3VT4 Molded Case Circuit Breakers up to 1000 A

Circuit breakers, Switch disconnectors

Technical specifications
Specifications Type Standards Approval marks EN 60 947-2, IEC 947-2 EN 60 947-3, IEC 947-3 3VT4 circuit breakers Switch disconnectors

Number of poles Rated current In Rated normal current Iu Rated operational current Ie Rated operational voltage Ue Rated frequency fn Rated impulse withstand voltage Uimp Rated insulation voltage Ui Utilization category (selectivity) AC 690 V Utilization category (switching mode) AC 690 V DC 440 V Rated short-time withstand current Ue=AC 690 V Icw/t Rated ultimate short-circuit breaking capacity (rms value)1) Icu/Ue Off-time at Icu Rated short-circuit service breaking capacity (rms value) Ics/Ue A A A V Hz kV V

3 315, 630, 800, 1000 1000 -AC max. 690 50/60 8 690 A, B --15 kA/1 s AC 85 kA/230V AC 65 kA/415V AC 45 kA/500V AC 20 kA/690V 30 ms AC 45 kA/230V AC 36 kA/415V AC 30 kA/500V AC 20 kA/690V 140 kA/AC 415 V W cycles cycles cycles /hr N 100 10000 4000 120 230 IP40 IP20 C 40 -40 ... +55 dry and tropical climate 3 m Hz 2000 3g (8 ... 50) / - //--/- /-/ / / /-1) In case circuit breaker connection is reversed (input terminals 2, 4, 6 output terminals 1, 3, 5), Icu does not change. -AC-23 B DC-23 B 15 kA/1 s -1000 AC max. 690 DC max. 440 --

---

Rated short-circuit making capacity (peak value) Icm/Ue Losses per pole at In = 250 A Mechanical endurance Electrical endurance (Ue = AC 415 V ) Switching frequency Operating force Front-side device protection Terminal protection

30 kA/AC 415 V 30 kA/DC 440 V

Operating conditions
Reference ambient temperature Ambient temperature range Working environment Degree of pollution Max. elevation Seismic resistance

Design modifications
Front/rear connection Plug-in design Withdrawable design

Accessories
Switches-auxiliary/relative/signal/early Shunt trip/with signal switch Undervoltage release/with early switch with signal switch Manual front operating mechanism/lateral operating mechanism right/left Mechanical interlocking to the manual operating mechanism, by Bowden wire Motorized operating mechanism/with operations counter Locking-type lever Bolt sealing inset/additional cover for overcurrent release available, -- unavailable

Siemens LV 36 2008

5/5