1-11. Power-Limited Fire Alarm Circuit Power (Inherently-Limited) (ac) Voltage Ampere O to 20 Volts 5 ampere 2O to 3O Volts 3.33 ampere 3O to 100 Volts 1 ampere Power 100VA 100VA 100 VA
Wiring Methods - Power-limited fire alarm circuit conductors must be installed using either of the following methods: An acceptable wiring method described in Chapter 3, splices must be in outlet boxes in accordance with Section 300-15 [760-52(a)], Exposed Power-Limited Fire Alarm (FPL) cables, communications wires and cables (CM), and multipurpose coaxial cables (MP) [Figure 760-61] can be used where not subject to physical damage [760-52(b) and 760-61]. But all splices and devices must be installed within an outlet box in accordance with Section 300-15 [760-52(b)].
FIGURE 1-12