You are on page 1of 1

UCHC MARB

Farmington,CT 06030
VFD PM Checklist / Worksheet Equipment TAG VFD Manufacturer VFD Model Bypass Model VFD SW/FW Fault History: VFD Fuses: N/A VFD O.L. Config: 1050s/100% Bypass O.L. Config: VFD U.V. Config: System Check Set / Confirm VFD Date/Time Back-up Parameters to Panel Ambient Temp VFD Temp at Check-out (Display) IR Scan of VFD / Panel Inspect / Tighten all Elec. Conn. Clean VFD & Bypass Panel Check all Panel Indicator Lamps / Data X X 19c 33.5c X X X X VFD Freq Limits: 12 TO 57 Hz www.flowtechinc.com DATE Location VFD S/N Bypass S/N Operating Hours DC UNDERVOLT Main Fuses: VFD I-Limit Setting: 64.9a

RTU-3-SF-1
ABB ACH550UH059A4 None 202C Hex OVERCURRENT

3/23/13
Roof 2042901105 None 72.22kh DC UNDERVOLT

System Check Check Cooling Fan Operation Record Fan Capacitor Rating Record Fan Capacitor Actual Motor / Wire Insulation Check Check Speed Control Signal Check Other I/O Signals Perform Static Diode / IGBT Test Reset VFD Fault History OPERATING SPEED 484 341 19 Vac Vac Amps C-A: C-A: C: C: 481 342 20 Vac Vac Amps

/ Data X N/A N/A X X X X X 44.1 HZ

DYNAMIC SYSTEM POWER CHECKS Input Voltage A-B: Output Voltage A-B: Input Current Output Current DC Bus Voltage A: A: 483 340 15 29 Vac Vac Amps Amps 662 649 B-C: B-C: B: B: Vdc

Display 342 Vac

Display 28.2 648 0 672 N/A N/A N/A N/A N/A Amps Vdc Hz

28.5 Amps

29.5 Amps 6 Vac

DC Level:

AC Level:

STATIC SYSTEM VOLTAGE CHECKS DC Bus Voltage +10vdc VFD Supply +24vdc VFD Supply Control TX Voltage +7vdc E-Bypass V +24vdc E-Bypass V DC Level: DC Level: Vdc Vdc DC Level: DC Level: DC Level: 661 10 28 Vdc Vdc Vdc

OPERATING SPEED AC Level: AC Level: AC Level: AC Level: AC Level: AC Level: 15 12 21 Vac mVac mVac