You are on page 1of 9

Diversified Air Systems,Inc.

Firetrace Technology

Call today: 800-264-8958

8/16/2013

What is Firetrace?
Suppression for the micro-environment Pneumatic heat detection Fire suppression system Total flooding OR Local application Detection and suppression at the ignition point

8/16/2013

Its All About the TUBE

Linear, pneumatic flame detection Bursts at 212F (100C) Tubing can be the detector & the piping network Tubing is durable and flexible Tubing is not conductive or corrosive Good for harsh chemical environments
8/16/2013 3

Direct System
Direct Low Pressure System

8/16/2013

Characteristics of the Firetrace Detection Tubing


Commercial Name : Physical Appearance: Change in Physical state: Bulk Density : Dielectric Strength: dry 40 Thermal Decomposition: Temperature at Burst: FT 1992 Thermoplas 6mm OD red tube Melts @ 194 C (381.2 F) 17g / meter (5.18g/ft) (DIN 53481)kV/mm Above 300 C (572 F) 100-115 C @ 150 psi (212-239 F @ 150 psi)

8/16/2013

The Burst

8/16/2013

Direct Low Pressure (DLP) System Tubing is used as a detector and delivery of agent from cylinder Valve is a X-over only to allow for connection of the tubing to cylinder

4 ports on this valve for gauge, P/S, Ball Valve and cylinder
Discharge time is limited due to the x-sectional area of the ball valve orifice.
8/16/2013

Max 3.3 ft / layer

DLP (Direct Low Pressure) System

8/16/2013

OPTIONS
PRESSURE SWITCH

Monitors pressure in the tubing and in cylinder Can use one on cylinder and as many as needed on tubing network Used for: Building alarm tie-in Power lock-out or shunt trip Fan/damper control Auxiliary controls 8/16/2013