You are on page 1of 1

2 Functions

Figure 2-59

Distance protection for three ends with two 7SA6 and one 7SA522, chain topology

Communication Media

The communication can be carried out directly via fiber optic connections or via communication networks. Which kind of media is used depends on the distance and on the communication media available. For shorter distances, direct connection via fiber optic cables with a transmission rate of 512 kBit/s is possible. Otherwise we recommend communication converters. A transmission via copper cables and communication networks can also be realized. Please take into consideration that the responding times of the protection data communication depend on the quality of transmission and that they are prolonged in case of a reduced transmission quality and/or an increased operating time. Figure 2-60 shows some examples for communication connections. In case of a direct connection the distance depends on the type of the optical fibre. Table 2-15 lists the options available. The modules in the device are replaceable. For ordering information see Appendix, under Accessories.
Table 2-15 Module in the Device FO5 FO6 FO7 FO8 FO17 FO18 FO19 Communication via Direct Connection Connector Type ST ST ST FC LC LC LC Fibre Type Multimode 62.5/125 Pm Multimode 62.5/125 Pm Monomode 9/125 Pm Monomode 9/125 Pm Monomode 9/125 Pm Monomode 9/125 Pm Monomode 9/125 Pm Optical Perm. Path AtWavelength tenuation 820 nm 820 nm 1300 nm 1300 nm 1300 nm 1300 nm 1550 nm 8 dB 16 dB 7 dB 18 dB 13 dB 29 dB 29 dB Distance, Typical 1.5 km (0.94 miles) 3.5 km (2.18 miles) 10 km (6.2 miles) 35 km (21.75 miles) 24 km (14.9 miles) 60 km (37.3 miles) 100 km (62 miles)

140

7SA6 Manual C53000-G1176-C156-4