are not limited to: a. Mortar dust b. Drywall dust c. Firesafing materials d. Wall texture e. Paint overspray 6. Damper should be sufficiently covered as to prevent overspray of spray-on insulating, wall texturing, or spray painting when performed within 5 feet of the damper. Excessive dirt or foreign material deposits can cause damper to bind and not operate properly. 7. Caulking is not necessary, nor is it allowed, between the damper sleeve and the wall or floor opening (annular space). However, caulking may be applied to the retaining angles. 8. ACCESS: Suitable access (such that fusible links can be changed) must be provided for damper inspection and servicing. Where it is not possible to achieve sufficient size access, it will be necessary to install a removable section of duct. (Refer to NFPA 90A). 9. The Code Authority Having Jurisdiction (AHJ) must evaluate and provide approval of final installation where variations to these instructions are necessary.
Installation -
These instructions apply to 11/2 hour rated fire dampers mounted in masonry, block or stud walls and concrete floors. Specific requirements in these instructions are mandatory. These instructions meet the requirements of UL 555. Installation shall comply with the requirements of NFPA 90A Standard for the Installation of Air Conditioning and Ventilating Systems. U.L. listing R13317, California State Fire Marshal listings 3225-981:102, and New York City BSA/MEA listing 260-91-M as they apply to these dampers. Note: Fire dampers are manufactured and labelled for either vertical or horizontal installation. The dampers must be installed in accordance with the labelling.
10
Galvanized steel fire dampers and sleeves: 1/8 in. (3mm) per linear foot of damper width and height with a minimum clearance of 1/4 in. (6mm) .Recommended clearances, for width and/or height dimensions of: 1) 48 in. (1219mm) or less: 1/2 in. (13mm) clearance 2) More than 48 in. (1219mm) and 96 in. (2438mm) or less: 1 in. (25mm) clearance 3) More than 96 in. (2438mm): 11/2 in. (38mm) clearance These are total clearances (ignoring fastener heads) and do not need to be equally spaced around the damper. Refer to Section 3 and Figure 1 for additional installation considerations.
Retaining Angle
2 in 6 in
Duct
. M ax.
. M ax.
Damper
6 in
Example:
A 12 in. x 12 in. (305mm x 305mm) damper would require a minimum clearance of 1/4 in. (6mm). A 48 in. x 12 in. (1219mm x 305mm) damper would require a minimum clearance of 1/2 in. (13mm) on width and 1/4 in. (6mm) on height.
. M ax.
2 in
. M ax
*only applicable for damper sizes above 36 in. x 36 in. 1/4 in. minimum
total clearance
6 in.
Duct Duct
Damper
Damper Damper
Type A
Type A
Type A
Wall or Floor
Wall or Floor
Wall or Floor
Damper Damper
Damper
Duct
Duct Duct
On types R & CR factory On furnished& CR collar types R duct factory furnished ductbreakaway qualies as collar qualies as breakaway connection.
Type B Type B
Wall or Floor
Wall or Floor
connection.
Duct
Damper
Duct
Damper
Duct
Type C, CO, CR, & R
Damper
11
Figure 2: Vertical Mount Type A, R Type C, CO, CR, & Type B, and Type C, CO, CR, R damper installation diagrams.
Damper Model
Retaining Angles (See Section 4)
Maximum Sizes for Single Section Dampers* in. (mm) 48 x 48 (1219 x 1219)
Maximum Overall Size for MultiSection Dampers* in. (mm) 96 x 48 or 120 x 40 ((2438 x 1219) or (3048 x 1016) 72 x 48 or 60 x 60 (1829 x 1219) or (1524 x 1524) 48 x 36 (1219 x 914)
FD-150X (H or V)
See Section 2 K side Wall or Floor
DFD-150X (V)
36 x 36 (914 x 914)
DFD-150X (H)
30 x 30 (762 x 762)
Duct
Note: V = Vertical mount & H = Horizontal * Sizes are based on damper with no transitions.
Type A
Table 1:
Duct
Type B
Duct
ll construction and fasteners must meet then A requirements of the appropriate wall design. (See UL Fire Resistance Directory)
K side
Wall or oor
Sleeve
Ceiling Runner
12 in.
On types R & CR factory furnished duct collar qualies as breakaway connection, see Section 5
Figure 3: Horizontal Mount Type A, Type B, and Type C, CO, CR, R damper installation diagrams.
2 Panhead Screws 2 in. (51mm) 2 in. (51mm)
Floor Runner
12
Damper Sleeve
In metal stud construction, exposed steel surfaces need not be covered with gypsum wallboard.
Damper Sleeve
In wood stud construction, gypsum wallboard must cover all wood stud surfaces.
Figure 5: Detail of retaining angles and gypsum board application for metal and wooden stud construction.
Duct-Sleeve Connections
Wooden Stud Construction Traditional Breakaway Style Transverse Joints Transverse joints illustrated in Figure 6 have always been Gypsum Wa llboard approved as breakaway connections. SMACNA testing has also approved the following variations as breakaway connections.
Stud or Runner he breakaway connections shown to the right can be T applied with maximum of (2) #10 sheet metal screws on each side and on the bottom located in the center of the slip pocket and penetrating both sides of the Retaining Angl e slip pocket.
Plain S Slip
Hemmed S Slip
Double S Slip
Standing S
Standing S (Alt.)
1 in. Min. ransverse joints illustrated can T be applied as top and bottom joints with Drive Slip - side Drive Slip Joint In wood stud construction, Damper joints in duct heights up to 20 in. Sleeve gypsum wallboard must cover (508mm). all wood stud surfaces. Round and Oval Duct Breakaway Connections Round or flat oval ducts connected to factory supplied Type R, CR, or CO damper collars may use #10 sheet metal screws as follows: ucts 22 in. (559mm) wide (or dia.) and smaller may D use 3 screws. ucts larger than 22 in. (559mm) wide (or dia.) may D use 5 screws.
Standing S (Alt.)
Proprietary Flange System Breakaway Connections (Ductmate, Ward, Nexus) Flanged connection systems manufactured by Ductmate, Ward, and Nexus are approved as breakaway connections when installed as illustrated in Figure 7.
Fire Damper Sleeve 6 in. long 1/16 in. max. thickness plastic cleats; 12 in. c-c (min. 1 per side) Flanged system angles
Figure 7:
13
(TDC by Lockformer, TDF by Engle) TDC and TDF systems are approved as breakaway connections when installed as described in the SMACNA Duct Construction Standards. Standard 6 in. metal clips may be used with spacing (see Figure 8). Three-eighth in. metal bolts and nuts may be used to fasten together corner pieces (see Figure 9).
Clip Spacing
6 in. 60 in. Duct 4 Reqd. 48 in. Duct 3 Reqd. Sleeve Duct 36 in. Duct 3 Reqd. 24 in. Duct 2 Reqd. 18 in. Duct & Smaller 1 Reqd. 7 in. Std. Clip Length 6 in.
Corner Piece
5 in.
5 in.
5 in.
5 in.
C L Duct
Figure 8:
2. INSTALLATION
Fire damper with SSC option must be in place before the wall is constructed or it can be installed as the wall is being constructed. Wall opening is framed around the fire damper before sheet rock or other wall board material is applied to the steel studs. This installation provides appropriate protection for duct penetrations in fire resistant wall construction using steel studs with a fire resistance rating less than 3 hours. The following wall design numbers (as detailed in the UL Fire Resistance Directory) are appropriate for fire damper installations using this SSC option: 1 Hour Design: U405, U406, U422, U434, U448, U451, U456, U457, U465, U468, U469, U485, U494 11/2 Hour Design: U449, U452, U470, U471 2 Hour Design: U403, U411, U412, U421, U425, U428, U429, U443, U453, U474, U475, U477, U484, U491, U495
14
Item 1 2 3 4 5 6
Steel stud wall (see UL Fire Resistance Directory for specifc details) Steel stud frame around opening in wall Duct connection (see section 6)
2 Retaining Bar 3
Wallboard (see UL Fire Resistance Directory for specific details) Fasteners (see UL Fire Resistance Directory and Section 5)
3
Sid of
3 6
Retaining Bar
3
Top Cross-section View
Damper Maintenance
Dampers shall be maintained, cycled, and tested in intervals as stated in the latest editions of NFPA 90A, 92A, and UL 864 unless local codes require more frequent inspections. Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild detergents or solvents. If lubrication is desired, do not use oil-based lubricants or any other lubricants that attract 3 contaminants such as dust.
6
Symptom Retaining Bar Damper does not fully open and/or fully close
Possible Cause 1 Frame is 'racked' causing blades to bind on jamb Screws in damper linkage Contaminant's on damper 4 Heat 2
Corrective Action 4 Adjust frame such that it is square and plumb Locate screws and remove Clean with a non-oil based solvent (see Damper Maintenance)
Copyright 2008 Greenheck Fan Corporation 453946 FD/DFD 150X series R12 December 2008
15
Table of Contents
UL CLASSIFIED (see complete marking on product) UL CLASSIFIED to Canadian safety standards (see complete marking on product) UL Standard 555 (Classification #R13317)
SAFETY WARNING:
Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment.
WARRANTY
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the shipment date. Any units or parts which prove to be defective during the warranty period will be repaired or replaced at our option. Greenheck shall not be liable for damages resulting from misapplication or misuse of its products. Greenheck will not be responsible for any installation or removal costs. Greenheck will not be responsible for any service work or backcharges without prior written authorization.
INSTALLATION SUPPLEMENTS
Refer to the appropriate Greenheck installation supplements for special rquirements: Steel Deck Supplement
Due to continuing research, Greenheck reserves the right to change specifications without notice.
This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the job is complete.
16
Table of Contents
Pre-Installation Guidelines ...................................................................................17 Installation .......................................................................................................17-19 Maintenance .........................................................................................................19 Troubleshooting ....................................................................................................19
Pre-Installation Guidelines
The basic intent of a proper installation is to secure the fire damper in the opening in such a manner as to prevent distortion and disruption of damper operation. This is accomplished by allowing the fire damper in rated separation openings to expand and for the connecting duct to separate in the event of the collapse of the hanging system. The following items will aid in completing the damper installation in a timely and effective manner. 1) Check the schedules for proper damper locations within the building. Visually inspect the damper for damage and verify that the fusible link is in place or has not separated. Dampers will be supplied with a temperature responsive fusible link device. If fusible link is not present or has separated, replace link. Never install a fire damper without the proper UL approved fusible link in place. 2) Lift or handle damper using the frame. Do not lift damper using blades. 3) Do not install screws into the main body area of the damper frame as screws may interfere with and prevent damper blade from opening and/or closing. 4) Damper must be installed into duct or opening free of distortion or other misalignment. Damper must not be squeezed or stretched into duct or opening. Out of round, racked, twisted or misaligned installations can cause torque requirements to exceed damper design. 5) Damper must be kept clean and protected from dirt, dust and other foreign materials prior to and after installation. Examples of such foreign materials include but are not limited to: 1) Mortar dust 2) Drywall dust 3) Firesafing materials 4) Wall texture and 5) Paint overspray. 6) Damper should be sufficiently covered to prevent overspray if wall texturing or spray painting will be performed within 5 feet of the damper. Excessive dirt or foreign material deposits on damper can cause torque requirements to exceed damper design. 7) Caulking is not allowed between the damper sleeve and the wall or floor opening (annular space). However, caulking may be applied to the retaining plates and a field-applied sealant may be required for the damper sleeve and transitions to meet certain duct leakage standards. 8) ACCESS: Suitable access (such that fusible links can be maintained) must be provided for damper inspection and servicing. Where it is not possible to achieve sufficient size access, it will be necessary to install a removable section of duct. (Refer to NFPA 90A). 9) The Code Authority Having Jurisdiction (AHJ) must evaluate and provide approval of final installation where variations to these instructions are necessary.
Installation -
These instructions apply to 11/2 hour rated fire dampers mounted (blades must be horizontal) in: 1) masonry, block or stud walls and 2) concrete floors or ceilings. Specific requirements in these instructions are mandatory. Dampers must be installed in accordance with these instructions to meet the requirements of UL 555. The installation of the damper and all duct connections to the damper sleeve shall conform to the latest editions of NFPA 90A, Standard for the Installation of Air Conditioning and Ventilating Systems, and the SMACNA Fire, Smoke and Radiation Damper Installation Guide, and UL Classifications R13317.
CLEARANCE FOR EXPANSION RETAINER PLATE BLADE LATCH ACCESS DOOR TO BE ON SAME SIDE AS BLADE LATCH
2 in.
6 in. max.
Fig. 1 17
Installation -
Continued
Place the damper and attached retainer plate into the wall/floor opening. If a second retaining plate is being used, secure it on the opposite side of the wall/floor
Fig. 2
Clamping Screw
Clamping Screw
Fasteners
Nut
Nut
Clamping Screw
5. Recommended Preparation of Openings in Clamping Screw Wood and Metal Stud Walls
Frame wall openings as shown below. (see Fig. 3) Double vertical studs are not required for openings 36 in. x 36 in. (914mm x 914mm) or smaller. Gypsum wall board must be fastened 12 in. (305mm) on center to all stud and runner flanges surrounding opening. (see Fig. 4) All construction and fasteners must meet the requirements of the appropriate wall design (See UL Fire Resistance Directory) and/or local codes.
Fig. 3
DAMPER FRAME
DAMPER FRAME
18
12 in.
2 in . 2 Panhead Screws 2 in .
Fig. 4
Floor Runner
Axle Axle 30
30
Axle
Normal
Damper Maintenance
Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild detergents or solvents. If lubrication is desired for components such as axle bearings, do not use oil-based lubricants or any other lubricants that attract contaminants such as dust. Dampers must be maintained, cycled, and tested at intervals not less than every six months and in accordance with the latest editions of NFPA 90A & 92A, UL864 and local codes.
Damper Troubleshooting
The following is a possible cause and correction list for common concerns with the dampers.
Symptom
Possible Cause Frame is out of round causing blades to interfere with frame Screws interfere with blade Contaminants on damper Heat
Corrective Action Adjust frame such that it is round Locate screws and remove Clean with a non-oil based solvent (see Damper Maintenance) Replace link
Link separated
Copyright 2008 Greenheck Fan Corporation 462721 DFDR-XXX FS Rev. 5 December 2008
19
Table of Contents
11/2 Hour Combination Fire Smoke or Curtain Fire Dampers Out of Wall or Out of Floor Vertical or Horizontal Mount
UL Classified (see complete marking on product) UL Classified to Canadian safety standards (see complete marking on product) UL Standard 555 & 555S (Classification R13317)
Receiving and Handling Upon receiving dampers, check for both obvious and hidden damage. If damage is found, record all necessary information on the bill of lading and file a claim with the final carrier. Check to be sure that all parts of the shipment, including accessories, are accounted for. Dampers must be kept dry and clean. Indoor storage and protection from dirt, dust and the weather is highly recommended. Do not store at temperatures in excess of 100F (38C).
Electrical Guidelines All wiring shall be done in accordance with the National Electrical Code ANSI/NFPA-70 latest edition, any local codes that may apply, and wiring diagrams developed in compliance with the job or project design and specifications. Safety Warning: Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment.
Warranty Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the purchase date. Any units or parts which prove to be defective during the warranty period will be repaired or replaced at our option. Greenheck shall not be liable for damages resulting from misapplication or misuse of its products. Greenheck will not be responsible for any installation or removal costs. Greenheck will not be responsible for any service work or backcharges without prior written authorization.
Safety Caution! Electrical input may be needed for this equipment. This work should be performed by a qualified electrician. Verify power before wiring actuator. Greenheck is not responsible for any damage to, or failure of the unit caused by incorrect field wiring. To avoid causing death or serious bodily harm to building occupants, follow all instructions carefully. Dampers must close completely to preserve the integrity of the fire smoke separation.
Due to continuing research, Greenheck reserves the right to change specifications without notice.
This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the job is complete.
20
Table of Contents
Pre-Installation Guidelines ................................................................................................................................ 21 Installation .................................................................................................................................................... 21-29 Clearances Requirements ............................................................................................................22-28 Duct to Sleeve Connections...................................... ........................................................................28 Securing the Damper/Sleeve Assembly to Wall and Floor Openings ........................ ................28-29 Actuator Connections................................... .....................................................................................29 Breakaway Connections ...................................... .............................................................................30 Maintenance .......................................................................................................................................................31 Troubleshooting ..................................................................................................................................................31
Pre-Installation Guidelines
The basic intent of a proper installation is to secure the fire or fire smoke damper in, not to, the opening in such a manner as to prevent distortion and disruption of damper operation. This is accomplished by allowing the fire or fire smoke damper in rated separation openings to expand and for the connecting duct to separate in the event of the collapse of the hanging system. The following items will aid in completing the damper installation in a timely and effective manner. 1) Check the schedules for proper damper locations within the building. Visually inspect the damper for damage and verify that the Reusable Resettable Link (RRL) is in place or has not activated. Never install a fire damper without the proper UL approved RRL in place. (RRL is standard control option. These electric links have a button for resetting.) If damper is furnished with fusible link, visually inspect the link to verify its not missing or broken. Replace link as necessary. Lift or handle damper using sleeve or frame. Do not lift damper using blades or actuators. Damper has label on outside of sleeve indicating a No Screw area. Do not install screws into this area as screws may interfere with unexposed blade linkage and prevent damper blades from opening and/or closing. Damper has label indicating position of damper and sleeve assembly in the wall. Install accordingly to comply with manufacturers appropriate UL Classification file number. Damper must be installed into duct or opening square and free of twist or other misalignment. Damper must not be squeezed or stretched into duct or opening. Out of square, racked, twisted or misaligned installations can cause excessive leakage and/or torque requirements to exceed damper/actuator design. 6) Damper and actuator must be kept clean and protected from dirt, dust and other foreign materials prior to and after installation. Examples of such foreign materials include but are not limited to: a) Mortar dust b) Drywall dust c) Firesafing materials d) Wall texture e) Paint overspray 7) Damper should be sufficiently covered as to prevent overspray if wall texturing or spray painting will be performed within 5 feet of the damper. Excessive dirt or foreign material deposits on damper can cause excessive leakage and/or torque requirements to exceed damper/actuator design. Caulking is not necessary, nor is it allowed, between the damper sleeve and the wall or floor opening (annular space). However, caulking may be applied to the retaining angles. ACCESS: Suitable access (such that RRLs and actuators can be maintained, etc.) must be provided for damper inspection and servicing. Where it is not possible to achieve sufficient size access, it will be necessary to install a removable section of duct. (Refer to NFPA 90A).
2) 3)
8)
9)
4)
5)
10) The Code Authority Having Jurisdiction (AHJ) must evaluate and provide approval of final installation where variations to these instructions are necessary.
21
the header, sill and jamb framing members. Screw into rear portion of the studs so as to avoid space conicts with the grille assembly. Factory Supplied Thermal Blanket Factory Supplied Thermal Blanket
1. DAMPER IS INSTALLED OUTSIDE OF WALL PLANE Grille OFSD-XXX (Supplied Figure 1 shows two approved installations for combination fire smoke dampers: 1) Through the grille access and 2) installation in continuing duct. To provide through the grille access to the damper actuator, the damper is located toward the back of the sleeve and the actuator is installed between the damper and grille. Actuator and damper can be accessed and serviced by removing the grille. To provide access to the damper actuator for continuing ductwork, refer to the 7 1/2 in. Max. requirements of NFPA 90A.
by others)
Gypsum Wallboard
Stud or Runner
In wood stud construction, gypsum wallboard must cover all wood stud surfaces.
Flange
#10 2 1/2 in. long sheet metal screws spaced 6 in. on center and maximum of 2 in. from the corners (minimum of 2 screws per side) through the sleeve into the header, sill and jamb framing members. Screw into rear portion of the studs so as to avoid space conicts with the grille assembly. Factory Supplied Thermal Blanket Factory Supplied Thermal Blanket
#10 sheet metal screws, 2 1/2 inches long, spaced 6 in. on center and maximum of 2 in. from corners (minimum of 2 screws per side). Screw into rear portion of the studs so as to avoid
Duct Terminates Metal Stud Note: Both installations for vertical mount.
Figure 1: Installation configurations for Out of Wall combination fire smoke dampers. ODFD-XXX, OFD-XXX, and OSSFD-XXX: Figure 2 shows installations that are also approved for curtain fire dampers. For access to inspect the damper and fusible link, refer to the requirements of NFPA 90A. 2. CLEARANCE REQUIREMENTS There is no minimum clearance requirement between the wall/floor opening and the sleeve exterior (with thermal blanket attached). However, to facilitate installation, clearances between the wall/floor opening and the damper sleeve are recommended. although there is no maximum allowable clearance, the minimum overlap requirements between the wall/floor and the flange/retaining angle must be met. On grill mount installations the flange must overlap the wall/floor by 1/2 in. (13mm). On continuous duct installations, the retaining angles must overlap the wall/floor by 1 in. (25mm). Because no clearances are required between the wall/floor opening and the sleeve, dampers may not be installed in the plane of the wall using this installation method.
22
Figure 2
Concrete or Masonry Wall Wood Stud
Damper
Steel Stud
Damper
Type A - Horizontal Mount Above Floor/Wall, Duct Terminates Single Angle Method
Factory Supplied Thermal Blanket 7 1/2 in. (191mm) max.
Retaining Angle
Damper
Concrete or Masonry Floor
Type A - Horizontal Mount Below Floor/Wall, Duct Terminates Single Angle Method
23
Figure 2 cont...
Masonry or Concrete Wall Wood Stud
Wood Stud
Damper
Metal Stud
Damper
Retaining Angle
Damper
Damper
Retaining Angle
Retaining Angle
Retaining Angle
Type A - Horizontal Mount Above Floor/Wall, Thru Duct with Two Retaining Angles
Retaining Angle
Type A - Horizontal Mount Above Floor/Wall, Thru Duct with Single Retaining Angle
Retaining Angle
Damper
Type A - Horizontal Mount Below Floor/Wall, Thru Duct with Two Retaining Angles
Type A - Horizontal Mount Below Floor/Wall, Thru Duct with Single Retaining Angle
24
Figure 2 cont....
Damper
Wood Stud
Metal Stud
Masonry or Concrete
Damper
Wood Stud
Factory Supplied Thermal Blanket
Steel Stud
Retaining Angle
Retaining Angle
Flange
Type B2- Vertical Mount, Thru Duct with Two Retaining Angles
Factory Supplied Thermal Blanket Masonry or Concrete
Damper
Flange
Masonry or Concrete
Retaining Angle
Type B2 - Horizontal Mount Above Floor/Wall, Thru Duct with Two Retaining Angles
Damper
Factory Supplied Thermal Blanket Retaining Angle
Masonry or Concrete
Damper
Type B2 - Horizontal Mount Below Floor/Wall, Thru Duct with Two Retaining Angles
25
Figure 2 cont....
Damper 7 1/2 in. (191mm) maximum Concrete or Masonry
Damper Metal Stud Wood Stud 7 1/2 in. (191mm) maximum
Type B2- Vertical Mount, Thru Duct with Single Retaining Angle
Damper
Retaining Angle
Concrete or Masonry
Concrete or Masonry
Type B2 - Horizontal Mount Above Floor/Wall, Duct Terminates Single Angle Method
Retaining Angle
Type B2 - Horizontal Mount Above Floor/Wall, Thru Duct with Single Retaining Angle
Factory Supplied Thermal Blanket Retaining Angle
Concrete or Masonry
Concrete or Masonry
Damper
Damper
Type B2 - Horizontal Mount Below Floor/Wall, Duct Terminates Single Angle Method
Type B2 - Horizontal Mount Below Floor/Wall, Thru Duct with Single Retaining Angle
26
Figure 2 cont....
7 1/2 in. (191mm) maximum Wood Stud
Wood Stud 7 1/2 in. (191mm) maximum Metal Stud
Damper
Flange
Concrete or Masonry
Concrete or Masonry
Retaining Angle
Type C2- Vertical Mount, Thru Duct with Two Retaining Angles
Damper
Damper
Retaining Angle
Concrete or Masonry
Concrete or Masonry
Flange
Retaining Angle
Type C2 - Horizontal Mount Above Floor/ Wall, Duct Terminates Flange Method
Flange
Type C2 - Horizontal Mount Above Floor/Wall, Thru Duct with Two Retaining Angles
Concrete or Masonry
7 1/2 in. (191mm) maximum Factory Supplied Thermal Blanket 7 1/2 in. (191mm) maximum
Damper
Type C2 - Horizontal Mount Below Floor/Wall, Thru Duct with Two Retaining Angles
27
Figure 2 cont....
Wood Stud Metal Stud 7 1/2 in. (191mm) maximum
3. DUCT TO SLEEVE CONNECTIONS Dampers are supplied with actuators (on applicable models) and sleeves from the factory and can be installed without the need for additional field installed sleeves. Sleeve gauges of 20-14 (.9mm - 2mm) are to be used. UL Standard 555 requires all ducts to terminate at fire damper sleeves. Sleeve thickness must not be less than the gauge of the connecting duct. Duct to sleeve breakaway connections must be of the type described on page 5. Factory furnished round duct collars on type R and CR dampers are also considered to be breakaway connections and may be used.
Concrete or Masonry
Type C2- Vertical Mount, Thru Duct with Single Retaining Angle
Flange
Retaining Angle
Wall
Concrete or Masonry
Figure 3: Sleeved damper with Thermal Blanket (duct termination). 4. SECURING THE DAMPER/SLEEVE ASSEMBLY TO WALL OPENINGS. Damper/sleeve assemblies must be installed in wall openings using flanges and sheet metal screws as illustrated and described below. lange on front (grille end) of sleeve must be a F minimum of 16 gauge (1.5mm) steel and have a 58 in. (16mm) minimum flange leg (refer to Figure 3). Using #10 (19mm) sheet metal screws, screw from inside of sleeve through the rear portion of the studs (as shown in Figure 1). Space screws a maximum of 6 in. (152mm) on center and a maximum of 2 in. (51mm) from the corners (minimum of 2 screws per side). No retaining angles are required on the side of wall opposite from the grille. etaining angles for 11/2 hour rated dampers with a R width and height 48 in. (1219mm) or less must be a minimum of 20 ga. (1mm). Retaining angles for all 3 hour rated dampers and all dampers with a width or height greater than 48 in. (1219mm) must be a minimum of 16 gauge (1.5mm). The leg of the retaining angle on the damper sleeve shall be a minimum of 11/4 in. (32mm). The leg of the retaining angle on the wall/floor shall be long enough to cover the annular space and overlap the wall/floor by a minimum of 1 in. (25mm)(see Figure 4).
Type C2 - Horizontal Mount Above Floor/Wall, Thru Duct with Single Retaining Angle
Retaining Angle
Concrete or Masonry
Damper
Type C2 - Horizontal Mount Below Floor/Wall, Thru Duct with Single Retaining Angle
28
4. SECURING THE DAMPER/SLEEVE ASSEMBLY TO WALL OPENINGS continued.... etaining angles must be attached to the sleeve using R one or more of the following methods of attachment: Tack or spot welds #10 (19mm) sheet metal screws 14 in. (6mm) bolts and nuts 316 in. (4.7mm) steel pop rivets Attachments must be spaced a minimum of 6 in. (152mm) on center and a maximum of 2 in. (51mm) from corners. The angles must be attached to all 4 sides of the sleeve. A minimum of two attachments are required on each side, top and bottom. The angles need not be attached to each other at the corners.
Retaining Angle Thermal Blanket (installed around entire outside surface of sleeve)
2i 6i
n. n.
Ma Ma
x. x.
6i 2i
n. n.
Ma Ma
x. x.
Wall
Figure 4: Sleeved damper with Thermal Blanket (duct continuation). Note: Thermal blanket is riveted to the damper sleeve and the seam is taped with acrylic adhesive tape, FSK facing tape 152 5CWnt, manufactured by Venture Tape Company.
5. ACTUATOR CONNECTIONS Electrical and/or pneumatic connections to damper actuators should be made in accordance with wiring and piping diagrams developed in compliance with applicable codes, ordinances and regulations (see Electrical Guidelines). 6 Recommended Preparation of Openings in
Ceiling Runner
12 in.
Frame wall openings as shown (see Figure 5) ouble vertical studs are not required for openings 36 D in. x 36 in. (914mm x 914mm) or smaller. ypsum wall board must be fastened 12 in. (305mm) G on center to all stud and runner flanges surrounding opening (see Figure 5). ll construction and fasteners must meet the A requirements of the appropriate wall design (See UL Fire Resistance Directory) and/or local codes.
16 in. o.c. Maximum (wood studs) 24 in. o.c. Maximum
2 Panhead Screws
Floor Runner
Figure 5
29
Breakaway Connections
Traditional Breakaway Style Transverse Joints Transverse joints illustrated at right have always been approved as breakaway connections. SMACNA testing has also approved the following variations as breakaway connections. he breakaway connections shown (Figure 7) T can be applied with maximum of two #10 (19mm) sheet metal screws on each side and on the bottom located in the center of the slip pocket and penetrating both sides of the slip pocket. ransverse joints illustrated T can be applied as top and bottom joints with Drive Slip - side joints in duct heights up to 20 inches (508mm) See Figure 6.
Plain S Slip Hemmed S Slip Double S Slip
Standing S
Standing S (Alt.)
Standing S (Alt.)
Figure 6
Figure 7
Fire Damper Sleeve 6 in. long 1 in. max. /16 thickness plastic cleats; 12 in. c-c (min. 1 per side) Flanged system angles
Round and Oval Duct Breakaway Connections Round or flat oval ducts connected to Type R or O damper collars shall be attached with #10 (19mm) sheet metal screws as follows: ucts to 22 in. (558mm) wide (or dia.) and smaller D shall have three screws. ucts larger than 22 in. (558mm) wide (or dia.) up to D and including 36 in. (914mm) wide (or dia.) shall have five screws.
NOTE: All breakaway connections described may have duct sealant applied, PA2084T duct sealant adhesive manufactured by Precision, DP1010 water base duct sealant manufactured by Design Polymetrics, Grey Pookie or Ductmate PROseal in accordance with SMACNA recommendations.
Figure 8
Clip Spacing Std. Clip Length 9 in. 6 in. 60 in. Duct 4 Reqd. 7 in. 48 in. Duct 3 Reqd. Duct 36 in. Duct 3 Reqd. 5 in. 24 in. Duct 2 Reqd. 18 in. Duct Smaller Std. Clip Length 1 Reqd.
6 in.
Manufactured Flanged System Breakaway Connections Flanged connection systems manufactured by Ductmate, Ward, and Nexus are approved as breakaway connections when installed as illustrated (Figure 8).
Sleeve
6 in.
6 in.
7 in.
5 in.
5 in.
Proprietary Flange System Breakaway Connections (TDC by Lockformer, TDF by Engle) TDC and TDF systems are approved as breakaway Typical TDC/TDF joint connections when installed as described in the TDC or TDF addendum to the SMACNA Duct Construction Standards except the corners may not be bolted. Standard 6 in. (152mm) metal clip may be used with spacing as shown in Figure 9. 3/8 in. (9.5mm) metal bolts and nuts Sleeve Duct may be used to fasten together corner pieces (see Figure 10).
Typical TDC/TDF joint
5 in.
&
9 in.
Clip Spacing
C L Duct
6 in.
Figure7 in. Detail of proprietary flanged system 9: 7 in. breakaway connections. 48 in. Duct
3 Reqd. 5 in. 5 in. 36 in. Duct 3 Reqd. 5 in. 24 in. Duct 2 Reqd. 18 in. Duct Smaller 1 Reqd. & C L Duct
5 in.
Corner Piece
Figure 10
30
Damper Maintenance
Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild detergents or solvents. If lubrication is desired for components such as axle bearings, jackshaft bearings and jamb seals, do not use oil-based lubricants or any other lubricants that attract contaminants such as dust. Dampers and their actuator(s) must be maintained, cycled, and tested a minimum in accordance with: The latest editions of NFPA 80, 90A, 92A, 92B, 101, 105, UL864, AMCA 503-03 and local codes. Actuator manufacturer recommendations.
Damper Troubleshooting
The following is a possible cause and correction list for common concerns with the dampers. Symptom Possible Cause Frame is 'racked' causing blades to bind on jamb seals Actuator linkage loose Damper does not fully open and/or close Defective motor Screws in damper linkage Contaminants on damper RRL or TOR sensor tripped Damper does not operate Heat No power supplied to the actuator Corrective Action Adjust frame such that it is square and plumb Close damper, disconnect power, adjust and tighten linkage Replace Damper installed too far into wall. Move out to line as designated on damper label Clean with a non-oil based solvent (see Damper Maintenance) Push reset button located on backside of RRL or TOR Add power supply
Copyright 2011 Greenheck Fan Corporation 461337 OFSD ODFD Rev 11 October 2011
31
Table of Contents
Part Number 474015 Single Side Retaining Angle Installation Instructions Supplement
FD & DFD Series FSD Series
Refer to: Installation Instructions for FD, DFD, SSFD, & KFD Models (Part #452763) or Installation Instructions for FSD-XXX, DFD-XXX, SSFSDXXX & CFSD-XXX Series Fire & Combination Fire Smoke Dampers (Part #461336) or Installation Instructions for FD & DFD 150X Series Curtain Fire Dampers (Part #453946) for additional details.
11/2 Hour Fire Dampers and 11/2 Hour Combination Fire Smoke Dampers
UL CLASSIFIED (see complete marking on product) UL CLASSIFIED to Canadian safety standards (see complete marking on product) Standards UL 555 & 555S Classifications Filed at UL under Listing #R13317 Single side retaining angle
These instructions apply to 11/2 hour rated combination fire smoke dampers and curtain fire dampers mounted in masonry or block walls, metal stud walls, wood stud walls or concrete floors. Specific requirement in these instructions are mandatory. These instructions meet the requirements of NFPA 90A (Standard for the Installation of Air Conditioning and Ventilating Systems). Vertical mount dampers up to a maximum size of 80 in. W x 50 in. H (2032mm x 1270mm), 50 in. W x 80 in. H (1270mm x 2032mm), or 40 in. W x 100 in. H (1016mm x 2540mm) or horizontal mount dampers up to a maximum size of 144 in. W x 96 in. H (3658mm x 2438mm) may be installed as illustrated below. Larger damper assemblies require retaining angles on both sides of the partition. Note: Model specific size limits can be found in the base installation instruction documents noted above. 1. Clearance Requirements On vertical mount single side angle installations there are no minimum clearance requirements between the wall opening and the damper sleeve. However, to facilitate installation, clearances between the wall opening and the damper sleeve are recommended. On horizontal mount single side angle installations a minimum clearance is required between the outside of the damper sleeve and the floor opening of 1/8 in. per foot (3mm per .3m) of damper width and 1/8 in. per foot (3mm per .3m) height with a minimum clearance of 1/4 in. (6mm). The maximum overall clearance is 1 1/2 in. (38mm), 2. Securing the Damper/Sleeve Assembly to Wall/ Floor Opening Retaining angles must be attached to both the sleeve and the partition (see figures 1-8). etaining angles for dampers with a width and R height of 48 in. (1219mm) or less must be a minimum of 20 ga. (1mm). Retaining angles for dampers with a width or height greater than 48 in. (1219mm) must be a minimum of 16 ga. (1.5mm). The leg of the retaining angle on the damper sleeve shall be a minimum of 1 1/4 in. (32mm). The leg of the retaining angle on the wall/floor shall be long enough to cover the annular space and overlap the wall/floor by at least 1 in. (25mm). For metal stud partitions only, the single-side mounting angle may be directly attached to the metal stud prior to the installation of the drywall. etaining angles must be attached to the R sleeve using one of the methods shown below: tack or spot welds #10 sheet metal screws 1/4 in. (6mm) nuts and bolts etaining angles must be attached to the R partition using one of the methods shown below: Drywall screws of a length such that the screw engages the steel stud/track by 1/2 in. (13mm) (steel framing).
32
2. Securing the Damper/Sleeve Assembly to the Wall/Floor opening cont....... Drywall screws of a length such that the screw engages the wood stud by 13/4 in. (44mm) (wood framing). Steel anchors or self tapping concrete screws penetrating masonry or block 11/4 in. (31mm). minimum of two connections per side are A required. Additional connections must be
Damper Sleeve
made at a maximum of 12 in. (305mm) O.C. (on center) maximum for openings of 48 in. W x 36 in. H (1219mm x 914mm) and less, and 6 in. (152mm) O.C. (on center) for openings 80 in. W x 50 in. H (2032mm x 1270mm), 50 in. W x 80 in. H (1270mm x 2032mm), and 40 in. W x 100 in. H (1016mm x 2540mm) or less.
Damper Sleeve
in. UL Classied Gypsum Wallboard (see UL Rated Wall Design for Additional Details)
Two layers of 1/2 in. UL Classied Gypsum Wallboard (see UL Rated Wall Design for Additional Details)
1/ 2
in. UL Classied Gypsum Wallboard (see UL Rated Wall Design for Additional Details)
Two layers of 1/2 in. UL Classied Gypsum Wallboard (see UL Rated Wall Design for Additional Details) 2 1/2 in. min. Metal Stud or Runner
Damper Sleeve
Damper Sleeve
Damper Sleeve
in. UL Classied Gypsum Wallboard (see UL Rated Wall Design for Additional Details)
in. UL Classied Gypsum Wallboard (see UL Rated Wall Design for Additional Details)
Grille Installations (Dampers up to 36 in. x 36 in. [914mm x 914mm] maximum) Angle legs may be reversed and one leg inserted into the wall/floor opening. Retaining angles used in conjunction with grille installations must be a minimum of 20 gauge (1mm) steel and have a minimum of 5/8 in. x 1 in. (15mm x 25mm) 20 gauge (1mm) steel.
Space screws a maximum of 6 in. (152mm) on center and a maximum of 2 in. (51mm) from the corners (minimum of 2 screws per side). See Figure 9 and Figure 10. Note: Screws used to attach grille are allowed to penetrate reversed angle leg.
Damper Sleeve #10 sheet metal screws spaced 6 in. on center and a maximum of 2 in. from the corners (minimum of 2 screws per side). Screw into studs so as to avoid space conicts with the grille Angle Fastener (see Note 2)
Damper Sleeve #10 sheet metal screws spaced 6 in. on center and a maximum of 2 in. from the corners (minimum of 2 screws per side). Screw into studs so as to avoid space conicts with the grille Angle Fastener (see Note 2) 2 1/2 in. Min. Stud or Runner
1 /2
in. UL Classied Gypsum Wallboard (see UL Rated Wall Design for Additional Details)
Two layers of 1/2 in. UL Classied Gypsum Wallboard (see UL Rated Wall Design for Additional Details)
Copyright 2011 Greenheck Corporation 474015 Single Side Retaining Angle Suppl Rev. 2 July 2011
34
DATE
NOTES
35
36