K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories

Class 8502

CONTENTS Description Page General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Mini-contactors Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Auxiliary Contacts and Timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 Dimensions and Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Overload Relays Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 Dimensions, Mounting, and Schematics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 Low-consumption Mini-contactors Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 Auxiliary Contacts, Timers, and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 Dimensions and Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

Schneider Electric Brands

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


General Information
K-line Mini-contactors, Enclosed Starters, and Overload Relays are ideal for general-duty applications where small size and reliability are key concerns. They feature: Three contactor ratings for the USA market: K06 rated for 3 HP motors at 480 Vac or 600 Vac. K09 rated for 5 HP motors at 480 Vac or 600 Vac. K12 rated for 7.5 HP motors at 480 Vac or 10 HP at 600 Vac. Space savings the special magnet and armature structure allow for a DC coil-operated device with the same physical size and panel footprint of the AC coil version. IP20-rated touch-safe terminals with both North American and International terminal markings Mountable on 35mm DIN rail or panel mount with screws Available in 3-pole contactor versions with built-in auxiliary contact for holding circuit or 4-pole contactor versions. Easily-installed accessories. 2-pole or 4-pole instantaneous auxiliary contact blocks with screw clamp, slip-on, or spring terminals. Transient voltage surge suppressors. Electronic 1 to 30 second on-delay timers. Four wiring methods to reduce installation time: Captive screw terminals for use with either Phillips or slotted head screwdrivers. Slip-on terminals for quick installation of single 1/4" or double 1/8" tabs. Terminal pins for soldering the contactor directly to a printed circuit board. Spring terminals for extreme-vibration applications. Control circuit flexibility All versions of the K-line mini-contactors are available with an AC, DC, or low-consumption DC operating coil. The low-consumption DC coil operating device can be energized by a low level DC signal from a computer or PLC and includes built-in transient suppression and LED On indicator. Bimetallic overload relays The K-line Class 10 bimetallic overload relays are ambient-compensated and include single-phase sensitivity for phase unbalance and phase loss protection. Standard features include isolated N/C trip contact and N/O alarm contact, manual or automatic reset function, tamper resistant window for full load current settings, and Test trip button. Five pins connect to the contactor load side terminals three for the power circuit and two for the control circuit which eliminate customer wiring for the 3wire control holding circuit.

34 2001 Schneider Electric All Rights Reserved


04/01

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Characteristics of Type LCK and LPK Contactors

Environment
Conforming to IEC 60947 Conforming to VDE 0110 gr C Rated insulation voltage (Vi) Conforming to BS 5424, NF C 20-040 V 690 600 8 Conforming to CSA 22-2 No. 14, UL 508 V Rated impulse withstand voltage (Vimp) Conforming to standards kV V V 690 750

Meets the essential requirements of the LV IEC 60947, NF C 63-110, VDE 0660, BS 5424, UL508, CSA 22-2 No. 14 & EMC directives LCK06, LCK09, LCK12 LPK06, LPK09, LPK12 Conforming to IEC 60068 (DIN 50016) Conforming to VDE 0106 Storage Operation Without derating Vertical axis E164862 NLDX (Screw Clamp) E164862 NLDX2 (Slip-on &
Solder Pin)

Approvals

LR 43364 321104

Protective treatment Degree of protection Ambient air temperature around the device Maximum operating altitude

TC (Fungus-proof, tropicalization protection) Protection against direct finger contact - 50 to + 80C (-58 to +176F) - 25 to + 50C (-13 to +122F) 2000 m (6562 ft.) Horizontal axis

90

90

Operating position

90
Without derating Conforming to UL 94 Flame resistance

Without derating

18 0

Conforming to NF F 16-101 and 16-102 Shock resistance (1/2 sine wave, 11 ms) Vibration resistance 5 to 300 Hz Safe circuit separation Cabling Solid or stranded cable Solid cable Screw-clamp terminals Stranded cable without cable end Stranded cable with cable end Slip-on connectors Solder pins for printed circuit board Tightening torque Terminal referencing x Safety extra low voltage. Clip With locating device between power and control circuits Contactor open Contactor closed Contactor open Contactor closed Conforming to VDE 0106 and IEC 60536

Phillips no. 2 or 3/16 slotted head screwdriver 0.8 Nm (7lb.-in.) Conforming to standards EN 50005 and EN 50012 Up to 5 contacts

04/01

2001 Schneider Electric All Rights Reserved

90
10 gn 15 gn 2 gn 4 gn SELV x, up to 400 V Min AWG 1 x 18 mm2 1 x 1.5 mm2 1 x 0.75 mm2 1 x 0.34 4 mm x 35 microns

Derate current carrying capability by 15% when not mounted vertically

Self-extinguishing material V1 Conforming to requirement 2

Max 2 x 14 or 1 x 12 2x4 2x4 1 x 1.5 + 1 x 2.5

Max to IEC 60947 1 x 4 + 1 x 2.5 2 x 2.5 1 x 1.5 + 1 x 2.5

2 x 2.8mm or 1 x 6.35mm (2 x 0.110 in. or 1 x 0.250 in.)

35

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Characteristics of Type LCK and LPK Contactors

Pole Characteristics
Conventional thermal current (Ith) For ambient temperature 50 C (122 F) Rated operational frequency Frequency limits of the operational current Rated operational voltage (Ve) I rms conforming to NF C 63-110 and IEC 60947 LCK06, LPIK06, LCK09, LPK09 Rated making capacity LCK12, LPK12 LCK16 Conforming to NF C 63-110 and IEC 60947 LCK06, LPK06, LCK09, LPK09 I rms LCK12, LPK12 LCK16 In free air for a time "t from cold state ( 50 C [122 F]) Permissible short-time rating LCK06, LPK06, LCK09, LPK09 LCK12, LPK12 LCK16 By circuit breaker Short-circuit protection By fuses Average impedance/pole At Ith and 50 Hz Maximum rated operational current for a temperature 50 C (122 F) Maximum rated operational current for a temperature 70 C (158 F) Max 400% of motor FLA 3 m 20 A 16 A for Ve only On-load factor Rated operational current limits in relation to on-load factor and operating frequency 300 op. cycles/hour 120 op. cycles/hour 30 op. cycles/hour 90% 13 A 15 A 19 A 60% 15 A 18 A 20 A 30% 18 A 19 A 20 A 20 A 50/60 Hz Up to 400 Hz 690 Vac 110 A 144 A 160 A 220/ 230 V 110 A 1s 90 A 115 A 380/ 400 V 110 A 5s 85 A 105 A 415 V 110 A 10 s 80 A 100 A 440 V 110 A 110 A 110 A 30 s 60 A 75 A 500 V 80 A 80 A 80 A 1 min 45 A 55 A 660/ 690 V 70 A 70 A 70 A 3 min 40 A 50 A 15 min 20 A 25 A

Rated breaking capacity

Select in accordance with NEC and local codes

Utilization in category AC-1: resistive circuit, heating, lighting (Ve 440 V)

Apply the following coefficients to the current values given above. These take into account the often unbalanced current distribution between poles Increase in operational current by paralleling of poles 2 poles in parallel: K = 1.60 3 poles in parallel: K = 2.25 4 poles in parallel: K = 2.80 Operational power according to the voltage LCK06, LPK06 LCK09, LPK09 Utilization in category AC-3 Squirrel cage motors LCK12, LPK12 Voltage 50 or 60 Hz 115 V 1-phase Motor ratings Motor ratings 0.37 kW 0.55 kW 0.75 kW 1.1 kW 220 V 220/ 240 V 3-phase 1.5 kW 2.2 kW 2.2 kW 4 kW 3 kW 4 kW 5.5/4 (480) kW 5.5/4 (480) kW 600 100% 220 220/ 208 3-phase 1 HP 1.5 HP 2 HP 1.5 HP 2 HP 3 HP 3 HP 3 HP 3 HP 3 HP 5 HP 7.5 HP 3 HP 5 HP 10 HP 220/ 240 460/ 480 3 kW 4 kW 3 kW 4 kW 380/ 415 V 440/ 480 V 500/ 600 V 660/ 690 V

Motor ratings

3 kW

5.5 kW

4 kW

4 kW

LCK16

Motor ratings

4 kW

7.5 kW

4 kW 900 75% 575/ 600

4 kW 1200 50%

Maximum operating rate (in operating cycles/ hour in relation to percentage of rated power) Operational power according to the voltage Utilization in category AC-3 Squirrel cage motors LCK06, LPK06 LCK09, LPK09 LCK12, LPK12 LCK16, LPK16 Voltage 50 or 60 Hz Motor ratings Motor ratings Motor ratings

Op. cycles/hour Power 115 1-phase 0.5 HP 0.5 HP 1 HP

Not UL Listed or CSA Certified.

36 2001 Schneider Electric All Rights Reserved


04/01

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Characteristics of Type LCK and LPK Contactors

Control Circuit Characteristics


Type Rated control circuit voltage (Vc) Control voltage limits ( 50 C [122 F]) single voltage coil Average consumption at 20 C (68 F) and at Vc Sealed Heat dissipation Between coil energization and: - opening of the N/C contacts - closing of the N/O contacts Operating time at 20 C (68 F) and at Vc Between coil de-energization and: - opening of the N/O contacts - closing of the N/C contacts Maximum immunity to micro-breaks Maximum operating rate Mechanical durability at Vc In millions of operating cycles x v In operating cycles per hour 50/60 Hz coil DC coil 10 to 20 ms 15 to 25 ms 2 ms 3600 10 5 30 ms 40 ms 2 ms 3600 10 5 10 ms 15 ms 2 ms 3600 10 5 5 to 15 ms 10 to 20 ms 25 to 35 ms 30 to 40 ms 25 to 35 ms 30 to 40 ms 4.5 VA 1.3 3 VA 3 3W 3 For operation v For drop-out Inrush LC1 LC2 LC7 LC8 LP1 LP2 12 to 690 Vac x 0.8 to 1.15 Vc 0.20 Vc 30 VA 24 to 230 Vac 0.85 to 1.1 Vc 0.10 Vc 3 VA 12 to 250 Vdc x 0.8 to 1.15 Vc 0.10 Vc 3W

For mains supplies with a high level of interference (voltage surge > 800 V), use a suppressor module LA4KE1FC (50 to 129 V) or LAFKE1UG (130 to 250 V); see page 52. LC1K16: 0.85 to 1.15 Vc.

37
04/01

2001 Schneider Electric All Rights Reserved

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Characteristics of Type LCK and LPK Contactors
Auxiliary Contact Characteristics and Instantaneous Contact Blocks
Number of contacts Rated operational voltage (Ve) On LCK or LPK On LA1K Up to Conforming to BS 5424 Conforming to IEC 60947 Rated insulation voltage (Vi) Conforming to VDE 0110 group C Conforming to CSA C 22.2 No.14, UL 508 Conventional thermal current (lth) Frequency of operational current V min (DIN 19 240) Minimum switching capacity I min Short-circuit protection Rated making capacity Conforming to IEC 60947 and VDE 0660, gl fuse Conforming to IEC 60947 I rms 1s Overload current Permissible for 500 ms 100 ms Insulation resistance Non-overlap distance Linked contacts conforming to INRS and BIA spec. 5 mA 10 A 110 A 80 A 90 A 110 A > 10 m 0.5 mm For ambient temperature 50 C (122 F) 750 Vac 600 Vac 10 A Up to 400 Hz 17 Vac 1 2 or 4 690 Vac 690 Vac 690 Vac

Operational power of contacts conforming to IEC 60947

AC supply, category AC-15 Electrical durability (valid up to 3600 operating cycles per hour) on an inductive load such as the coil of an electromagnet: making current (power factor 0.7) = 10 times the breaking current (power factor 0.4). V 24 48 17 7 1000 48 96 34 14 2050 110/ 127 240 86 36 5000 220/ 230 440 158 66 440 880 317 132 600/ 690 1200 500 200

DC supply, category DC-13 Electrical durability (valid up to 1200 operating cycles per hour, on an inductive load such as the coil of an electromagnet, without economy resistor, the time constant increasing with the load. V W W W W 24 120 55 15 720 48 80 38 11 600 110 60 30 9 400 220 52 28 8 300 440 51 26 7 230 600 50 25 6 200

1 million operating cycles 2 million operating cycles 10 million operating cycles Occasional making capacity

VA VA VA VA

10000 13000 9000

Power in broken VA
16 000

Power in broken W

Time constant in ms

1 Breaking limit of contacts valid for


maximum of 50 operating cycles at 10 s intervals (breaking current = making current x power factor 0.7).

10 000 8000 6000 5000 4000 3000 2000 1000 800 600 500 400 300 200 100 80 60 40 24 48

1000 700 500

3
300 200 100 80 60 50 40 30 20

2 Electrical durability of contacts for:


- 1 million operating cycles (2a) - 3 million operating cycles (2b) -10 million operating cycles (2c).
4

250 200 140

2a 2b

3 Breaking limit of contacts valid for


maximum of 20 operating cycles at 10 s intervals with current passing for 0.5 s per operating cycle.

2a

100

2b

2c
2c
110 120 220 380 500 440 690 V

4 Thermal limit.

50 20

10 8 6 12 24 48 110 220 440 600 V

38 2001 Schneider Electric All Rights Reserved


04/01

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Selection of Contactors for Motor Control
General-purpose Contactors for AC Control Circuits The table below shows general-purpose contactors. The contactors mount on 35 mm DIN rails or with 4 mm (# 6) screws. The wire termination screws are in the open, ready-to-tighten position. For information on add-on auxiliary contact blocks and accessories, see page 50 to 53.
Horsepower Ratings for North American Applications Maximum Horsepower Rating Category AC-3, 50/60 Hz 1-Phase 115/ 120 V HP 230/ 240 V HP 3-Phase 200/ 208 V HP 220/ 240 V HP 460/ 480 V HP 575/ 600 V HP Max. Inductive Current A Kilowatt Ratings for International Applications Standard power ratings of 3-phase motors, 50/60 Hz in category AC-3 220 V 230 V kW 380 V 415 V kW 440/500 V 660/690 V kW Rated operational current, up to 440 V A Screw clamp Slip-on 1 x 0.25 in., or 2 x 0.11 in. 0.5 1 1.5 1.5 3 3 6 1.5 2.2 3 6 Solder pins for printed circuit board Spring terminals Screw clamp Slip-on 1 x 0.25 in., or 2 x 0.11 in. 0.5 1.5 2 3 5 5 9 2.2 4 4 9 Solder pins for printed circuit board Spring terminals Screw clamp Slip-on 1 x 0.25 in., or 2 x 0.11 in. 12 Solder pins for printed circuit board Spring terminals Screw clamp Slip-on 1 x 0.25 in., or 2 x 0.11 in. 16 Solder pins for printed circuit board Spring terminals w v Auxiliary Contacts Type of Connection Catalog Number wv N/O 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 N/C 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 LC1K0610 LC1K0601 LC1K06107 LC1K06017 LC1K06105 LC1K06015 LC1K06103 LC1K06013 LC1K0910 LC1K0901 LC1K09107 LC1K09017 LC1K09105 LC1K09015 LC1K09103 LC1K09013 LC1K1210 LC1K1201 LC1K12107 LC1K12017 LC1K12105 LC1K12015 LC1K12103 LC1K12013 LC1K1610 LC1K1601 LC1K16107 LC1K16017 LC1K16105 LC1K16015 LC1K16103 LC1K16013 0.40 (0.180) 0.40 (0.180) 0.40 (0.180) 0.40 (0.180) 0.46 (0.210) 0.46 (0.210) 0.40 (0.180) 0.40 (0.180) 0.40 (0.180) 0.40 (0.180) 0.40 (0.180) 0.40 (0.180) 0.46 (0.210) 0.46 (0.210) 0.40 (0.180) 0.40 (0.180) 0.40 (0.180) 0.40 (0.180) 0.40 (0.180) 0.40 (0.180) 0.46 (0.210) 0.46 (0.210) 0.40 (0.180) 0.40 (0.180) 0.40 (0.180) 0.40 (0.180) 0.40 (0.180) 0.40 (0.180) 0.46 (0.210) 0.46 (0.210) 0.40 (0.180) 0.40 (0.180) Weight lb. (kg)

0.5

1.5

7.5

10

12

5.5

4 (> 440) 5.5 (440)

Not for North American applications not UL Listed or CSA Certified

7.5

4 (440) 5.5 (440)

Use voltage codes on page 49 Coil Selection to complete catalog number. For mains supplies with a high level of interference (voltage surge > 800 V), use a suppressor module LA4KE1FC (50 to 129 V) or LA4KE1UG (130 to 250 V), see page 52.

LC1K0610

LC1K06107

LC1K09103

39
04/01

2001 Schneider Electric All Rights Reserved

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Selection of Contactors for Motor Control
Sensitive-Environment Contactors for AC Control Circuits The tables below show the kilowatt ratings (for international applications) and horsepower ratings (for North American applications) of contactors for use in sensitive environments. They are recommended for use in areas sensitive to noise, high interference mains supplies, and so forth. The contactors mount on 35 mm DIN rails or with 4 mm (# 6) screws. The wire termination screws are in the open, ready-totighten position, and include a coil with a built-in rectifier and suppressor. For information on add-on auxiliary contact blocks and accessories, see page 50 to 53. LC7K06105
Horsepower Ratings for North American Applications Maximum Horsepower Rating Category AC-3, 50/60 Hz 1-Phase 115/ 120 V HP 230/ 240 V HP 3-Phase 200/ 208 V HP 220/ 240 V HP 460/ 480 V HP 575/ 600 V HP Max. Inductive Current A Kilowatt Ratings for International Applications Standard power ratings of 3-phase motors, 50/60 Hz in category AC-3 220 V 230 V kW 380 V 415 V kW 440/500 V 660/690 V kW Rated operational current, 440V up to: A Screw clamp 0.5 1 1.5 3 3 6 6 1.5 2.2 3 6 Slip-on 1 x 0.25 in., or 2 x 0.11 in. Solder pins for printed circuit board Screw clamp 0.5 1.5 2 3 5 5 9 2.2 4 4 9 Slip-on 1 x 0.25 in., or 2 x 0.11 in. Solder pins for printed circuit board Screw clamp 0.5 1.5 3 3 7.5 10 12 3 5.5 4 (> 440) 5.5 (440) 12 Slip-on 1 x 0.25 in., or 2 x 0.11 in. Solder pins for printed circuit board w Use voltage codes on page 49 Coil Selection to complete catalog number. Auxiliary Contacts Type of connection Catalog Number w N/O 1 1 1 1 1 1 1 1 1 N/C 1 1 1 1 1 1 1 1 1 LC7K0610 LC7K0601 LC7K06107 LC7K06017 LC7K06105 LC7K06015 LC7K0910 LC7K0901 LC7K09107 LC7K09017 LC7K09105 LC7K09015 LC7K1210 LC7K1201 LC7K12107 LC7K12017 LC7K12105 LC7K12015 0.50 (0.225) 0.50 (0.225) 0.50 (0.225) 0.50 (0.225) 0.50 (0.225) 0.50 (0.225) 0.50 (0.225) 0.50 (0.225) 0.50 (0.225) 0.56 (0.255) 0.56 (0.255) 0.50 (0.225) 0.50 (0.225) 0.50 (0.225) 0.50 (0.225) 0.50 (0.225) 0.56 (0.255) 0.56 (0.255) Weight lb. (kg)

40 2001 Schneider Electric All Rights Reserved


04/01

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Selection of Contactors for Motor Control
Three-Pole Contactors for DC Control Circuits The table below shows the kilowatt ratings (for international applications) and horsepower ratings (for North American applications) for three-pole contactors for DC control circuits. The contactors mount on 35 mm DIN rails or with 4 mm (# 6) screws. The wire termination screws are in the open, ready-totighten position. For information on add-on auxiliary contact blocks and accessories, see page 50 to 53.
Horsepower Ratings for North American Applications Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 220 V 230 V kW 380 V 415 V kW 440/500 V 660/690 V kW Kilowatt Ratings for International Applications 3- phase 50/60 HZ 200/ 208 V HP 220/240 V 460/480 V HP HP Maximum Inductive Current in AC-3 575/600 V Category HP A Screw clamp Slip-on 1 x 0.25 in., or 2 x 0.11 in. 1.5 2.2 3 6 0.5 1 1.5 1.5 3 3 6 Solder pins for printed circuit board Spring terminals Screw clamp Slip-on 1 x 0.25 in., or 2 x 0.11 in. 2.2 4 4 9 0.5 1.5 2 3 5 5 9 Solder pins for printed circuit board Spring terminals Screw clamp Slip-on 1 x 0.25 in., or 2 x 0.11 in. 12 0.5 1.5 3 3 7.5 10 12 Solder pins for printed circuit board Spring terminals w Use voltage codes on page 49 Coil Selection to complete catalog number. Type of Connection Auxiliary Contacts Catalog Number w Weight lb. (kg)

Maximum Horsepower Ratings Rated operationa l current. up to 440 V A 1- phase 50/60 HZ 115/ 120 V HP 230/ 240 V HP

N/O 1 1 1 1 1 1 1 1 1 1 1 1

N/C 1 1 1 1 1 1 1 1 1 1 1 1 LP1K0610 LP1K0601 LP1K06107 LP1K06017 LP1K06105 LP1K06015 LP1K06103 LP1K06013 LP1K0910 LP1K0901 LP1K09107 LP1K09017 LP1K09105 LP1K09015 LP1K09103 LP1K09013 LP1K1210 LP1K1201 LP1K12107 LP1K12017 LP1K12105 LP1K12015 LP1K12103 LP1K12013 0.50 (0.225) 0.50 (0.225) 0.50 (0.225) 0.50 (0.225) 0.56 (0.255) 0.56 (0.255) 0.50 (0.225) 0.50 (0.225) 0.50 (0.225) 0.50 (0.225) 0.50 (0.225) 0.50 (0.225) 0.50 (0.225) 0.56 (0.255) 0.50 (0.225)) 0.50 (0.225) 0.50 (0.225) 0.50 (0.225) 0.50 (0.225) 0.50 (0.225) 0.56 (0.255) 0.56 (0.255) 0.50 (0.225) 0.50 (0.225)

5.5

4 (>440 V) 5.5 (440 V)

LP1K0610

LP1K06107

41
04/01

2001 Schneider Electric All Rights Reserved

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Selection of Contactors for Resistive Loads
Three- and Four-Pole Contactors for AC Control Circuits The tables below show general-purpose and sensitive-environment three- and four-pole contactors for AC control circuits. (The sensitive-environment contactors are recommended for use in areas sensitive to noise, high interference mains supplies, and so forth.) The contactors mount on 35 mm DIN rails or with 4 mm (# 6) screws. The wire termination screws are in the open, ready-to-tighten position. In addition, the sensitive-environment contactors include a coil with a built-in rectifier and suppressor. For information on add-on auxiliary contact blocks and accessories, see page 50 to 53. General-purpose Contactors x
Non-inductive loads Category AC-1 Maximum current at 50 C (122 F) A Power Poles Type of Connection Auxiliary Contacts Catalog Number w N/O 3 Screw clamp 3 4 2 3 3 4 2 3 Solder pins for printed circuit board 3 4 2 3 Spring terminals 3 4 2 N/C 2 2 2 2 N/O 1 1 1 1 N/C 1 1 1 1 LC1K0910 LC1K0901 LC1K09004 LC1K09008 LC1K09107 LC1K09017 LC1K090047 LC1K090087 LC1K09105 LC1K09015 LC1K090045 LC1K090085 LC1K09103 LC1K09013 LC1K090043 LC1K090083 0.56 (0.255) 0.56 (0.255) 0.40 (0.180) 0.40 (0.180) 0.56 (0.255) 0.56 (0.255) 0.40 (0.180) 0.40 (0.180) 0.56 (0.255) 0.56 (0.255) 0.46 (0.210) 0.46 (0.210) 0.56 (0.255) 0.56 (0.255) 0.46 (0.210) 0.46 (0.210) Weight lb. (kg)

LC1K09004
20

Slip-on 1 x 0.25 in. or 2 x 0.11 in.

Sensitive-environment Contactors
3 Screw clamp 3 4 2 3 20 Slip-on 1 x 0.25 in. or 2 x 0.11 in. 3 4 2 3 Solder pins for printed circuit board 3 4 2 2 2 2 1 1 1 1 1 1 LC7K0910 LC7K0901 LC7K09004 LC7K09008 LC7K09107 LC7K09017 LC7K090047 LC7K090087 LC7K09105 LC7K09015 LC7K090045 LC7K090085 0.56 (0.255) 0.56 (0.255) 0.56 (0.255) 0.56 (0.255) 0.56 (0.255) 0.56 (0.255) 0.56 (0.255) 0.56 (0.255) 0.56 (0.255) 0.56 (0.255) 0.56 (0.255) 0.56 (0.255)

LC7K090047

x For mains supplies with a high level of interference (voltage surge > 800 V), use a suppressor module LA4KE1FC (50 to 129 V) or LAFKE1UG (130 to 250 V), see page 52. w Use voltage codes on page 49 Coil Selection to complete catalog number.

42 2001 Schneider Electric All Rights Reserved


04/01

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Selection of Contactors for Resistive Loads
Three- and Four-pole Contactors for DC Control Circuits The table below shows three- and four-pole contactors for DC control circuits. The contactors mount on 35 mm DIN rails or with 4 mm (# 6) screws. The wire termination screws are in the open, ready-totighten position. For information on add-on auxiliary contact blocks and accessories, see page 50 to 53.
Power Poles Type of Connection Auxiliary Contacts Catalog Number w N/O 3 Screw clamp 3 4 2 3 Slip-on 1 x 0.25 in. or 2 x 0.11 in. 3 4 2 3 Solder pins for printed circuit board 3 4 2 3 Spring terminals 3 4 2 w N/C 2 2 2 2 N/O 1 1 1 1 N/C 1 1 1 1 LP1K0910 LP1K0901 LP1K09004 LP1K09008 LP1K09107 LP1K09017 LP1K090047 LP1K090087 LP1K09105 LP1K09015 LP1K090045 LP1K090085 LC1K09103 LC1K09013 LC1K090043 LC1K090083v 0.56 (0.225) 0.56 (0.225) 0.56 (0.225) 0.56 (0.225) 0.56 (0.225) 0.56 (0.225) 0.56 (0.225) 0.56 (0.225) 0.56 (0.225) 0.56 (0.225) 0.56 (0.225) 0.56 (0.225) 0.56 (0.225) 0.56 (0.225) 0.46 (0.210) 0.46 (0.210) Weight lb. (kg)

Non-inductive loads Category AC-1 Maximum current at 50 C (122 F) A

LP1K09004

20

Use voltage codes on page 49 Coil Selection to complete catalog number.

43
04/01

2001 Schneider Electric All Rights Reserved

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Selection of Reversing Contactors for Motor Control
Three-pole Reversing Contactors for AC Control Circuits The table below shows three-pole reversing contactors with integrated mechanical interlock. The contactors mount on 35 mm DIN rails or with 4 mm (# 6) screws. The wire termination screws are in the open, ready-to-tighten position. Customer wiring is required to connect coil terminations to electrical interlock; see page 56 (top row, center drawing). For information on add-on auxiliary contact blocks and accessories, see page 50 to page 53.
Horsepower Ratings for North American Applications Maximum Horsepower Rating Category AC-3, 50/60 Hz 1-Phase 115/ 120 V HP 230/ 240 V HP 3-Phase 200/ 208 V HP 220/ 240 V HP 460/ 480 V HP 575/ 600 V HP Max. Inductive Current A Kilowatt Ratings for International Applications Standard power ratings of 3-phase motors, 50/60 Hz in category AC-3 220 V 230 V kW 380 V 415 V kW 440/500 V 660/690 V kW Rated Operational Current, up to 440 V A Screw clamp v Slip-on 1 x 0.25 in., or 2 x 0.11 in. 0.5 1 1.5 1.5 3 3 6 1.5 2.2 3 6 Solder pins for printed circuit board Spring terminals Screw clamp v Slip-on 1 x 0.25 in., or 2 x 0.11 in. 0.5 1.5 2 3 5 5 9 2.2 4 4 9 Solder pins for printed circuit board Spring terminals Screw clamp v Slip-on 1 x 0.25 in., or 2 x 0.11 in. 12 Solder pins for printed circuit board Spring terminals Screw clamp v Slip-on 1 x 0.25 in., or 2 x 0.11 in. 16 Solder pins for printed circuit board Spring terminals w s v Auxiliary Contacts Type of Connection Catalog Number ws N/O 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 N/C 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 LC2K0610 LC2K0601 LC2K06107 LC2K06017 LC2K06105 LC2K06015 LC2K06103 LC2K06013 LC2K0910 LC2K0901 LC2K09107 LC2K09017 LC2K09105 LC2K09015 LC2K09103 LC2K09013 LC2K1210 LC2K1201 LC2K12107 LC2K12017 LC2K12105 LC2K12015 LC2K12103 LC2K12013 LC2K1610 LC2K1601 LC2K16107 LC2K16017 LC2K16105 LC2K16015 LC2K16103 LC2K16013 0.86 (0.390) 0.86 (0.390) 0.81 (0.370) 0.81 (0.370) 0.95 (0.430) 0.95 (0.430) 0.86 (0.390) 0.86 (0.390) 0.86 (0.390) 0.86 (0.390) 0.86 (0.390) 0.86 (0.390) 0.95 (0.430) 0.95 (0.430) 0.86 (0.390) 0.86 (0.390) 0.86 (0.390) 0.86 (0.390) 0.86 (0.390) 0.86 (0.390) 0.95 (0.430) 0.95 (0.430) 0.86 (0.390) 0.86 (0.390) 0.86 (0.390) 0.86 (0.390) 0.86 (0.390) 0.86 (0.390) 0.95 (0.430) 0.95 (0.430) 0.86 (0.390) 0.86 (0.390) Weight lb. (kg)

0.5

1.5

7.5

10

12

5.5

4 (> 440) 5.5 (440)

Not for North American applications not UL Listed or CSA Certified

7.5

4 (440) 5.5 (440)

Use voltage codes on page 49 Coil Selection to complete catalog number. For mains supplies with a high level of interference (voltage surge > 800 V), use a suppressor module LA4KE1FC (50 to 129 V) or LA4KE1UG (130 to 250 V), see page 52. Pre-wired power circuit connections are standard on screw clamp versions.

LC2K0610

LC2K06107

LC2K09103

44 2001 Schneider Electric All Rights Reserved


04/01

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Selection of Reversing Contactors for Motor Control
Sensitive-environment Reversing Contactors for AC Control Circuits The tables below show the kilowatt ratings (for international applications) and horsepower ratings (for North American applications) for reversing contactors with mechanical interlock for use in sensitive environments. They are recommended for use in areas sensitive to noise, high interference mains supplies, and so forth. A coil with incorporated rectifier and suppressor is standard. LC8K06105 The contactors mount on 35 mm DIN rails or with 4 mm (# 6) screws. The wire termination screws are in the open, ready-to-tighten position. Customer wiring is required to connect coil terminations to electrical interlock; see page 56 (top row, center drawing). For information on add-on auxiliary contact blocks and accessories, see page 50 to 53.
Kilowatt Ratings for International Applications Standard power ratings of 3-phase motors, 50/60 Hz in category AC-3 220 V 230 V kW 380 V 415 V kW 440/500 V 660/690 V kW Rated Operational Current, up to 440 V A Screw clamp v 0.5 1 1.5 3 3 6 6 1.5 2.2 3 6 Slip-on 1 x 0.25 in., or 2 x 0.11 in. Solder pins for printed circuit board Screw clamp v 0.5 1.5 2 3 5 5 9 2.2 4 4 9 Slip-on 1 x 0.25 in., or 2 x 0.11 in. Solder pins for printed circuit board Screw clamp v 0.5 1.5 3 3 7.5 10 12 3 5.5 4 (> 440) 5.5 (440) 12 Slip-on 1 x 0.25 in., or 2 x 0.11 in. Solder pins for printed circuit board w v Use voltage codes on page 49 Coil Selection to complete catalog number. Pre-wired power circuit connections are standard on screw clamp versions. Auxiliary Contacts Type of Connection Catalog Number w N/O 1 1 1 1 1 1 1 1 1 N/C 1 1 1 1 1 1 1 1 1 LC8K0610 LC8K0601 LC8K06107 LC8K06017 LC8K06105 LC8K06015 LC8K0910 LC8K0901 LC8K09107 LC8K09017 LC8K09105 LC8K09015 LC8K1210 LC8K1201 LC8K12107 LC8K12017 LC8K12105 LC8K12015 1.05 (0.480) 1.05 (0.480) 1.00 (0.460) 1.00 (0.460) 1.14 (0.520) 1.14 (0.520) 1.05 (0.480) 1.05 (0.480) 1.00 (0.460) 1.00 (0.460) 1.14 (0.520) 1.14 (0.520) 1.05 (0.480) 1.05 (0.480) 1.00 (0.460) 1.00 (0.460) 1.14 (0.520) 1.14 (0.520) Weight lb. (kg)

Horsepower Ratings for North American Applications Maximum Horsepower Rating Category AC-3, 50/60 Hz 1-Phase 115/ 120 V HP 230/ 240 V HP 3-Phase 200/ 208 V HP 220/ 240 V HP 460/ 480 V HP 575/ 600 V HP Max. Inductive Current A

45
04/01

2001 Schneider Electric All Rights Reserved

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Selection of Reversing Contactors for Motor Control
Three-pole Reversing Contactors for DC Control Circuits The table below show the kilowatt ratings (for international applications) and horsepower ratings (for North American applications) for three-pole reversing contactors with integrated mechanical interlock for DC control circuits. The contactors mount on 35 mm DIN rails or with 4 mm (# 6) screws. The wire termination screws are in the open, ready-to-tighten position. Customer wiring is required to connect coil terminations to electrical interlock; see page 56 (top row, center drawing). For information on add-on auxiliary contact blocks and accessories, see page 50 to 53.
Horsepower Ratings for North American Applications Maximum Horsepower ratings 1- phase 50/60 HZ 3- phase 50/60 HZ 220/ 460/ 575/ 240 V 480 V 600 V HP HP HP Maximum Inductive Current in AC-3 Category A Kilowatt Ratings for International Applications Standard power ratings of 3-phase motors 50/ 60 Hz in category AC-3 220 V 230 V kW 380 V 415 V kW 440/500 V 660/690 V kW Rated Operation al Current in AC-3 up to 400 V Auxiliary Contacts Type of Connection Catalog Number w Weight lb. (kg)

115/ 230/ 200/ 120 V 240 V 208 V HP HP HP

A Screw clamp v Slip-on 1 x 0.25 in. or 2 x 0.11 in. Solder pins for printed circuit board Screw clamp v Slip-on 1 x 0.25 in. or 2 x 0.11 in. Solder pins for printed circuit board Screw clamp v

N/O 1 1

N/C 1 LP2K0610 LP2K0601 LP2K06107 LP2K06017 LP2K06105 LP2K06015 LP2K0910 LP2K0901 LP2K09107 LP2K09017 LP2K09105 LP2K09015 LP2K1210 LP2K1201 LP2K12107 LP2K12017 LP2K12105 LP2K12015 1.05 (0.480) 1.05 (0.480) 1.00 (0.460) 1.00 (0.460) 1.14 (0.520) 1.14 (0.520) 1.05 (0.480) 1.05 (0.480) 1.00 (0.460) 1.00 (0.460) 1.14 (0.520) 1.14 (0.520) 1.05 (0.480) 1.05 (0.480) 1.00 (0.460) 1.00 (0.460) 1.14 (0.520) 1.14 (0.520)

0.5

1.5

1.5

1.5

2.2

1 1 1 1 1 1 1

1 1 1 1 1 1 1

0.5

1.5

2.2

0.5

1.5

7.5

10

12

5.5

4 (> 440) 5.5 (440)

12

Slip-on 1 x 0.25 in. or 2 x 0.11 in. Solder pins for printed circuit board

w v

Use voltage codes on page 49 Coil Selection to complete catalog number. Pre-wired power circuit connections are standard on screw clamp versions.

LP2K0610

LP2K06107

46 2001 Schneider Electric All Rights Reserved


04/01

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Selection of Reversing Contactors for Resistive Loads
Three- and Four-pole Reversing Contactors for AC Control Circuits The tables below show general purpose and sensitive-environment three- and four-pole reversing contactors for AC control circuits. The sensitive-environment contactors are recommended for use in areas sensitive to noise, high interference mains supplies, and so forth. The contactors incorporate an integrated mechanical interlock. Both types of contactors mount on 35 mm DIN rails or with 4 mm (# 6) screws. The wire termination screws are in the open, ready-to-tighten position. In addition, the sensitive-environment contactors include a coil with a built-in rectifier and suppressor. Customer wiring is required to connect coil terminations to the electrical interlock; see page 56 (top row, center drawing). For information on add-on auxiliary contact blocks and accessories, see page 50 to 53. General-purpose Contactors x
Non-inductive loads Category AC-1 Maximum current at 50 C (122 F) A Power Poles Type of Connection Auxiliary Contacts Catalog Number w N/O 3 Screw clamp v N/C N/O 1 1 1 1 N/C 1 1 1 1 LC2K0910 s LC2K0901 LC2K09004 LC2K09107 LC2K09017 LC2K090047 LC2K09105 LC2K09015 LC2K090045 LC2K09103 LC2K09013 LC2K090043 0.86 (0.390) 0.86 (0.390) 0.84 (0.380) 0.81 (0.370) 0.81 (0.370) 0.81 (0.370) 0.95 (0.430) 0.95 (0.430) 0.95 (0.430) 0.86 (0.390) 0.86 (0.390) 0.86 (0.390) Weight lb. (kg)

LC2K09004

3 4 3

Slip-on 1 x 0.25 in. or 2 x 0.11 in. 20 Solder pins for circuit board

3 4 3 3 4 3

Spring terminals

3 4

Sensitive-Environment Contactors
3 Screw clamp v 3 4 3 20 Slip-on 1 x 0.25 in. or 2 x 0.11 in. 3 4 3 Solder pins for circuit board 3 4 1 1 1 1 1 1 LC8K0910 f LC8K0901 f LC8K09004 LC8K09107 LC8K09017 LC8K090047 LC8K09105 LC8K09015 LC8K090045 1.05 (0.480) 1.05 (0.480) 1.03 (0.470) 1.01 (0.460) 1.01 (0.460) 1.01 (0.460) 1.14 (0.520) 1.14 (0.520) 1.14 (0.520)

LC8K09105

x For mains supplies with a high level of interference (voltage surge > 800 V), use a suppressor module LA4KE1FC (50 to 129 V) or LAFKE1UG (130 to 250 V), see page 52. w Use voltage codes on page 49 Coil Selection to complete catalog number. v Pre-wired power circuit connections are standard on screw clamp versions. s WARNING: This reversing contactor is pre-wired for reverse motor operation as standard.

47
04/01

2001 Schneider Electric All Rights Reserved

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Selection of Reversing Contactors for Resistive Loads
Three- and Four-pole Reversing Contactors for DC Control Circuits The table below shows general-purpose three- and four-pole reversing contactors for DC control circuits. The contactors incorporate an integrated mechanical interlock. The contactors mount on 35 mm DIN rails or with 4 mm (# 6) screws. The wire termination screws are in the open, ready-to-tighten position. Customer wiring is required to connect coil terminations to the electrical interlock; see page 56 (top row, center drawing). For information on add-on auxiliary contact blocks and accessories, see page 50 to 53.
Power Poles Type of Connection Auxiliary Contacts Catalog Number w N/O 3 Screw clamp v 3 4 3 20 Slip-on 1 x 0.25 in. or 2 x 0.11 in. 3 4 3 Solder pins for circuit board 3 4 N/C N/O 1 1 1 N/C 1 1 1 LP2K0910 s LP2K0901 s LP2K09004 LP2K09107 LP2K09017 LP2K090047 LP2K09105 LP2K09015 LP2K090045 1.05 (0.480) 1.05 (0.480) 1.05 (0.480) 1.01 (0.460) 1.01 (0.460) 1.01 (0.460) 1.14 (0.520) 1.14 (0.520) 1.14 (0.520) Weight lb. (kg)

Non-inductive loads Category AC-1 Maximum current at 50 C (122 F) A

LC2K09004

w Use voltage codes on page 49 Coil Selection to complete catalog number. v Pre-wired power circuit connections are standard on screw clamp versions. s WARNING: This reversing contactor is pre-wired for reverse motor operation as standard.

48 2001 Schneider Electric All Rights Reserved


04/01

K-line Mini-contactors, D-line Contactors, and Enclosed Starters


Coil Selection
NOTE: Voltage codes in bold face are typical control voltages.. Contactors LC1K, LC2K (0.8 to 1.15 Vc)
Volts AC 200/ 220/ 230/ 380/ 400/ 12 20 24 v 36 42 48 110 120 127 230 256 277 400 50/60 Hz 208 230 x 240 x 400 x 415 x Voltage J7 Z7 B7 C7 D7 E7 F7 G7 FC7 L7 M7 P7 U7 W7 UE7 Q7 V7 N7 Code Up to and including 240 V, coil with integral suppression device available: add 2 to the code required. Example: J72. v When connecting an electronic sensor or timer in series with the coil of the control relay, select a 20 V coil (AC control circuit voltage code Z7, DC control circuit voltage code ZD) so as to compensate for the incurred voltage drop. x 0.85 to 1.1 Vc. 440 R7 480 T7 500 S7 575 SC7 600 X7 660/ 690 x Y7

Contactors LC7K, LC8K (0.85 to 1.1 Vc)


Volts AC 50/60 Hz Voltage Code 24 B7 42 D7 48 E7 110 F7 120 G7 220 M7 230/ 240 U7

Contactors LP1K, LP2K (0.8 to 1.15 Vc)


Volts DC 12 20 24 q 36 48 60 72 100 110 125 155 174 200 Voltage Code JD ZD BD CD ED ND SD KD FD GD PD QD LD Coil with integral suppression device available: add 3 to the code required. Example: JD3. v When connecting an electronic sensor or timer in series with the coil of the control relay, select a 20 V coil (AC control circuit voltage code Z7, DC control circuit voltage code ZD) so as to compensate for the incurred voltage drop. 220 MD 230 MPD 240 MUD 250 UD

LC1D, LC2D AC/DC Supply (3 Pole)


AC Coils LC1D09 . . . D38
24 V 50/60 Hz B7 42 V D7 48 V E7 110 V F7 115 V FE7 120 V G7 127 V FC7 208 V LE7 220 V M7 230 V P7 240 V U7 277 V W7 380 V Q7 400 V V7 415 V N7 440 V R7 480 V T7 500 V 575 V SC7 600 V X7 660 V

LC1D12 & D25, 4 Pole


50/60 Hz 50 Hz 60 Hz a B7 B5 B6 D7 D5 E7 E5 E6 F7 F5 F6 FE7 FE5 G7 G6 G5 LE7 L6 M7 M5 M6 P7 P5 U7 U5 U6 W6 Q7 Q5 Q6 V7 V5 N7 N5 N6 a R7 R5 R6 T6 S5 SC7 S6 X6 Y5

N6 voltage code not availabel for LC1D25 4-pole contactor.

LC1D40 . . . D95, 3 or 4-Pole


50/60 Hz 50 Hz 60 Hz B7 B5 B6 D7 D5 E7 E5 E6 F7 F5 F6 FE7 FE5 G7 G6 G5 L6 M7 M5 P7 P5 U7 U5 U6 W6 Q7 Q5 V7 V5 N7 N5 R7 R5 R6 T6 S5 S6 X6 Y5

LC1D115 & D150 Coils with integral suppression device fitted as standard
50/60 Hz 50 Hz 60 Hz B7 B5 B6 D7 D5 E7 E5 E6 F7 F5 F6 FE7 FE5 G7 G6 FC7 FC5 LE7 L6 M7 M5 M6 P7 P5 U7 U5 U6 UE7 W6 Q7 Q5 Q6 V7 V5 N7 N5 R7 R5 R6 T7 T6 S7 S5

DC Coils LC1D09 . . .D38 Coils with integral suppression device fitted as standard
5V U 0.7 . . . 1.25 Uc 12 V JD 20 V 24 V BD 36 V CD 48 V ED 60 V ND 72 V SD 96 V 110 V FD 125 V GD 220 V MD 250 V UD 440 V RD

LC1D09 . . . D38 LOW CONSUMPTION Coils with integral suppression device fitted as standard
U 0.7 . . . 1.25 Uc AL JL ZL BL CD EL SL DL FL ML UL

LC1D40 . . . D95
U 0.85 . . . 1.1 Uc (standard) U 0.75 . . . 1.2 Uc (wide range) JD JW BD BW CD CW ED EW ND SD SW FD FW GD MD MW UD RD

LC1D115 & D150 Coils with integral suppression device fitted as standard
U 0.75 . . . 1.2 Uc BD ED ND SD FD GD MD UD RD

49
12/01 12/01

2001 Schneider Electric All Rights Reserved

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Selection of Auxiliary Contacts and Timers

XX

LC1/LC7/LP1K

LA1KNq q q

LA1KNq qM LC1/LC7/LP1K

LA1KNq q

LA1KT2q LC1/LC7/LP1K

LA1 KNq qP

50 2001 Schneider Electric All Rights Reserved


04/01

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Selection of Auxiliary Contacts and Timers
Instantaneous Auxiliary Contact Blocks for Type LCK and LPK Contactors Recommended for standard applications. Clip-on front mounting, 1 block per contactor
Auxiliary Contacts

Type of Connection

Type of Contactor

Catalog Number

Weight lb. (kg)

N/O 2 LC1, LC2 LC7, LC8 LP1, LP2 3- or 4-pole 1 4 3 2 1 2 LC1, LC2 LC7, LC8 LP1, LP2 3- or 4-pole 1 4 3 2 1 2 1 Spring Terminals LC1, LC2 LP1, LP2 3- or 4-pole 4 3 2 1

N/C 2 1 1 2 3 4 2 1 1 2 3 4 2 1 1 2 3 4 LA1KN20 LA1KN02 LA1KN11 LA1KN40 LA1KN31 LA1KN22 LA1KN13 LA1KN04 LA1KN207 LA1KN027 LA1KN117 LA1KN407 LA1KN317 LA1KN227 LA1KN137 LA1KN047 LA1KN203 LA1KN023 LA1KN113 LA1KN403 LA1KN313 LA1KN223 LA1KN133 LA1KN043 0.10 (0.045) 0.10 (0.045) 0.10 (0.045) 0.10 (0.045) 0.10 (0.045) 0.10 (0.045) 0.10 (0.045) 0.10 (0.045) 0.10 (0.045) 0.10 (0.045) 0.10 (0.045) 0.10 (0.045) 0.10 (0.045) 0.10 (0.045) 0.10 (0.045) 0.10 (0.045) 0.10 (0.045) 0.10 (0.045) 0.10 (0.045) 0.10 (0.045) 0.10 (0.045) 0.10 (0.045) 0.10 (0.045) 0.10 (0.045)

Screw Clamp

Slip-on 1 x 0.25 in. or 2 x 0.11 in.

With terminal referencing conforming to standard EN 50012. Clip-on front mounting, 1 block per contactor
LC1, LC2 LC7, LC8 LP1, LP2 3-pole + N/O 1 3 2 1 LC1, LC2 LC7, LC8 LP1, LP2 4-pole 1 2 2 1 1 2 3 1 2 LA1KN02M LA1KN11M LA1KN31M LA1KN22M LA1KN13M LA1KN11P LA1KN22P 0.10 (0.045) 0.10 (0.045) 0.10 (0.045) 0.10 (0.045) 0.10 (0.045) 0.10 (0.045) 0.10 (0.045)

Screw clamp with terminal referencing conforming to standard EN 50012

Electronic Time-Delay Auxiliary Contact Blocks for Type LCK and LPK Contactors
Relay output, with common point changeover contact, AC or DC 240 Vac, 2 A maximum. Control voltage: 0.85 to 1.1 Vc. Maximum switching capacity: 250 VA or 150 W. Operating temperature: -10 to + 60 C (14 to 140 F). Reset time: 1.5 s during the time delay period, 0.5 s after the time delay period.

Clip-on front mounting, 1 block per contactor


Auxiliary Contacts Voltage Type Timing Range s SPDT On-delay On-delay 1 to 30 1 to 30 1 1 LA2KT2E LA2KT2U 0.09 (0.040) 0.09 (0.040) Catalog Number Weight lb. (kg)

V AC or DC 24 to 48 AC 110 to 240

51
04/01

2001 Schneider Electric All Rights Reserved

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Selection of Accessories
Coil Suppressor Modules With an LED Indicator for Type LCK and LPK Contactors
Mounting and connection Type For voltages:
AC and DC 12 to 24 V AC and DC 32 to 48 V AC and DC 50 to 129 V AC and DC 201 to 250 V Diode + Zener diode x DC 12 to 24 V DC 32 to 48 V AC 220 to 250 V

Sold in lots of Catalog Number


5 5 5 5 5 5 5 LA4KE1B LA4KE1E LA4KE1FC LA4KE1UG LA4KC1B LA4KC1E LA4KA1U

Weight lb. (kg)


0.02 (0.010) 0.02 (0.010) 0.02 (0.010) 0.02 (0.010) 0.02 (0.010) 0.02 (0.010) 0.02 (0.010)

Varistor s Clip-on mounting on the front of LC1 and LP1 contactors. No tools required.

LA4K
s x v

RC v

Protection by limitation of the transient voltage up to 2 Vc maximum. Maximum reduction of transient voltage peaks. Slight time delay on drop-out (1.1 to 1.5 times the normal time). No overvoltage or oscillation frequency. Polarized component. Slight time delay on drop-out (1.1 to 1.5 times the normal time). Protection by limitation of the transient voltage up to 3 Vc maximum and limitation of the oscillation frequency. Slight time delay on drop-out (1.2 to 2 times the normal time).

Mounting and Marking Accessories


Description
Mounting plates s For mounting on 2 rails Marker holder Clip-on

Application
For mounting on 1 rail Clip-on 110/120 mm mounting centers Onto front of contactor Strips of 10 identical numbers 0 to 9 Strips of 10 identical capital letters A to Z

Sold in lots of Unit Catalog Number Weight lb. (kg)


1 10 100 25 25 10 10 LA9D973 DX1AP25 LA9D90 AB1R v AB1G v AM1DP200 AM1ED200 0.05 (0.025) 0.14 (0.065) 0.002 (0.001) 0.004 (0.002) 0.004 (0.002) 2.88 (1.310) 1.44 (0.650)

Clip-in markers

4 maximum per contactor

35mm " DIN rail (7.5mm deep x 2m long) 35mm " DIN rail (15mm deep x 2m long) s v

Order 1 mounting plate for a contactor and 2 mounting plates for a reversing contactor. Complete the catalog number by replacing the with the required character.

DX1AP25

Cabling Accessories
Description
Paralleling links Set of 6 power connections Set of 4 power connections

Application
For 2-poles For 4-poles For 3-pole reversing contactors for motor control For 4-pole changeover contactor pairs With screw clamp terminals With screw clamp terminals For contactors with screw clamp terminals For contactors with screw clamp terminals

Sold in lots of
4 2 100 100

Unit Catalog Number


LA9E01 LA9E02 LA9K0969 LA9K0970

Weight kg (lb.)
0.02 (0.010) 0.03 (0.015) 0.02 (0.010) 0.02 (0.010)

LA9E01

52 2001 Schneider Electric All Rights Reserved


04/01

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Dimensions and Mounting of Type LCK and LPK Contactors

XXX
Contactors LC1K, LC7K, LP1K On panel On mounting rail AM1DP200 or AM1DE200 1.4 in. (35 mm) DIN rail

LA1 K

0.16 (#6) screws 4mm 2.28 58

2.28 58

1.97 50

2.24 57

1.78 45

1.22 31

2.24 57

1.38 35 1.78 45

On one asymmetrical rail DZ5MB with clip-on mounting plate LA9D973 DX1AP25

0.20 5

DZ5 ME5

1.97 50

4.72 120

2.24 57

0.83 21

1.38 35 1.78 45

0.20 5

On printed circuit board

2.24 57
A1

1.06 27

1.78 45

0.34 8.65

== =

2.28 58

10x 0.05 1.3

1.78 45

Electronic time-delay auxiliary contact blocks LA2KT On contactor

1.97 50 2.09 53

A2

LA2 KT

1.34 34

1.50 38

1.06 27

1.34 34

2.24 57

Suppressor modules LA4K On contactor

0.87 22

0.99 25

0.24 6

2.26 58

2.28 58

0.87 22

2.24 57

Dimensions Inches mm

4.33 110

53
04/01

2001 Schneider Electric All Rights Reserved

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Dimensions and Mounting of Type LCK and LPK Reversing Contactors

Reversing contactors LC2K, LC8K, LP2K On panel

On mounting rail AM1DP200 or AM1DE200 1.4 (35 mm) DIN rail

LA1K

2.28 58

1.97 50

2.24 57 1.22 31 2.24 57 = 3.15 80 3.54 90 = =

2.28 58

0.16 (#6) screws 4 mm

3.54 90

On one asymmetrical rail DZ5MB with 2 clip-on mounting plates LA9D973 or on 2 mounting plates DX1AP25. 2 x LA9D973 2 x DX1AP25

0.20 5

1.78 45 DZ5 ME5

1.97 50

2.24 57

0.83 21

0.20

3.54 90
On printed circuit board for reversing contactors or 2 contactors mounted side by side
2.24 57 1.06 27 3.54 90

0.34 8.65

== =

= ==

0.34 8.65

A1

A1 A2

2.28 58

A2

20x1.3 0.05

1.78 45

1.78 45

Electronic time delay auxiliary contact blocks LA2KT On reversing contactors

1.97 50 2.09 53

1.38 35

LA2 KT

1.34 34

1.50 38

1.06 27

1.34 34

2.24 57

Suppressor modules LA4K On reversing contactors

0.99 25

0.87 22

0.24 6

2.28 58

2.28 58

4.72 120

0.87 22

2.24 57

Dimensions inches mm

54 2001 Schneider Electric All Rights Reserved


04/01

4.33 110

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Schematics
Type LCK and LPK Contactors and Accessories
3-pole contactors LC1K, LC7K, LP1K 3-pole + N/O 3-pole + N/C Integrated-coil suppression device LC7K

3/L2

1/L1

5/L3

13/NO

3/L2

1/L1

5/L3

A2

14

A2

A1

T1/2

T2/4

T3/6

T1/2

T2/4

T3/6

22

21/NC

A1

4-pole contactors LC1K, LC7K, LP1K 4-pole 2-pole N/O + 2-pole N/C

Integrated-coil suppression device LC7K

3/L2

1/L1

5/L3

7/L4

R1

R3

A1

A2

T1/2

T2/4

T3/6

T4/8

A2

A1

R2

R4

Instantaneous auxiliary contacts LA1K For contactors LCK and LPK 2 N/O LA1KN20 LA1KN207 2 N/C LA1KN02 LA1KN027 1 N/O + 1 N/C LA1KN11 LA1KN117

53/NO

53/NO

63/NO

51/NC

61/NC

54

64

52

4 N/O LA1KN40 LA1KN407

3 N/O + 1 N/C LA1KN31 LA1KN317

62

2 N/O + 2 N/C LA1KN22 LA1KN227

54

62

61/NC

1 N/O + 3 N/C LA1KN13 LA1KN137

A2

A1

A2

A1

4 N/C LA1KN04 LA1KN047

53/NO

63/NO

73/NO

83/NO

51/NC

61/NC

71/NC 72 42 41/NC

53/NO

61/NC

71/NC

53/NO

73/NO

83/NO

61/NC

53/NO

83/NO

61/NC

71/NC

81/NC

52

62

54

62

72

54

62

74

84

54

62

72

54

64

74

Terminal referencing conforming to standard EN 50012 For 3-pole contactors 2 N/C LA1KN02M 1 N/O + 1 N/C LA1KN11M 3 N/O + 1 N/C LA1KN31M 2 N/O + 2 N/C LA1KN22M 1 N/O + 3 N/C LA1KN13M

21/NC

31/NC

84

84

43/NO

53/NO

82

33/NO

21/NC

33/NO

43/NO

22

32

53/NO

21/NC

22

32

44

54

22

32

22

34

22

34

44

For 4-pole contactors 1 N/O + 1 N/C LA1KN11P 2 N/O + 2 N/C LA1KN22P

13/NO

21/NC

13/NO

14

22

14

22

32

Electronic time delay auxiliary contact blocks LA2KT For contactors LCK and LPK 1 C/O

Suppressor modules LA4KC

44

43/NO

21/NC

31/NC

54

LA4KE

A1

16

A2

15

18

DC

AC/ DC

54

53/NO

21/NC

31/NC

21/NC

31/NC

82

81/NC

55
04/01

2001 Schneider Electric All Rights Reserved

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Schematics
Type LCK and LPK Reversing Contactors and Accessories
3-pole reversing contactors LC2K, LC8K, LP2K With screw clamp terminals 3 P + N/O Dashed lines indicate suggested customer wiring to electrically interlock coils 3 P + N/C Integrated-coil suppression device LC8K

3/L2

5/L3

3/L2

1/L1

13/NO

1/L1

5/L3

13/NO

3/L2

5/L3

3/L2

1/L1

21/NC

1/L1

5/L3

A1

A1

A1

21/NC

A1

T3/6

T1/2

T2/4

T1/2

T2/4

T3/6

A2

T3/6

T1/2

T2/4

T1/2

With Slip-on connectors or solder pins (printed circuit board) 3 P+ N/O


3/L2 5/L3 3/L2 1/L1 1/L1 5/L3 13/NO 13/NO

With Slip-on connectors or solder pins (printed circuit board) 3 P + N/C


3/L2 5/L3 3/L2 1/L1 21/NC 1/L1 5/L3 21/NC

A1

T2/4

T3/6

A1

A1

A2

A2

A2

14

14

T3/6

T1/2

T2/4

T1/2

T3/6

T1/2

T2/4

T1/2

4-pole reversing contactors LC2K, LC8K, LP2K With screw clamp terminals 4P
1N 1/L1 1/L2 1/L3 2/L1 2/L2 2/L3 2N

T2/4

T3/6

T2/4

T3/6

A2

22

22

A1

A2

22

22

Integrated-coil suppression device LC8K With Slip-on connectors or solder pins (printed circuit board) 4P

A1

A2

A1

A1

A2

A2

A2

A1

L1

L2

L3

Instantaneous auxiliary contact blocks LA1K For contactors LCK and LP2K 2 N/O LA1KN20 LA1KN207 2 N/C LA1KN02 LA1KN027 1 N/O + 1 N/C LA1KN11 LA1KN117 Terminal referencing conforming to standard EN 50012 1 N/O + 1 N/C LA1KN11P

53/NO

63/NO

51/NC

61/NC

53/NO

13/NO

61/NC

52

54

64

62

62

14

54

For contactors LCK, LP2K 4 N/O LA1KN40 LA1KN407 3 N/O + 1 N/C LA1KN31 LA1KN317 2 N/O + 2 N/C LA1KN22 LA1KN227 1 N/O + 3 N/C LA1KN13 LA1KN137 4 N/C LA1KN04 LA1KN047

53/NO

73/NO

83/NO

61/NC

53/NO

61/NC

22

21/NC

71/NC

53/NO

83/NO

81/NC

51/NC

61/NC

71/NC 72

A2 53/NO 63/NO 73/NO 83/NO 61/NC 62 54 74 84 71/NC 54 62 72 82 52 62 54 62 72 54 64 74


For auxiliary contacts with terminal referencing conforming to standard EN 50012 see page 51. Electronic time delay contact blocks LA2KT For contactors LCK and LPK 1 C/O Suppressor modules LA4KC LA4KE

A1 82 81/NC

A1

16

A2

15

18

84

84

DC

+
56

AC/ DC

2001 Schneider Electric All Rights Reserved

A2

A2

A2

14

14

A1

04/01

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Characteristics of Type LRK Overload Relays

Environment
Conforming to standards Meets the essential requirements of the LV & EMC directives IEC 60947, NF C 63-650, VDE 0660, BS 4941, UL 508, CSA 22.2 No. 14

Product certifications

E164353 NKCR Conforming to IEC 60068 (DIN 50016) Conforming to VDE 0106 Storage TC (Fungus-proof, tropicalization protection) Protection against direct finger contact -40 to +70 C (-40 to +158 F) -20 to +55 C (-4 to +131 F) without derating -30 to +60 C (-22 to +140 F) with derating s 2000 m (6562 ft.) Horizontal axis

LR43364 3211 03

Protective treatment Degree of protection Ambient air temperature around the device Maximum operating altitude

For normal operation (IEC 60947) Operating limit Without derating Vertical axis

90
Operating positions

90
Without derating Flame resistance Shock resistance, hot state (1/2 sine wave, 11 ms) Vibration resistance, hot state 5 to 300 Hz Safe separation of circuits Cabling Solid or stranded cable Screw clamp terminals Solid cable Stranded cable without cable end Stranded cable with cable end Tightening torque Mounting Phillips no. 2 or 3/16 slotted head Conforming to UL 94 Conforming to NF F 16-101 and 16-102 Conforming to IEC 60068, N/C contact Conforming to IEC 60068, N/O contact Conforming to IEC 60068, N/C contact Conforming to IEC 60068, N/O contact Conforming to VDE 0106 and IEC 60536

90

90

With derating s Self-extinguishing material V1 Conforming to requirement 2 10 gn 10 gn 2 gn 2 gn SELV, up to 400 V v Minimum AWG mm2 mm2 mm2 1 x 18 1 x 1.5 1 x 0.75 1 x 0.34 Maximum 2 x 14 or 1 x 12 2x4 2x4 1 x 1.5 + 1 x 2.5 Maximum to IEC 60947 1 x 4 + 1 x 2.5 2 x 2.5 1 x 1.5 + 1 x 2.5

0.8 N.m (7 lb.-in.)

Directly under the contactor or reversing contactor Made automatically when mounted under the contactor, as follows: - contactor terminal A2 connected to overload relay terminal 96 on all products, - contactor terminal 14 connected to overload relay terminal 95 on products with 3 P + N/O When using 3 P + N/C, or 4 P contactors, or the N/O auxiliary contact marked 13-14, at a voltage other than the coil voltage, break off the link marked 14. (See page 60 for additional information.)

Connections

s Please consult your Local Field Sales Office. v Safe extra low voltage.

Auxiliary Contact Characteristics


Number of contacts Conventional thermal current Short-circuit protection Conforming to IEC 60947, VDE 0660. gl fuse or supplementary protector GB2CB AC A A V VA DC Maximum operational voltage AC, category AC-15 DC, category DC-13 V W V V 1 N/C + 1 N/O 6 6 max. 24 100 24 100 690 250 48 200 48 100 110 400 110 50 220/ 230 600 220 45 400 600 250 35 415/ 440 600 600/ 690 600

Maximum power of the controlled contactor coils (sealed) (Occasional operating cycles of contact 95-96)

57
04/01

2001 Schneider Electric All Rights Reserved

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Characteristics of Type LRK Overload Relays
Electrical Characteristics of the Power Circuit
Rated operational voltage (Ve) Up to Conforming to BS 4941 Rated insulation voltage (Vi) Conforming to IEC 60947 Conforming to VDE 0110 group C Conforming to UL 508, CSA 22.2 No. 14 Rated impulse withstand voltage (Vimp) V V V V V kV 690 690 690 750 600 6

Frequency limits of the operational current Power dissipated per pole Short-circuit protection and coordination By circuit breaker By fuses

Hz W

Up to 400

2 Select in accordance with NEC and local codes Maximum 400% of motor FLA

Operating Characteristics
Sensitivity to phase failure Reset Signalling Reset-Stop function Conforming to IEC 60947 Manual or automatic Yes Selected by means of a lockable and sealable switch on the front of the relay

On front of relay

Trip indicator Pressing the Reset-Stop button: Actuates the N/C contact Has no effect on the N/O contact Pressing the Test button enables: Checking of the control circuit wiring Simulation of overload tripping (actuation of both N/C and N/O contacts, and of the trip indicator)

Test function

By pushbutton

Tripping curves Average operating time related to multiples of the current setting Class 10 A Time
2h 1h 20 min 1h 40 min 20 min 10 min 6 min 4 min 2 min 1 min 40 s 20 s 10 s 6s 4s 2s 1s 1 1.2 1.5 2 3 4 5 6 8 10 15

Class 10 A

Time
2h 1h 20 min 1h 40 min 20 min 10 min 6 min 4 min 2 min 1 min 40 s 20 s 10 s 6s 4s 2s 1s

Class 10 A

1 2
1 1.2 1.5 2 3 4 5 6 8 10 15

x setting current (Ir) Balanced 3-phase operation, from cold state.

x setting current (Ir) Balanced operation with 2-phases only, from cold state. 1 = Setting: at lower end of scale. 2 = Setting: at upper end of scale.

58 2001 Schneider Electric All Rights Reserved


04/01

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Selection of Type LRK Overload Relays
These overload relays are designed for the protection of motors. They are ambient-compensated and phase-failure sensitive. They may be reset either manually or automatically. For direct mounting, the relays are placed under the contactors with screw clamp terminals only (pre-wired terminals; see page 60). For separate mounting, use terminal block LA7K0064 (see below). The front face of the overload relay provides: Selection of reset mode: Manual (marked H) or Automatic (marked A). A red pushbutton for the Trip Test function. A blue pushbutton for Stop and manual reset. A yellow trip flag to indicate that the overload relay tripped. Three-pole Relays with Screw Clamp Terminals
Short-circuit protection for North American applications Relay Setting Range A
0.11 to 0.16 By circuit breaker By fuses Select in accordance with NEC and local codes Maximum 400% of motor FLA

European type fuses Maximum rating Type aM A


0.25 0.25 0.5 1 1 2 2 4 4 6 8 10 16 20

Catalog Number BS88 A


6 6 10 16 16 20 20 25 32 LR2K0301 LR2K0302 LR2K0303 LR2K0304 LR2K0305 LR2K0306 LR2K0307 LR2K0308 LR2K0310 LR2K0312 LR2K0314 LR2K0316 LR2K0321 x LR2K0322 x

Weight lb. (kg)

gl A
0.5 0.5 1 1.6 2 4 6 8 10 16 20 25 32 40

Class 10 A (the standard specifies a tripping time of between 2 and 10 seconds at 7.2 In) 0.32 (0.145) 0.32 (0.145) 0.32 (0.145) 0.32 (0.145) 0.32 (0.145) 0.32 (0.145) 0.32 (0.145) 0.32 (0.145) 0.32 (0.145) 0.32 (0.145) 0.32 (0.145) 0.32 (0.145) 0.32 (0.145) 0.32 (0.145)

LR2K0301

0.16 to 0.23 0.23 to 0.36 0.36 to 0.54 0.54 to 0.8 0.8 to 1.2 1.2 to 1.8 1.8 to 2.6 2.6 to 3.7 3.7 to 5.5 5.5 to 8 8 to 11.5 10 to 14 12 to 16 x

Not UL Listed or CSA Certified.

Overload Relays without Single-phase Sensitivity x


Class 10 A: To order, replace the prefix LR2 by LR7 in the catalog numbers selected from above (only applicable to overload relays LR2K0305 to LR2K0322). Example: LR7K0308. x Not UL Listed or CSA Certified.

Accessory
Description
Terminal block for separate clip-on mounting of the overload relay on 35 mm " DIN rail

Type of Connection
Screw clamp

Catalog Number
LA7K0064

Weight lb. (kg)


0.22 (0.100)

LA7K0064

59
04/01

2001 Schneider Electric All Rights Reserved

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Dimensions, Mounting, and Schematics for Type LRK Overload Relays

Protection components
LR2K Direct mounting beneath the contactor Separate mounting with terminal block LA7K0064 on 1.4 in. (35 mm) DIN rail (AM1DP200 or AM1DE200)

1.97 50

0.16 4mm (#6) screws

4.57 116

3.15 80

1.50 38

0.31 8

1.38 35

2.95 75 c

2.28 58

1.77 45
AM1DP200 DE200 c 3.09 in. / 78.5mm 3.38 in. / 86mm

2.56 65

1.77 45

LR2K

LR2K + LCK Built-in wiring schematic

A H 1 3 5

A1

13

KM1 14

13

95

97

95 Internal Links 96

14

A2

96

98

O 96 KM1 97 2 4 95 6 98 96 A1 A2

Reset/stop

LR2K Overload Relays feature built-in wiring to save time and materials when all five links of the overload relay are connected to a K-line contactor with an integrated N/O (normally-open) auxiliary contact. Terminal 96 of the N/C (normally-closed) overload relay contact (95-96) will be internally linked in series with terminal A2 of the contactor operating coil. Terminal 95 of the N/C overload relay contact (95-96) will be internally linked in series with terminal 14 of N/O coil holding contact (13-14) of the contactor. These internal links help to eliminate additional wiring when using a conventional 3-wire control circuit similar to the diagram shown.
L1 Stop Start 95 96 A2 A1 L2

13

14

Internal Links

If integrated wiring between contactor and overload relay is not desired, break off the two links on the overload relay as indicated.

60 2001 Schneider Electric All Rights Reserved


04/01

95

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Characteristics of Type LPK Low-consumption Contactors

Environment
Conforming to IEC 60947 Rated insulation voltage (Vi) Conforming to VDE 0110 gr C Conforming to BS 5424, NF C 20-040 Conforming to CSA 22.2 No. 14, UL 508 Rated impulse withstand voltage (Vimp) Conforming to standards Meets the essential requirements of the LV & EMC directives LPK06, LPK09, LPK12 Conforming to IEC 60068 (DIN 50016) Conforming to VDE 0106 Storage Operation Without derating Vertical axis V V V V kV 690 750 690 600 8 IEC 60947, NF C 63-110, VDE 0660, BS 5424, UL 508, CSA 22.2 No. 14 E164862 NLDX
(screw clamp)

Approvals

LR43364 3211 04

E164862 NLDX2 (Slip-on & solder pin)

Protective treatment Degree of protection Ambient air temperature around the device Maximum operating altitude

TC (Fungus-proof, Tropicalization protection) Protection against direct finger contact - 50 to + 80 C (-58 to +176F) - 25 to + 50C (-13 to +122F) 2000 m (6562 ft) Horizontal axis

90

Operating positions

90
Without derating Flame resistance Shock resistance (1/2 sine wave, 11 ms) Vibration resistance 5 to 300 Hz Safe separation of circuits Cabling

18 0

Conforming to UL 94 Conforming to NF F 16-101 and 16-102 Contactor open Contactor closed Contactor open Contactor closed Conforming to VDE 0106 and IEC 60536

Solid or stranded cable Screw clamp terminals Solid cable Stranded cable without cable end Stranded cable with cable end Slip-on connectors Solder pins for printed circuit board Tightening torque Terminal referencing v Safe extra low voltage. Clip With locating device between power and control circuits Phillips no. 2 or 3/16" slotted head screwdriver Conforming to standards EN 50005 and EN 50012

04/01

2001 Schneider Electric All Rights Reserved

90
Without derating 10 g 15 g 2g 4g SELV, up to 400 V v Min
AWG

Derate current carrying capability by 15% when not mounted vertically

90

Self-extinguishing materials V1 Conforming to requirement 2

Max 2 x 14 or 1 x 12 2x4 2x4 1 x 1.5 + 1 x 2.5

Max to IEC 60947 1 x 4 + 1 x 2.5 2 x 2.5 1 x 1.5 + 1 x 2.5

1 x 18 1 x 1.5 1 x 0.75 1 x 0.34

mm2 mm2 mm2

2 x 2.8mm or 1 x 6.35mm (2 x 0.110 in. or 1 x 0.250 in.) 4 mm x 35 microns 0.8 to 1.3 Nm (7 to 11.5 lb.-in) Up to 3 contacts

61

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Characteristics of Type LPK Low-consumption Contactors
Pole Characteristics
Conventional rated thermal current (Ith) Rated operational frequency Frequency limits of the operational current Rated operational voltage (Ve) I rms conforming to NF C 63-110 and IEC 60947 LPK06, LPK09 LPK12 Conforming to NF C 63-110 and IEC 60947 LPK06, LPK09 LPK12 I rms V A For ambient temperature 50 C (122F) A Hz Hz V A 110 144 220/ 230 110 1s A 90 115 380/ 400 110 5s 85 105 415 110 10 s 80 100 440 110 120 30 s 60 75 500 80 80 1 min 45 55 660/ 690 70 70 3 min 40 50 15 min 20 25 20 50/60 Up to 400 690

Rated making capacity

Rated breaking capacity

Permissible short time rating

Open mounted, for a time t from cold state ( 50 C [122 F]) LPK06, LPK09 LPK12 By circuit breaker By fuses At Ith and 50 Hz Maximum rated operational current for a temperature 50 C (122 F) Rated operational current limits in relation to on-load factor and operating frequency m A

Short-circuit protection Average impedance per pole

Select in accordance with NEC and local codes Max 400% of motor FLA 3 20 On-load factor A 300 op. cycles/hour 120 op. cycles/hour 30 op. cycles/hour 90% 13 15 19 60% 15 18 20 30% 18 19 20

Utilization in category AC-1 resistive circuits, heating, lighting (Ve 440 V)

Increase in operational current by paralleling poles

Apply the following coefficients to the current values given above. These take into account the often unbalanced current distribution between poles 2 poles in parallel: K = 1.60 3 poles in parallel: K = 2.25 4 poles in parallel: K = 2.80

Operational power according to the voltage LPK06 Utilization in category AC-3 Squirrel cage motors LPK09 LPK12

Voltage V 50 or 60Hz Motor ratings Motor ratings Motor ratings kW kW kW

115 1-ph 0.37 0.55

220 1-ph 0.75 1.1

220/ 240 3-ph 1.5 2.2 3 600 100% 220/ 208 3-ph 1.5 2 3

380/ 415 3-ph 2.2 4 5.5

440/ 480 3-ph 3 4 5.5 4 (480) 900 75%

500/ 600 3-ph 3 4 4

660/ 690 3-ph 3 4 4 1200 50%

Percent utilization of operational power in relation to the maximum operating rate Operational power according to the voltage LCK06, LPK06 LCK09, LPK09 LCK12, LPK12 LCK16, LPK16 Voltage 50 or 60Hz Motor ratings Motor ratings Motor ratings V

Op. cycles/h Puissance 115 1-ph HP HP HP 0.5 0.5 1 220 1-ph 1 1.5 2

220/ 240 3-ph 3 3 3

460/ 480 3-ph 3 5 7.5

575/ 600 3-ph 3 5 10

Utilization in category AC-3 Squirrel cage motors

Not for North American Applications. Not UL Listed or CSA Certified.

62 2001 Schneider Electric All Rights Reserved


04/01

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Characteristics of Type LPK Low-consumption Contactors
Control Circuit Characteristics
Type Rated control circuit voltage (Vc) Control voltage limits ( 50 C [122 F]) single-voltage coil Average consumption at 20 C (68 F) and at Vc Heat dissipation Between coil energization and: - opening of the N/C contacts - closing of the N/O contacts Between coil de-energization and: - opening of the N/O contacts - closing of the N/C contacts For operation For drop-out Inrush Sealed W W W ms ms ms ms ms In operating cycles per hour Wide range DC coil V LP4 DC 12 to 72 0.7 to 1.30 Vc 0.10 Vc 1.8 1.8 1.8 25 to 35 30 to 40 10 to 20 15 to 25 2 3600 30 5 LP5

Operating time at 20 C (68 F) and at Vc

Maximum immunity to micro breaks Maximum operating rate Mechanical durability at Vc In millions of operating cycles

63
04/01

2001 Schneider Electric All Rights Reserved

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Characteristics of Type LPK Low-consumption Contactors
Auxiliary Contact Characteristics of Contactors and Instantaneous Contact Blocks
Number of contacts Rated operational voltage (Ve) On LP4, LP5K On LA1K Up to Conforming to BS 5424 Rated insulation voltage (Vi) Conforming to IEC 60947 Conforming to VDE 0110 group C Conforming to CSA 22.2 No. 14, UL 508 Conventional rated thermal current (lth) For ambient temperature 50 C (122 F) Frequency of operational current Minimum switching capacity Short-circuit protection Rated making capacity V min (DIN 19 240) I min Conforming to IEC 60947 and VDE 0660, gl fuse Conforming to IEC 60947 I rms 1s Overload current Permissible for 500 ms 100 ms Insulation resistance Non-overlap distance Operational power of contacts conforming to IEC 60947 V V V V V A Hz V mA A A A A A M Linked contacts conforming to INRS and BIA specs. mm 1 2 max. 690 690 690 750 600 10 Up to 400 17 (reliability <10-8 at 24V) 5 10 110 80 90 110 > 10 0.5

AC supply, category AC-15 Electrical durability (valid up to 3600 operating cycles per hour) on an inductive load such as the coil of an electromagnet: making current (power factor 0.7) = 10 times the breaking current (power factor 0.4).
V 24 48 17 7 48 96 34 14 110/ 127 240 86 36 220/ 230 440 158 66 380/ 400 800 288 120 400 880 317 132 600/ 690 1200 500 200

DC supply, category DC-13 Electrical durability (valid up to 1200 operating cycles per hour) on an inductive load such as the coil of an electromagnet, without economy resistor, the time constant increasing with the load.
V W W W W 24 120 55 15 720 48 80 38 11 600 110 60 30 9 400 220 52 28 8 300 440 51 26 7 230 600 50 25 6 200

1 million operating cycles 3 million operating cycles 10 million operating cycles Occasional making capacity

VA VA VA VA

1000 2050 5000 10000 14000 13000 9000

Power in broken VA
16 000 10 000 8000 6000 5000 4000 3000 2000 1000 800 600 500 400 300 200 100 80 60 40 24 48 110 120 220 380 500 440 690 V

Power in broken W

Time constant in ms

1000 700 500

1 Breaking limit of contacts valid for


maximum of 50 operating cycles at 10 s intervals (breaking current = making current x power factor 0.7).

3
300 200 100 80 60 50 40 30 20

2 Electrical durability of contacts for:


- 1 million operating cycles (2a) - 3 million operating cycles (2b) -10 million operating cycles (2c).
4

250 200 140

2a 2b

3 Breaking limit of contacts valid for


maximum of 20 operating cycles at 10 s intervals with current passing for 0.5 s per operating cycle.

2a

100

2b

2c
2c
50 20 12 24 48 110 220 440 600 V 10 8 6

4 Thermal limit.

64 2001 Schneider Electric All Rights Reserved


04/01

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Selection of Low-consumption Contactors for Motor Control
The table below shows three-pole contactors with low-consumption coils for DC control circuits. They are compatible with programmable controller outputs, and incorporate an LED indicator. For wide-range coils (0.7 to 1.3 Vc), a suppressor is fitted as standard (consumption is 1.8 W). The contactors mount on 35 mm DIN rails or with 4 mm (# 6) screws. The wire termination screws are in the open, ready-to-tighten position. For information on add-on auxiliary contact blocks and accessories, see page 69. Three-pole Contactors with Low-consumption Coils for DC Control Circuits
Horsepower Ratings for North American Applications Maximum Horsepower Rating Category AC-3, 50/60 Hz 1-Phase 115/ 120 V HP 230/ 240 V HP 3-Phase 200/ 208 V HP 220/ 240 V HP 460/ 480 V HP 575/ 600 V HP Max. Inductive Current A Kilowatt Ratings for International Applications Standard power ratings of 3-phase motors, 50/60 Hz in category AC-3 220 V 230 V kW 380 V 415 V kW 440/500 V 660/690 V kW Rated Operational Current, up to 440 V A Screw clamp Slip-on 1 x 0.25 in., or 2 x 0.11 in. 0.5 1 1.5 1.5 3 3 6 1.5 2.2 3 6 Solder pins for printed circuit board Spring terminals Screw clamp Slip-on 1 x 0.25 in., or 2 x 0.11 in. 0.5 1.5 2 3 5 5 9 2.2 4 4 9 Solder pins for printed circuit board Spring terminals Screw clamp Slip-on 1 x 0.25 in., or 2 x 0.11 in. 12 Solder pins for printed circuit board Spring terminals x w Standard control circuit voltages (variable delivery times, please consult your Local Square D Field Sales Office). Use voltage codes on page 49 Coil Selection to complete catalog number. Auxiliary Contacts Type of Connection Catalog Number xw N/O 1 1 1 1 1 1 1 1 1 1 1 1 N/C 1 1 1 1 1 1 1 1 1 1 1 1 LP4K0610 LP4K0601 LP4K06107 LP4K06017 LP4K06105 LP4K06015 LP4K06103 LP4K06013 LP4K0910 LP4K0901 LP4K09107 LP4K09017 LP4K09105 LP4K09015 LP4K09103 LP4K09013 LP4K1210 LP4K1201 LP4K12107 LP4K12017 LP4K12105 LP4K12015 LP4K12103 LP4K12013 0.52 (0.235) 0.52 (0.235) 0.52 (0.235) 0.52 (0.235) 0.265 (0.58) 0.58 (0.265) 0.52 (0.235) 0.52 (0.235) 0.52 (0.235) 0.52 (0.235) 0.52 (0.235) 0.52 (0.235) 0.58 (0.265) 0.58 (0.265) 0.52 (0.235) 0.52 (0.235) 0.52 (0.235) 0.52 (0.235) 0.52 (0.235) 0.52 (0.235) 0.58 (0.265) 0.58 (0.265) 0.52 (0.235) 0.52 (0.235) Weight lb. (kg)

7.5

10

12

5.5

4 (> 440) 5.5 (440)

Coil Selection
Volts DC Code 12 JW3 24 BW3 48 EW3 72 SW3

LP4K06105

65
04/01

2001 Schneider Electric All Rights Reserved

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Selection of Low-consumption Reversing Contactors for Motor Control
The table below shows three-pole reversing contactors with low-consumption coils for DC control circuits. They are compatible with programmable controller outputs, and incorporate an LED indicator and mechanical interlock. For wide-range coils (0.7 to 1.3 Vc), a suppressor is fitted as standard (consumption is 1.8 W). The contactors mount on 35 mm DIN rails or with 4 mm (# 6) screws. The wire termination screws are in the open, ready-to-tighten position. Customer wiring is required to connect coil terminations to the electrical interlock; see page 72 for more information. For information on add-on auxiliary contact blocks and accessories, see page 69. Three-pole Reversing Contactors with Low-consumption Coils for DC Control Circuits
Horsepower Ratings for North American Applications Maximum Horsepower Rating Category AC-3, 50/60 Hz 1-Phase 115/ 120 V HP 230/ 240 V HP 3-Phase 200/ 208 V HP 220/ 240 V HP 460/ 480 V HP 575/ 600 V HP Max. Inductive Current A Kilowatt Ratings for International Applications Standard power ratings of 3-phase motors, 50/60 Hz in category AC-3 220 V 230 V kW 380 V 415 V kW 440/500 V 660/690 V kW Rated Operational Current, up to 440 V A Screw clamp v Slip-on 1 x 0.25 in., or 2 x 0.11 in. 0.5 1 1.5 1.5 3 3 6 1.5 2.2 3 6 Solder pins for printed circuit board Spring terminals Screw clamp v Slip-on 1 x 0.25 in., or 2 x 0.11 in. 0.5 1.5 2 3 5 5 9 2.2 4 4 9 Solder pins for printed circuit board Spring terminals Screw clamp v Slip-on 1 x 0.25 in., or 2 x 0.11 in. 12 Solder pins for printed circuit board Spring terminals x v w Standard control circuit voltages (variable delivery times, please consult your Local Square D Field Sales Office.). Pre-wired power circuit connections are standard on screw clamp versions. Use voltage codes on page 49 Coil Selection to complete catalog number. Auxiliary Contacts Type of Connection Catalog Number xw N/O 1 1 1 1 1 1 1 1 1 1 1 1 N/C 1 1 1 1 1 1 1 1 1 1 1 1 LP5K0610 LP5K0601 LP5K06107 LP5K06017 LP5K06105 LP5K06015 LP5K06103 LP5K06013 LP5K0910 LP5K0901 LP5K09107 LP5K09017 LP5K09105 LP5K09015 LP5K09103 LP5K09013 LP5K1210 LP5K1201 LP5K12107 LP5K12017 LP5K12105 LP5K12015 LP5K12103 LP5K12013 1.08 (0.490) 1.08 (0.490) 1.03 (0.470) 1.03 (0.470) 1.17 (0.530) 1.17 (0.530) 1.08 (0.490) 1.08 (0.490) 1.08 (0.490) 1.08 (0.490) 1.03 (0.470) 1.03 (0.470) 1.17 (0.530) 1.17 (0.530) 1.08 (0.490) 1.08 (0.490) 1.08 (0.490) 1.08 (0.490) 1.03 (0.470) 1.03 (0.470) 1.17 (0.530) 1.17 (0.530) 1.08 (0.490) 1.08 (0.490) Weight lb. (kg)

7.5

10

12

5.5

4 (> 440) 5.5 (440)

Coil Selection
Volts DC Code 12 JW3 24 BW3 48 EW3 72 SW3

LP5K06105

66 2001 Schneider Electric All Rights Reserved


04/01

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Selection of Low-consumption Contactors for Resistive Loads
Three- and Four-pole Contactors with Low-consumption Coils for DC Control Circuits The table below shows three- and four-pole contactors with low-consumption coils for DC control circuits. They are compatible with programmable controller outputs, and incorporate an LED indicator. For wide-range coils (0.7 to 1.3 Vc), a suppressor is fitted as standard (consumption is 1.8 W). The contactors mount on 35 mm DIN rails or with 4 mm (# 6) screws. The wire termination screws are in the open, ready-to-tighten position. For information on add-on auxiliary contact blocks and accessories, see page 69.
Power Poles Non-inductive loads Category AC-1 Maximum current at 50 C (122 F) A Auxiliary Contacts Catalog Number xw N/O 3 Screw clamp 4 2 3 Slip-on 1 x 0.25 in. or 2 x 0.11 in. 20 Solder pins for printed circuit board 4 2 3 4 2 3 Spring terminals 4 2 x w N/C 2 2 2 N/O 1 1 1 1 N/C 1 1 1 1 LP4K0910 LP4K0901 LP4K09004 LP4K09008 LP4K09107 LP4K09017 LP4K090047 LP4K090087 LP4K09105 LP4K09015 LP4K090045 LP4K090085 LP4K09103 LP4K09013 LP4K090043 LP4K090083 0.52 (0.235) 0.52 (0.235) 0.52 (0.235) 0.52 (0.235) 0.52 (0.235) 0.52 (0.235) 0.52 (0.235) 0.52 (0.235) 0.58 (0.265) 0.58 (0.265) 0.58 (0.265) 0.58 (0.265) 0.52 (0.235) 0.52 (0.235) 0.52 (0.235) 0.52 (0.235) Weight lb. (kg)

Type of Connection

LP4K090047

Standard control circuit voltages (variable delivery times, please consult your Local Square D Field Sales Office.). Use voltage codes on page 49 Coil Selection to complete catalog number.

Coil Selection
Volts DC Code 12 JW3 24 BW3 48 EW3 72 SW3

67
04/01

2001 Schneider Electric All Rights Reserved

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Selection of Low-consumption Contactors for Resistive Loads
Three- and Four-pole Reversing Contactors with Low-consumption Coils for DC Control Circuits The table below shows three- and four-pole contactors with low-consumption coils for DC control circuits. They are compatible with programmable controller outputs, and incorporate an LED indicator and mechanical interlock. For wide-range coils (0.7 to 1.3 Vc), a suppressor is fitted as standard (consumption is 1.8 W). LP5K0910 The contactors mount on 35 mm DIN rails or with 4 mm (# 6) screws. The wire termination screws are in the open, ready-to-tighten position. Customer wiring is required to connect coil terminations to the electrical interlock; see page 72 for more information. For information on add-on auxiliary contact blocks and accessories, see page 69.
Power Poles Non-inductive loads Category AC-1 Maximum current at 50 C (122 F) A Auxiliary Contacts Catalog Number xw N/O 3 Screw clamp 3 4 3 Slip-on 1 x 0.25 in. or 2 x 0.11 in. 20 Solder pins for printed circuit board 3 4 3 3 4 3 Spring terminals 3 4 N/C N/O 1 1 1 1 N/C 1 1 1 1 LP5K0910 s LP5K0901 s LP5K09004 LP5K09107 LP5K09017 LP5K090047 LP5K09105 LP5K09015 LP5K090045 LP5K09103 LP5K09013 LP5K090043 1.08 (0.490) 1.08 (0.490) 1.08 (0.490) 1.03 (0.470) 1.03 (0.470) 1.17 (0.530) 1.17 (0.530) 1.17 (0.530) 1.17 (0.530) 1.08 (0.490) 1.08 (0.490) 1.08 (0.490) Weight lb. (kg)

Type of Connection

x Standard control circuit voltages (variable delivery times, please consult your Local Square D Field Sales Office.). s WARNING: These reversing contactors are pre-wired for reverse motor operation w Use voltage codes on page 49 Coil Selection to complete catalog number.

Coil Selection
Volts DC Code 12 JW3 24 BW3 48 EW3 72 SW3

68 2001 Schneider Electric All Rights Reserved


04/01

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Selection of Auxiliary Contacts and Accessories for Low-consumption Contactors

Instantaneous Auxiliary Contact Blocks (clip-on front mounting, 1 block per contactor)
Auxiliary Contacts Type of Connection Type of Contactor N/O 2 Screw clamp 3- or 4-pole 1 N/C 2 1 2 1 2 1 LA1KN20 LA1KN02 LA1KN11 LA1KN207 LA1KN027 LA1KN117 LA1KN203 LA1KN023 LA1KN113 0.10 (0.045) 0.10 (0.045) 0.10 (0.045) 0.10 (0.045) 0.10 (0.045) 0.10 (0.045) 0.10 (0.045) 0.10 (0.045) 0.10 (0.045) Catalog Number Weight lb. (kg)

LP1KN
Slip-on 1 x 0.25 in. or 2 x 0.11 in. 3- or 4-pole

2 1 2 Spring terminals 3- or 4-pole 1

With terminal referencing conforming to EN 50012


Screw clamp 3-pole, 6 and 9 A 4-pole, 9 A 1 1 2 1 1 LA1KN02M LA1KN11M LA1KN11P 0.10 (0.045) 0.10 (0.045) 0.10 (0.045)

Electronic Time-delay Auxiliary Contact Blocks


Relay output, with common point changeover contact, AC or DC 240 V, 2 A maximum. Control voltage: 0.85 to 1.1 Vc. Maximum switching capacity: 250 VA or 150 W. Operating temperature: -10 to + 60 C (14 to 140 F). Reset time: 1.5 s during the time-delay period, 0.5 s after the time delay period.

Clip-on front mounting, 1 block per contactor


Auxiliary Contacts Voltage Type Timing Range Catalog Number Weight lb. (kg)

LA1KT2

V AC or DC 24 to 48 AC 110 to 240 On-delay On-delay

s 1 to 30 1 to 30

SPDT 1 1 LA2KT2E LA2KT2U 0.09 (0.040) 0.09 (0.040)

Mounting and Marking Accessories


Description Mounting plates (order 1 for a contactor; order 2 for a reversing contactor) Marker holder Application For mounting on 1 rail For mounting on 2 rails Clip-on Clip-on 110/120 mm mounting centers On to front of contactor Strips of 10 identical numbers 0 to 9 Clip-in markers 4 maximum per contactor Strips of 10 identical capital letters A to Z 35mm " DIN rail (7.5 mm deep x 2 m long) 35mm " DIN rail (15 mm deep x 2 m long) v Complete the catalog number by replacing the with the required character. 25 10 10 AB1G v AM1DP200 AM1ED200 0.004 (0.002) 2.88 (1.310) 1.44 (0.650) Sold in lots of 1 10 100 25 Unit Catalog No. LA9D973 DX1AP25 LA9D90 AB1R v Weight lb. (kg) 0.05 (0.025) 0.14 (0.065) 0.002 (0.001) 0.004 (0.002)

DX1AP25 Cabling Accessories


Description Application For 2-poles Paralleling links For 4-poles For 3-pole reversing contactors for motor control For 4-pole changeover contactor pairs With screw clamp terminals With screw clamp terminals For contactors with screw clamp terminals For contactors with screw clamp terminals Sold in lots of 4 2 Unit Catalog No. LA9E01 LA9E02 Weight lb. (kg) 0.02 (0.010) 0.03 (0.015)

Set of 6 power connections

100

LA9K0969

0.02 (0.010)

Set of 4 power connections

100

LA9K0970

0.02 (0.010)

LA9E01
69
04/01

2001 Schneider Electric All Rights Reserved

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Dimensions and Mounting of Low-consumption Contactors
XXXXX
Contactors LP4K On panel

On mounting rail AM1DP200 or AM1DE200 1.4 in. (35 mm) DIN rail

LA1 K

0.16 (#6) screws 4mm 2.28 58

2.28 58

1.97 50

2.24 57

1.78 45

1.22 31

2.24 57

1.38 35 1.78 45

On one asymmetrical rail DZ5MB with clip-on mounting plate LA9D973 DX1AP25

0.20 5

DZ5 ME5

1.97 50

4.72 120

2.24 57

0.83 21

1.38 35 1.78 45

0.20 5

On printed circuit board

2.24 57
A1

1.06 27

1.78 45

0.34 8.65

== =

2.28 58

10x 0.05 1.3

1.78 45

Electronic time-delay auxiliary contact blocks LA2KT On contactor

1.97 50 2.09 53

A2

LA2 KT

1.34 34

1.50 38

1.06 27

2.28 58

1.34 34

2.24 57

Dimensions inches mm

70 2001 Schneider Electric All Rights Reserved


04/01

4.33 110

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Dimensions and Mounting of Low-consumption Reversing Contactors

Reversing contactors LP5K On panel

On mounting rail AM1DP200 or AM1DE200 1.4 in. (35 mm) DIN rail

LA1K

2.28 58

1.97 50

2.24 57 1.22 31 2.24 57 = 3.15 80 3.54 90 = =

2.28 58

0.16 (#6) screws 4 mm

3.54 90

On one asymmetrical rail DZ5MB with 2 clip-on mounting plates LA9D973 or on 2 mounting plates DX1AP25. 2 x LA9D973 2 x DX1AP25

0.20 5

1.78 45 DZ5 ME5

1.97 50

2.24 57

0.83 21

0.20

3.54 90
On printed circuit board for reversing contactors or 2 contactors mounted side by side
2.24 57 1.06 27 3.54 90

0.34 8.65

== =

= ==

0.34 8.65

A1

A1 A2

2.28 58

A2

20x1.3 0.05

1.78 45

1.78 45

Electronic time-delay auxiliary contact blocks LA2KT On reversing contactors

1.97 50 2.09 53

1.38 35

LA2 KT

1.34 34

1.50 38

1.06 27

2.28 58

4.72 120

1.34 34

2.24 57

Dimensions inches mm

4.33 110

71
04/01

2001 Schneider Electric All Rights Reserved

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Type LPK Schematics

Type LPK Three-pole Low-consumption Contactors, Reversing Contactors, and Accessories


3-pole contactors LP4K 3-pole + N/O 3-pole + N/C Integrated-coil suppression device LP4K

3/L2

1/L1

5/L3

13/NO

3/L2

1/L1

5/L3

A2

14

A2

A1

T1/2

T2/4

T3/6

T1/2

T2/4

T3/6

22

21/NC

A1

3-pole reversing contactors LP5K With screw clamp terminals 3-pole + N/O

Dashed lines indicate suggested customer wiring to electrically interlock coils 3-pole + N/C

Integrated-coil suppression device LC5K

3/L2

5/L3

3/L2

1/L1

13/NO

1/L1

5/L3

13/NO

3/L2

5/L3

3/L2

1/L1

21/NC

1/L1

5/L3

A1

A1

A1

21/NC

A2

T3/6

T1/2

T2/4

T1/2

T2/4

T3/6

A2

14

14

A2

T3/6

T1/2

T2/4

T1/2

T2/4

T3/6

A2

22

22

A1

With Slip-on connectors or solder pins for printed circuit boards 3-pole + N/O
3/L2 5/L3 3/L2 1/L1 13/NO 1/L1 5/L3 13/NO

3-pole + N/O
3/L2 5/L3 3/L2 1/L1 21/NC 1/L1 5/L3 21/NC

A1

A1

A1

A2

A2

A2

14

14

T3/6

T1/2

T2/4

T1/2

T3/6

T1/2

T2/4

T1/2

Instantaneous auxiliary contact blocks LA1K For 3-pole contactors 2 N/O LA1KN20 LA1KN207 2 N/C LA1KN02 LA1KN027 1 N/O + 1 N/C LA1KN11 LA1KN117 Terminal referencing conforming to standard EN 50012 2 N/C LA1KN02 1 N/O + 1 N/C LA1KN11M

53/NO

63/NO

T2/4

51/NC

T3/6

61/NC

53/NO

61/NC

T2/4

T3/6

A2

22

22

A1

52

54

64

62

54

62

31/NC

22

22

Electronic Time-delay Auxiliary Contact Blocks LA2KT For 3-pole contactors LPK 1 C/O

A1

16

72 2001 Schneider Electric All Rights Reserved


04/01

A2

15

18

32

34

33/NO

21/NC

21/NC

-A2

+A1

-A2

+A1

K-line Mini-contactors, Enclosed Starters, Overload Relays, and Accessories


Type LPK Schematics

Type LPK Four-pole Low-consumption Contactors, Reversing Contactors, and Accessories


4-pole contactors LP4K 4-pole + N/O 2-pole N/O + 2-pole N/C Integrated-coil suppression device LP4K

3/L2

1/L1

5/L3

7/L4

R1

R3

A1

A2

T1/2

T2/4

T3/6

T4/8

A2

A1

R2

R4

4-pole reversing contactors LP5K With screw clamp terminals


1N 1/L1 1/L2 1/L3 2/L1 2/L2 2/L3 2N

Integrated-coil suppression device LP5K With slip-on terminals or solder pins for printed circuits boards

A2

A1

A1

A2

A2

A2

L1

L2

L3

Instantaneous auxiliary contact blocks LA1K 2 N/O LA1KN20 LA1KN207 2 N/C LA1KN02 LA1KN027 1 N/O + 1 N/C LA1KN11 LA1KN117 Terminal referencing conforming to standard EN 50012 1 N/O + 1 N/C LA1KN11P

53/NO

63/NO

51/NC

61/NC

53/NO

61/NC

13/NO

52

54

64

62

54

62

14

Electronic Time-delay Auxiliary Contact Blocks LA2KT For 3-pole contactors LPK 1 C/O

A1

16

A2

15

18

22

21/NC

-A2

+A1

A1

A1

-A2

+A1

73
04/01

2001 Schneider Electric All Rights Reserved