Professional Documents
Culture Documents
SF6-circuit
breaker
ABB Switchgear
Breaking principle
Arc
contact
Main
contact
Nozzle
Moving
cylinder
Closed position
Fixed
plunger
Breaking
Open position
The breaking pole in
different positions.
Breaking poles
Breaking gas
SF6 (sulphurhexafluoride) gas possesses a
unique combination of properties that
makes it extremely suitable for use in
circuit breakers. This has been confirmed
by service experience from more than
25,000 HPA breakers installed throughout
the world.
SF6 gas has an insulation strength some
three times higher than that of air at an
overpressure of 2 bar, which is even
higher than that of transformer oil.
Operating device
The HPA breaker is provided with a
simple and dependable operating device
based on well established principles in
combination with many years of service
experience.
The maintenance-free bearings and the
ease of dismantling and removing
breaking poles and operating devices are
examples of valuable properties that
reduce maintenance costs.
The HPA breaker is operated by a
spring-loaded operating device that is
normally tensioned by an electric motor. It
can also be tensioned manually.
The tripping spring is automatically
tensioned when the breaker is switched
on. After each make operation, the motor
starts and tensions the making spring.
A breaker that is switched on can then
perform an Off-On-Off operation without
having to tension the making spring in
between, which means that the breaker
can also be used for fast reconnection (a
further On-Off operation can be made
with a normal time lag).
The breaker has making and tripping
coils for electric operation and can also be
supplied with pushbuttons for manual
operation. There is space for an undervoltage release or a further tripping coil.
A counter for the number of operations
and indicators for tensioned/untensioned
making spring and open/closed breaker
are included as standard.
The operating device is easily accessible
in the breakers rack and can be easily
dismantled and replaced.
Lifetime
The HPA breaker requires a minimum of
maintenance. The gas and the breaking
poles do not need to be replaced and burnElectrical endurance of
the HPA circuit breaker.
90 mm
367 mm
Phase distance
185 or 210 mm
139 mm
640 mm
4.5 mm
kV
3.6 12
17
24
36
...................................................
...........................
..............................
...........................
.............................
...........................
.............................
.........................................................................................
kV
15
26
30
........................................................................................
Broschyr 1 VEB 580901-914. Edition 2b, 98-08. Production: Roos & Co Vsters. Stenby Offset. 2000 ex.
ABB Switchgear AB
Medium Voltage Division
12
Box 1023
S-732 27 Arboga, Sweden
Telephone: +46 589 851 00
Telefax:
+46 589 852 90
E-mail:
medium.voltage@seswg.mail.abb.com