IEC 61850 EXERCISE 1

Exercise 1
1. Building the Physical IEC 61850 Network
In this exercise you will build a physical network for IEC 61850 to be able to configure the communication in the following exercises.

1.1 Connecting devices to the IEC 61850 network Connect the devices to the IEC 61850 network according to the IEC 61850 layout picture (chapter 4).

1.2 REF543R Set the SPA address to REF543R feeder terminal. You can find the correct address from the IEC 61850 layout picture. SPA 7

REF543R

If you are unfamiliar with changing the addresses of REF feeder terminals, please read the instructions below.
1. 2. 3. 4. 5. Press down the E button down to enter the technical level. Navigate to Communication / SPA / SPA Address. Press E. Give password 2. You can change the digits and move from one digit to the next by using the arrow up/down/left/right keys. Enter the correct address. 6. Press E to accept the change. 7. Navigate back to the main menu and press E to save the parameters and to return to the Mimic view.

1.3 SPA Take in use SPA protocol for the REF feeder terminal. SPA has the transmission rate of 9.6 kbits/s. If you would choose IEC 61850 as the protocol, the transmission rate would be 38.4 kbits/s and you should also define IEC 61850 as the protocol in use in the CET for SPA-ZC 400. FISUB
1MRS751567-MTR 1

O246

IEC 61850 EXERCISE 1

If you are unfamiliar with changing the protocol, please read the instructions below.
1. 2. 3. 4. 5. 6. 7. Press down the E button down to enter the technical level. Navigate to Communication / General / Protocol 2. Press E. Give password 2. You can change the protocol by using the arrow up/down keys. Choose SPA. Press E to accept the change. Navigate to Configuration / General / Store in order to store the changes to the relay. 8. Press E. 9. Navigate to Software reset. 10. Select reset in order to reset the relay. This is required when one wants to take the changed protocol settings in use.

1.4 IP address Right click My Network Places on your desktop and choose Properties. Right click Local Area Connection and select Properties. Double click Internet Protocol (TCP/IP).

Define an IP address for your computer. Enter 192.0.2.1 to the IP address field (see the picture on next page). Note that later on in the Communication Engineering Tool for SPA-ZC 40x, this same address is called default gateway . The Subnet mask is generated automatically when you select the empty field.

FISUB
1MRS751567-MTR 2

O246

IEC 61850 EXERCISE 1

Press OK and close all the windows. Select Start and Run. Write cmd on the field and press OK.

Write the command ping 192.0.2.10 (the factory default IP address for SPA-ZC 400) and press enter in order to test if the communication is working properly.

FISUB
1MRS751567-MTR 3

O246

IEC 61850 EXERCISE 1

FISUB
1MRS751567-MTR 4

O246

IEC 61850 EXERCISE 2

Exercise 2
2. Configuring SPA-ZC 400
In this exercise you will select a connectivity package for REF 543 and then configure SPA-ZC 400 with the help of the connectivity package and the SPA-ZC 400 Communication Engineering Tool. You will also change the IP address of SPA-ZC 400.

2.1 REF 543 connectivity package Start the Connectivity Package Manager by double-clicking the shortcut on the desktop of your pc. Select the correct connectivity package 1.4 for REF543R.

FISUB
1MRS751567-MTR 5

O246

IEC 61850 EXERCISE 2

2.2 New project with CET for SPA-ZC 400 Start Communication Engineering Tool (CET) for SPA-ZC 400 by double-clicking the shortcut on the desktop of your PC. Create a new project by selecting File / Open/Manage Projects

Press New Project and fill in the following project information. Press Create and Open Project.

2.3 Adding SPA-ZC 400 and REF543R Add SPA-ZC 400 to your project by right clicking with the mouse and navigating to New / IEC61850 / SPA-ZC40x. The Object Properties window can be accessed from View / Object Properties. It is also

FISUB
1MRS751567-MTR 6

O246

IEC 61850 EXERCISE 2

advisable to open the output window that will display messages related to possible errors.

Add REF543R by right clicking the SPA-ZC 400 with the mouse and navigating to New / Feeder IEDs / REF541,543,545.

2.4 Importing REF configuration You should import the REF configuration .AR-file to your project by right clicking with the mouse on top of REF541,543,545 and by selecting Import. Select the correct file from your hard drive and press Open.

Those function blocks that do not contain information relevant to the IEC 61850 data model are excluded from the tree structure. Press OK.

FISUB
1MRS751567-MTR 7

O246

IEC 61850 EXERCISE 2

The configuration is now imported in CET in IEC 61850 format. Set the REF properties in the Object Properties window according to your relay type (ordering number). The relay used in this exercise is REF543KM129AABA. Set also the SPA address according to the IEC 61850 layout picture.

2.5 Downloading the configuration to SPA-ZC 400 Select SPAZC40x on the tree hierarchy and define a new IP address in the Object Properties window. The IP address should be changed to 192.168.1.10. The gateway (this was the IP address for the pc) can be left as the default 192.0.2.1.

FISUB
1MRS751567-MTR 8

O246

IEC 61850 EXERCISE 2

Select SPA-ZC 400 in the tree hierarchy and right click with the mouse. Select CID Export. Check that the IP address for SPA-ZC 400 is 192.0.2.10 and press Write. At this point the IP address has to be 192.0.2.10 because that is the current address for SPA-ZC 400. The address is changed to 192.168.1.10 when we press write. Save the .CID configuration file on your computer by assigning it a file name and pressing Save.

FISUB
1MRS751567-MTR 9

O246

IEC 61850 EXERCISE 2

Press Yes to accept the change of IP address and gateway. In the Communication Engineering Tool for SPA-ZC 400, we defined a new IP address for SPA-ZC 400. We also need a new default gateway according to the IP address. In our case the default gateway should be 192.168.1.1. This default gateway is actually also the new IP address for your computer. Go to the desktop of your computer and right-click My Network Places. Choose Properties. Right-click Local Area Connection and select Properties. Double-click Internet Protocol (TCP/IP). Redefine the IP address for your computer. Use address 192.168.1.1 and enter it to the IP address field (see the picture on next page). The Subnet mask is generated automatically when you select the empty field. Press OK and close the windows.

FISUB
1MRS751567-MTR 10

O246

IEC 61850 EXERCISE 2

Return to the CET for SPA-ZC 400 tool. Set the default gateway to 192.168.1.1. Right click on SPA-ZC 400 and select Reset Tool. Press Reset.

Close CET.

FISUB
1MRS751567-MTR 11

O246

IEC 61850 EXERCISE 3

Exercise 3
3. IEC61850 OPC Server
In this exercise you will configure the IEC 61850 OPC Server. 3.1 New project with CET for IEC 61850 OPC Server Start the Communication Engineering Tool (CET) for IEC 61850 OPC Server by double clicking the MicroSCADA Pro shortcut on the desktop of your pc. Double-click 61850 OPC Server Communication Engineering Tool. icon and then the icon for

Create a new project by selecting File / Open/Manage Project Press New Project and fill in the following project information.

FISUB
1MRS751567-MTR 12

O246

IEC 61850 EXERCISE 3

Press Create and Open Project. 3.2 IEC 61850 OPC Server definitions Add computer node to your project by right-clicking with the mouse on top of Own project and navigating to New / Communication / Computer Node. The Object Properties window can be accessed from View / Object Properties. It is also advisable to open the output window that will display messages related to possible errors. Select the Computer Node and define the Node Name as 127.0.0.1 in the Object Properties window. 127.0.0.1 is the IP address for MicroSCADA system (see exercise 6.1).

FISUB
1MRS751567-MTR 13

O246

IEC 61850 EXERCISE 3

Add an IEC 61850 OPC Server to the Computer Node by right clicking on the Computer Node and selecting New / IEC 61850 / IEC61850 OPC Server. Add an IEC61850 Subnetwork to the IEC61850 OPC Server by selecting New / IEC61850 / IEC61850 Subnetwork. Add an IEC61850 IED to the IEC61850 Subnetwork by selecting New / IEC61850 Subnetwork / IEC61850 IED.

FISUB
1MRS751567-MTR 14

O246

IEC 61850 EXERCISE 3

3.3 Importing relay configuration Right-click on the IEC61850 IED and select SCL Import. In the SCL Import dialog, click Choose File and select the .CID file (Configuration.cid) you previously created with the CET for SPA-ZC 400.

FISUB
1MRS751567-MTR 15

O246

IEC 61850 EXERCISE 3

Press Open. The SCL Import window should now look similar to the following screenshot.

Press Import in the SCL Import window. The SPA-ZC 400 configuration is now imported to your project. Close the SCL Import window. Select LD0 under SPAZC40x and set the SPA address to 7 in the Object Properties window. In a similar way, set the SPA address to 7 under LD1. Update the IEC 61850 OPC Server by right clicking on the Station computer Node and selecting Management. Click first Update Configuration.

FISUB
1MRS751567-MTR 16

O246

IEC 61850 EXERCISE 3

Click then Reload Configuration and the IEC61850 OPC Server is configured. Close the Management window.

25.4 Testing You can test the communication by right-clicking LD1 under SPA-ZC400 and selecting Online diagnostics. Write command RF: on the transparent SPA field and press Send. The relay should respond with <7D:REF543R : if the communication is working properly.

FISUB
1MRS751567-MTR 17

O246

IEC 61850 EXERCISE 3

You can also test the system by right-clicking Pos under SPA-ZC400 / LD1 / CBCSWI120 and selecting Online diagnostics.

FISUB
1MRS751567-MTR 18

O246

IEC 61850 EXERCISE 3

When you change the position of the circuit breaker (Q0) with the simulator, stVal should change according to the position of the circuit breaker. Circuit breaker 00 Undefined 10 Open 01 Closed 11 Undefined StVal 0 1 2 3

FISUB
1MRS751567-MTR 19

O246

IEC 61850 EXERCISE 3

Close the tool.

FISUB
1MRS751567-MTR 20

O246

IEC 61850 EXERCISE 4

Exercise 4
4. Configuring SYS 600 base system
In this exercise you will configure the SYS 600 base system. 4.1 Communication Links Open the SYS 600 Control Panel. In the MicroSCADA Control Panel dialog click Admin and Config. In the SYS_BASCON.COM file scroll down to the Communication Links section.
;---------------------------------------------------;Communication Links ;NOTE! Use the system configuration tool to create a link for the PC-NET! #CREATE LIN:V = LIST(-;Link to DCP-NET (requires DCP driver) LT = "RAM",;Link type SD = "RM00",;DCP card (first:RM00, second RM01) RE = "BCC",;Redundancy TI = 2,;Timeout length (s) NA = 3,;NAK limit EN = 3) ;ENQ limit ;#CREATE LIN1:B = %LIN #CREATE LIN:V = LIST(-;Link to other SYS or LAN frontend (requires TCP/IP) LT = "LAN") ;Link type ;#CREATE LIN2:B = %LIN ;----------------------------------------------------

Change LIN2 in the following way:


#CREATE LIN:V = LIST(-;Link to other SYS or LAN frontend (requires TCP/IP) LT = "LAN") ;Link type #CREATE LIN2:B = %LIN

FISUB
1MRS751567-MTR 21

O246

IEC 61850 EXERCISE 4

4.2 Node object In the SYS_BASCON.COM file scroll down to the Node object section.
;---------------------------------------------------;Node objects (NET's and SYS's) ;NOTE! Use the system configuration tool to create nodes for the PC-NET! #CREATE NOD:V = LIST(-;Node for DCP-NET LI = 1,;Link number SA = 201) ;Station address: 0..255 ;#CREATE NOD1:B = %NOD #CREATE NOD:V = LIST(-;Node for LAN frontend or SYS LI = 2,SA = 202) ;#CREATE NOD2:B = %NOD ;----------------------------------------------------

Change NOD2 in the following way:


#CREATE LI = SA = #CREATE NOD:V = LIST(-;Node for LAN frontend or SYS 2,202) NOD2:B = %NOD

4.3 Other stations In the SYS_BASCON.COM file scroll down to the Other stations section
;---------------------------------------------------;Other Stations ;NOTE! Use the system configuration tool to create stations for the PC-NET! ;NET 1 (DCP-NET) stations ;#CREATE STA:V = LIST(; TT = "EXTERNAL",; ST = "RTU",; ND = 1,; TN = 1) ;#CREATE STA1:B = %STA

Copy the STA1 section and paste it directly afterwards.


;---------------------------------------------------;Other Stations ;NOTE! Use the system configuration tool to create stations for the PC-NET! ;NET 1 (DCP-NET) stations ;#CREATE STA:V = LIST(; TT = "EXTERNAL",; ST = "RTU",; ND = 1,; TN = 1) ;#CREATE STA1:B = %STA

FISUB
1MRS751567-MTR 22

O246

IEC 61850 EXERCISE 4

;#CREATE ; TT = ; ST = ; ND = ; TN = ;#CREATE

STA:V = LIST("EXTERNAL","RTU",1,1) STA1:B = %STA

Change the pasted STA1 section in the following way.


#CREATE TT = ST = ND = TN = #CREATE STA:V = LIST("EXTERNAL","SPA",2,7) STA7:B = %STA

Save the SYS_BASCON.COM file and restart the SYS 600. Remember to open SYS 600 Notify so that you can see that there are no error messages when you start SYS 600.

FISUB
1MRS751567-MTR 23

O246

IEC 61850 EXERCISE 5

Exercise 5
5. Importing process objects
In this exercise you will create process objects with the help of SCL Importer and OPC PO List Tool.

5.1 SCL Importer Start MicroSCADA Pro SYS 600 Monitor and double-click SCL Importer from the Application Objects page in the Tool Manager. Select the correct SCL file by pressing the button with three dots. Locate the .CID file (Configuration.cid) you saved on your computer in the exercise 2 and Open it. Fill in the Object Identification information according to the following picture. Make sure that the Subnetwork field contains exactly the following text: IEC61850 Subnetwork. This is how the text appears in the OPC DA Client.

FISUB
1MRS751567-MTR 24

O246

IEC 61850 EXERCISE 5

Press Import. Press the View Log button in order to see if every item has been imported properly.

Close the log file and exit the SCL Import tool from the File menu.

27.2 OPC PO List Double click OPC PO List from the System Configuration page in the Tool Manager in order to create the necessary process objects.

FISUB
1MRS751567-MTR 25

O246

IEC 61850 EXERCISE 5

Select Edit / Include All.

Press OK to accept the suggested station number. Select File / Save As

FISUB
1MRS751567-MTR 26

O246

IEC 61850 EXERCISE 5

Save the list with the default name OPCPOLIST.PL by pressing OK.

Click Save.

Click OK for All to generate bit addresses automatically.

FISUB
1MRS751567-MTR 27

O246

IEC 61850 EXERCISE 5

Close the OPC PO List Tool. Exit Tool Manager and end the MicroSCADA session.

FISUB
1MRS751567-MTR 28

O246

IEC 61850 EXERCISE 6

Exercise 6
6. OPC DA Client Configuration Tool
In this exercise you will configure and start the OPC DA Client. 28.1 Configure the OPC DA Client Start the OPC DA Client Configuration Tool by double clicking the OPC DA Client icon in the MicroSCADA Pro Control System SYS600 window and then double clicking the OPC DA Client Configuration Tool icon.

Select File / New.

FISUB
1MRS751567-MTR 29

O246

IEC 61850 EXERCISE 6

Select Browse in the Server Properties dialog and locate the correct OPC server (ABB.IEC61850_OPC_DA_Server.Instance[1].1) from the list of available servers.

Press OK.

Press Next. Fill in the CPI Node Properties according to sys_bascon.

FISUB
1MRS751567-MTR 30

O246

IEC 61850 EXERCISE 6

Press Finish. Select File / Auto Configure Browse for the Process Object List file by pressing the button with three dots. Select the file you saved in previous exercise in connection with the OPC PO List tool. You can find the file under C:\sc\sys\active\sys_.

Press Open.

FISUB
1MRS751567-MTR 31

O246

IEC 61850 EXERCISE 6

Select Configure. This is how your tree hierarchy should now look like:

Close the OPC DA Client Configuration Tool and save the configuration file for example with name IEC61850.

FISUB
1MRS751567-MTR 32

O246

IEC 61850 EXERCISE 6

28.2 Start the OPC DA Client Double click the OPC DA Client Control Panel. Press New Instance and then Browse in order to find the file you saved in previous exercise.

Select the correct file and press Open.

Press OK.

FISUB
1MRS751567-MTR 33

O246

IEC 61850 EXERCISE 6

Press OK again. Then press Trace and select High. Press OK.

If you now press the Start Notify button, you can monitor the communication. Close the List of OPC DA Client instances dialog.

FISUB
1MRS751567-MTR 34

O246

IEC 61850 EXERCISE 7

Exercise 7
7. Creating display picture
In this exercise you will use the Display Editor in order to create a picture of the bay.

29.1 Starting Picture Editor Start MicroSCADA and SYS 600 Monitor Pro and Login.

Open the Display Builder by navigating to Tools / System Tools / Display Builder

FISUB
1MRS751567-MTR 35

O246

IEC 61850 EXERCISE 7

Create a new display by selecting File / New. Activate Snap and Grid from the View menu.

FISUB
1MRS751567-MTR 36

O246

IEC 61850 EXERCISE 7

29.2 Inserting objects to the display Select Actions / Object Browser to open the Object Browser. The application in the Object Browser window should be 1 - TUTOR. Press Select and you can see all the available objects in the tree structure.

FISUB
1MRS751567-MTR 37

O246

IEC 61850 EXERCISE 7

Add Local/Remote switch to your display picture by selecting Bay and pressing Create or by dragging and dropping the item to your picture. In a similar way, add position indications for the circuit breaker (Q01), disconnectors (Q3, Q4, Q92) and earth-switch (Q91). Add also phase current and neutral current measurements.

FISUB
1MRS751567-MTR 38

O246

IEC 61850 EXERCISE 7

Save the picture by selecting File / Save As.

Exit the Display Builder.

FISUB
1MRS751567-MTR 39

O246

IEC 61850 EXERCISE 7

29.3 Creating Station L/R switch with Object Navigator Navigate to Tools / System Tools / Tool Manager in the Monitor Pro window.

Double-click the Obj Navigator icon on the Application Objects page.

The Station L/R switch is not included in the connectivity package for REF as the process data for the Station L/R switch does not originate in REF 543. In our system, the Station L/R switch is not connected to the process but it is still needed in our application picture. In order to create the Station L/R switch manually, select Object / Install Standard Function

FISUB
1MRS751567-MTR 40

O246

IEC 61850 EXERCISE 7

Navigate to Station in the Standard Functions tree and press Install.

Fill in the correct information for the Station function according to the following picture.

FISUB
1MRS751567-MTR 41

O246

IEC 61850 EXERCISE 7

Press Apply. Select Tools page and double-click the Process Object Tool. Press Create All.

FISUB
1MRS751567-MTR 42

O246

IEC 61850 EXERCISE 7

Press Close and OK. Close the Install Standard Function window. The Station should now appear in your Process Objects list.

Close the Object Navigator and return to the Display Builder. Open the Object Browser and press Select again. Drag and drop IEC61850 to your picture in order to add the Station L/R switch there.

FISUB
1MRS751567-MTR 43

O246

IEC 61850 EXERCISE 7

29.4 Editing data variables for bay and controllable objects Navigate to Edit / Data Variables

FISUB
1MRS751567-MTR 44

O246

IEC 61850 EXERCISE 7

Change the Swap for the IEC6185020_KVBAY.State from None to swap values 0 and 1 and click Apply.

FISUB
1MRS751567-MTR 45

O246

IEC 61850 EXERCISE 7

Change the Swap for the IEC6185020_KVBAYQ01.State from Swap values 1 and 2 to None and click Apply.

FISUB
1MRS751567-MTR 46

O246

IEC 61850 EXERCISE 7

In a similar way, you should change the swapping to None with the disconnectors and earth-switch. Save the picture and exit Display Builder. 29.5 Defining the first picture shown after login Navigate to Tools / Options in the Monitor Pro window.

FISUB
1MRS751567-MTR 47

O246

IEC 61850 EXERCISE 7

Choose Select File.

Select the display picture that you previously saved and press Open. Press OK and the first picture shown after login will be the display picture you created.

FISUB
1MRS751567-MTR 48

O246

IEC 61850 EXERCISE 7

29.6 Testing If the Bay L/R switch is not remotely controllable, go to the Object Navigator. Select IEC6185020_KVBAY and 10. Then select Object / Standard Function Properties

L/R_REMOTELY_CONTROLLABLE has to be crossed.

FISUB
1MRS751567-MTR 49

O246

IEC 61850 EXERCISE 7

Press Apply. Select Tools and double-click the Process Object Tool. Press Create All and Close. Press OK. Select IEC6185020_KVBAYQ01 and 10. Then select Object / Standard Function Properties BAY_LR_POLARITY should be Remote=0, Local=1.

FISUB
1MRS751567-MTR 50

O246

IEC 61850 EXERCISE 7

Press Apply. Make similar changes to the disconnectors and earthswitch. Then exit the Object Navigator. Go to Tools / Options in the Monitor Pro window. System location should be Substation control system. Press OK. Test the function of the objects in your picture. Your Station L/R switch should be in station mode and the Bay L/R switch in remote mode.

FISUB
1MRS751567-MTR 51