DIgSILENT PowerFactory 14.1.

4 Fault Locations Complete Report Short-Circuit Calculation according to ANSI Pre-fault Voltage Consider Transformer Taps Grid: SIN Rated Voltage [kV] TG(1) Mom.Duty Int.Duty 30-cycle 6,60 0,067 0,067 0,073 0,197 0,199 0,242 18,279 18,127 15,064 -71,22 -71,35 -73,15 208,952 207,221 172,203 3,208 3,235 20,697 2 3 5 8 Equivalent Impedance R[Ohm] X[Ohm] 1,00 p.u. No Fault Impedance Resistance, Rf Reactance, Xf System Stage: SIN Symmetrical Current (E/Z) [kA] [deg] Apparent Power [MVA] X/R ratio Asym.RMS X/R based [kA] 0,00 Ohm 0,00 Ohm

Project: Date: 19/10/2012

3-Phase Short-Circuit NACD Mode Currents/Voltages for Annex: Asym.Peak X/R based [kA] 35,559 cycles cycles cycles cycles Sym.Base [kA] 18,127 18,127 18,127 18,127 Tot.Base [kA] 21,057 18,770 18,127 18,127 Interpolated LV/Interrupting / 1