Professional Documents
Culture Documents
Model
product brand name SENTRON
product designation 3WA air circuit breaker
suitability for use circuit breaker
size of the circuit-breaker III
number of poles 3.00
position / of neutral conductor no internal N-conductor
fastening method fixed-mounted circuit breakers
type of the driving mechanism manual operating mechanism with
mechanical or electrical closing
design of the electronic trip unit ETU600 LSIG
6/18/2022
Current
continuous current / rated value / maximum 5,000.00 A
continuous current / rated value 5,000.00 A
operating current
• at 40 °C / rated value 5,000 A
• at 45 °C / rated value 5,000 A
• at 50 °C / rated value 5,000 A
• at 55 °C / rated value 5,000 A
• at 60 °C / rated value 5,000 A
• at 65 °C / rated value 5,000 A
• at 70 °C / rated value 5,000 A
6/18/2022
Electronic trip unit
product feature
• upgradable Yes
• Bluetooth and USB interface Yes
• decoder for basic protection Yes
functions
• display and function keys Yes
• SENTRON powerconfig configuration Yes
software
6/18/2022
Minimum adjustable value current setting 2,000 A
(Ir) via eSET
Maximum adjustable value current setting 5,000 A
(Ir) via eSET
L: Overload protection neutral conductor
product feature / with neutral conductor
protection
product feature / with neutral conductor Yes
protection / can be switched on/off
Current setting (InN) 0.2-2;0.001
Reference value for current setting (InN) x In
Minimum adjustable value current setting 1,000 A
(InN) via eSET
Maximum adjustable value current setting 10,000 A
(InN) via eSET
S: Short-time-delayed short-circuit protection ST
product feature / for S-tripping
product feature / for S-tripping / Yes
independent of direction / can be switched
on/off
product feature / for S-tripping / Yes
independent of direction / selectable
characteristic function
Parameter setting via eSET or rotary coding Yes
switches
S: Short-time-delayed short-circuit protection ST, characteristic i0t
Current setting (Isd) 1.5;2;2.5;3;4;5;6;8;10
Reference value for current setting (Isd) x Ir
Tripping time (tsd) 0.08;0.15;0.22;0.3;0.4
Reference value for tripping time (tsd) s
Current setting (Isd) via eSET 0.6-10;0.001
Minimum adjustable value current setting 3,000 A
(Isd) via eSET
Maximum adjustable value current setting 80.0 kA
(Isd) at 500V via eSET
Maximum adjustable value current setting 68.0 kA
(Isd) at 690V via eSET
Tripping time (Isd) via eSET 0.02-0.4;0.001
6/18/2022
S: Short-time-delayed short-circuit protection ST, characteristic i2t
Current setting (Isd) 1.5;2;2.5;3;4;5;6;8;10
Reference value for current setting (Isd) x Ir
Tripping time (tsd) 0.1;0.2;0.3;0.4
Current setting (Isd) via eSET 0.6-10;0.001
Minimum adjustable value current setting 3,000 A
(Isd) via eSET
Maximum adjustable value current setting 80.0 kA
(Isd) at 500V via eSET
Maximum adjustable value current setting 68.0 kA
(Isd) at 690V via eSET
Tripping time (Isd) via eSET 0.02-0.4;0.001
I: Instantaneous short-circuit protection INST
product feature / for I-tripping
product feature / for I-tripping / can be Yes
switched on/off
Parameter setting via eSET or rotary coding Yes
switches
Current setting (Ii) 1.5;2;3;4;6;8;10;12;15
Reference value for current setting (Ii) x In
Current setting (Iimax) 0.80
Reference value for current setting (Iimax) x Ics
Current setting (Ii) via eSET 1.5-15;0.001
Minimum adjustable value current setting 7,500.0 A
(Ii) via eSET
Maximum adjustable value current setting 80.0 kA
(Ii) at 500V via eSET
Maximum adjustable value current setting 68.0 kA
(Ii) at 690V via eSET
G: Ground-fault protection GF
product feature / for G-tripping
product feature / for G-tripping / can be Yes
switched on/off
product feature / for G-tripping / selectable Yes
characteristic function
G: Ground-fault protection GF : characteristic i0t
Current setting (Ig) 0.06-0.4;0.001
3WA1350-5AF02-0AA0 Subject to change without notice
Page 5/8 © Copyright Siemens
6/18/2022
Reference value for current setting (Ig) x In
Tripping time (tg) 0.02-30;0.001
Reference value for tripping time (tg) s
G: Ground-fault protection GF : characteristic i2t
Current setting (Ig) 0.06-0.4;0.001
Reference value for current setting (Ig) x In
Tripping time (tg) 0.02-5;0.001
Reference value for tripping time (tg) s
Measuring functions
measurement function
• current measurement Yes
Communication
product function / communication function No
Durability
mechanical service life (switching cycles)
• without maintenance / typical 7,500.00
• with maintenance / typical 15,000.00
electrical endurance (switching cycles)
• at 690 V / without maintenance / 2,000
typical
• at 690 V / with maintenance / typical 15,000
Dimensions
height 437.00 mm
width 704.00 mm
depth 357.00 mm
3WA1350-5AF02-0AA0 Subject to change without notice
Page 6/8 © Copyright Siemens
6/18/2022
Main connection
arrangement of electrical connectors / for main connection on the rear, horizontal
main current circuit
Auxiliary circuits
design of the auxiliary switch 2 NO + 2 NC
number of NC contacts / for auxiliary 2.00
contacts
number of NO contacts / for auxiliary 2.00
contacts
number of CO contacts / for auxiliary 0.00
contacts
Internal accessories
product component / undervoltage release No
product component / voltage trigger No
product component / trip indicator Yes
product component / motor drive No
Electronic Accessories
Environment conditions
protection class IP / on the front IP20
Ambient temperature during operation
• min -40 °C
• max 70.00 °C
Ambient temperature during storage
• min -40 °C
• max 80.00 °C
Certificates
protection class IP / on the front Q
Further information
6/18/2022
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3WA1350-5AF02-0AA0
CAx-Online-Generator
http://www.siemens.com/cax
Tender specifications
http://www.siemens.com/specifications
6/18/2022