ss 1 Remote-Control, Signaling Article 725 Class 2 Remote-Control, Signaling Article 725 Class 3 Remote-Control, Signaling Article 760 Fire Alarm Power-Limited Circuits Article 760 Fire Alarm Power-Limited Circuits Article 770 Optical Fiber Cables Article 800 Telecommunications Systems Article 820 Cable Television (CATV) Article 820 Network LowPowered Broadband Article 820 Network MediumPowered Broadband
TABLE 7-1
CL2 - Class 2 Cable [725-71] OF - Optical Fiber Cable [770-71] CL3 - Class 3 Cable [725-71] MP - Multipurpose Cable (Coaxial) [800-50]* FPL - Power-Limited Fire Alarm Cable [760-71] CATV - CATV Cable [820-53]* NFPL - Nonpower-Limited Fire Alarm Cable [760-31] BL - Broadband Low-Power Cable [830-55]* CM - Communications Cable [800-53]* BM - Broadband Medium-Power Cable [830-55]* * Listing and marking are not required where the length of the cable within the building measured from its point of entrance does not exceed 50 feet [800-50 Exc. 3, 820-50 Exc. 3, and 830-55(c) Exc. 4].
The Code may require additional marking for low-voltage and limited-energy cables, depending on the intended use of the cable such as: The P suffix stands for plenum rating. Plenum cables are listed for use in environmental air space (dropped ceiling space used for return air) and they have adequate fire-resistant and low smoke-producing characteristics.
The R suffix stands for riser rating. Riser cables are listed for use in vertical shafts (risers) and they have fire-resistant characteristics to prevent the carrying of fire from floor to floor. The X suffix indicates that a cable is listed for use in dwellings and in raceways.
FIGURE 7-4