You are on page 1of 10

http://datasheet.eaton.com/datasheet.php?

model=290376

Datasheet - NZMH4-VE800-S1
Part no.
Article no.
Catalog No.

Delivery program
Product range
Protective function
Standard/Approval
Installation type
Release system
Construction size

Description
Number of poles
Standard equipment
Rated current = rated uninterrupted current In = I u
Switching capacity
1000 V 50/60 Hz Icu
Setting range
Overload trip
Ir
Short-circuit releases
Non-delayed Ii = I n x …
Delayed Isd = Ir x …

Technical data
Circuit-breakers
Rated surge voltage invariability Uimp
Main contacts
Auxiliary contacts
Rated operational voltage Ue
Rated current = rated uninterrupted current In = I u
Overvoltage category/pollution degree
Rated insulation voltage Ui
Utilization category
Ambient temperature
Ambient temperature, storage
Operation
Rated short-circuit making capacity
240 V 50/60 Hz Icm
400/415 V 50/60 Hz Icm
440 V 50/60 Hz Icm
525 V 50/60 Hz Icm
690 V 50/60 H Ic
1000 V 50/60 Hz Icm
Rated short-circuit breaking capacity Icn
Icu to IEC/EN 60947 test cycle O-t-CO Icu
240 V 50/60 Hz Icu
400/415 V 50 Hz Icu
440 V 50/60 Hz Icu
525 V 50/60 Hz Icu
690 V 50/60 Hz Icu
1000 V 50/60 Hz Icu
Ics to IEC/EN 60947 test cycle O-t-CO-t-CO Ics
230 V 50/60 Hz Ics
400/415 V 50/60 Hz Ics
440 V 50/60 Hz Ics
525 V 50/60 Hz Ics
690 V 50/60 Hz Ics
1000 V AC Ics
Rated short-time withstand current
t = 0.3 s Icw
t=1s Icw
Lifespan, mechanical Operations
Max. operating frequency

Lifespan, electrical
1000 V 50/60 Hz Operations
Terminal capacity
Standard equipment
Round copper conductor
Tunnel terminal
Stranded

4-hole
Bolt terminal and rear-side connection
Module plate
Single hole min.
Single hole max.
Module plate
Double hole min.
Double hole max.
Connection width extension

Connection width extension


Al conductors, Cu cable
Tunnel terminal
Stranded

4-hole
Cu strip (number of segments x width x segment thickness)
Flat conductor terminal
min.
max.
Module plate
Single hole
Bolt terminal and rear-side connection
Flat copper strip, with holes min.
Flat copper strip, with holes max.
Connection width extension
Copper busbar (width x thickness) mm
Bolt terminal and rear-side connection
Screw connection
Direct on the switch
min.

max.
Module plate
Single hole min.

Single hole max.


Module plate
Double hole
Connection width extension
Connection width extension min.
Connection width extension max.
Control cables

Design verification as per IEC/EN 61439


Technical data for design verification
Rated operational current for specified heat dissipation In
Equipment heat dissipation, current-dependent Pvid
Operating ambient temperature min.
Operating ambient temperature max.
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance
10.2.3.1 Verification of thermal stability of enclosures
heat
abnormal heat and fire due to internal electric effects
10.2.4 Resistance to ultra-violet (UV) radiation
10.2.5 Lifting
10.2.6 Mechanical impact
10.2.7 Inscriptions
10.3 Degree of protection of ASSEMBLIES
10.4 Clearances and creepage distances
10.5 Protection against electric shock
10.6 Incorporation of switching devices and components
10.7 Internal electrical circuits and connections
10.8 Connections for external conductors
10.9 Insulation properties
10.9.2 Power-frequency electric strength
10.9.3 Impulse withstand voltage
10.9.4 Testing of enclosures made of insulating material
10.10 Temperature rise
10.11 Short-circuit rating
10.12 Electromagnetic compatibility
10.13 Mechanical function

Technical data ETIM 7.0


Low-voltage industrial components (EG000017) / Power circuit-breaker for trafo/generator/installation protection (EC000228
protection (ecl@ss10.0.1-27-37-04-09 [AJZ716013])
Rated permanent current Iu
Rated voltage
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
Overload release current setting
Adjustment range short-term delayed short-circuit release
Adjustment range undelayed short-circuit release
Integrated earth fault protection
Type of electrical connection of main circuit
Device construction
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally closed contact
Number of auxiliary contacts as normally open contact
Number of auxiliary contacts as change-over contact
With switched-off indicator
With under voltage release
Number of poles
Position of connection for main current circuit
Type of control element
Complete device with protection unit
Motor drive integrated
Motor drive optional
Degree of protection (IP)

Characteristics
123U175
123U174

Dimensions
123X435

① Blow out area, minimum clearance to adjacent parts


Ui ≤ 690 V: 100 mm
Ui ≤ 1500 V: 200 mm
② Minimum clearance to adjacent parts
Ui ≤ 1000 V: 15 mm
Ui ≤ 1500 V: 70 mm

Additional product information (links)


IL01210010Z (AWA1230-2022) Circuit-Breaker, basic unit
IL01210010Z (AWA1230-2022) Circuit-Breaker, basic unit
Weight
Temperature dependency, Derating
Effective power loss
Selectivity, Back Up Protection and Coordination Guide
Setting-Specific Representation of Tripping Characteristics and Competent Assessment of their Interaction
Busbar Component Adapters for modern Industrial control panels
CurveSelect characteristics program
Eaton configurator
additional technical information for NZM power switch

21.02.2021 07:00
NZMH4-VE800-S1
290376
290376
1230PIC-715
Similar to illustration

Circuit-breaker
Systems, cable, selectivity and generator protection
IEC
Fixed
Electronic release
NZM4
R.m.s. value measurement and “thermal memory”
adjustable time delay setting to overcome current peaks tr: 2 – 20 s at 6 x
Ir also infinity (without overload releases)
Adjustable delay time tsd: Steps: 0, 20, 60, 100, 200, 300, 500, 750, 1000
ms
i2t constant function: switchable
NZM...S1 terminal type: NZM...XKSA cover required
3 pole
Screw connection
A 800

kA 20

A 400 - 800

2 - 12
2 - 10

V 8000
V 6000
V AC 1000
A 800
III/3
V 1000
B

°C - 40 - + 70
°C -25 - +70

kA 275
kA 187
kA 187
kA 143
kA 100
kA 40

kA
kA 125
kA 85
kA 85
kA 65
kA 50
kA 20
kA
kA 63
kA 50
kA 50
kA 50
kA 37
kA 15

kA 19.2
kA 19.2
10000
Ops/h 60
release

500

Screw connection

4 x (50 - 240)
mm2

mm2 1 x (185 - 240)


mm2 2 x (70 - 185)

mm2 4 x 50
mm2 4 x (35 - 185)
mm2
2 x 240
mm2 6 x (70 - 240)

4 x (50 - 240)
mm2

mm 6 x 16 x 0.8
mm (2 x) 10 x 32 x 1.0
mm (2 x) 10 x 50 x 1.0

mm (2 x) 10 x 50 x 1.0
mm (2 x) 10 x 50 x 1.0
mm (2 x) 10 x 80 x 1.0

M10

mm 25 x 5
2 x (50 x 10)
mm 2 x (80 x 10)

mm 25 x 5
2 x (50 x 10)
mm

mm 2 x (50 x 10)
mm
mm 60 x 10
mm 2 x (80 x 10)

1 x (0.75 - 2.5)
mm2 2 x (0.75 - 1.5)

A 800
W 79
°C -25
°C 70

Meets the product standard's requirements.


Meets the product standard's requirements.
Meets the product standard's requirements.
Meets the product standard's requirements.
Meets the product standard's requirements.
Does not apply, since the entire switchgear needs to be evaluated.
Does not apply, since the entire switchgear needs to be evaluated.
Meets the product standard's requirements.
Does not apply, since the entire switchgear needs to be evaluated.
Meets the product standard's requirements.
Does not apply, since the entire switchgear needs to be evaluated.
Does not apply, since the entire switchgear needs to be evaluated.
Is the panel builder's responsibility.
Is the panel builder's responsibility.

Is the panel builder's responsibility.


Is the panel builder's responsibility.
Is the panel builder's responsibility.
Eaton will provide heat dissipation data for the devices.
must be observed.
must be observed.
instruction leaflet (IL) is observed.

ator/installation protection (EC000228)

A 800
V 1000 - 1000
kA 85
A 400 - 800
A 800 - 8000
A 1600 - 9600
No
Screw connection
Built-in device fixed built-in technique
No
No
0
0
0
No
No
3
Front side
Rocker lever
Yes
No
Yes
IP20
of their Interaction

You might also like