Professional Documents
Culture Documents
Firetrace Technology
8/16/2013
What is Firetrace?
Suppression for the micro-environment Pneumatic heat detection Fire suppression system Total flooding OR Local application Detection and suppression at the ignition point
8/16/2013
Linear, pneumatic flame detection Bursts at 212F (100C) Tubing can be the detector & the piping network Tubing is durable and flexible Tubing is not conductive or corrosive Good for harsh chemical environments
8/16/2013 3
Direct System
Direct Low Pressure System
8/16/2013
8/16/2013
The Burst
8/16/2013
Direct Low Pressure (DLP) System Tubing is used as a detector and delivery of agent from cylinder Valve is a X-over only to allow for connection of the tubing to cylinder
4 ports on this valve for gauge, P/S, Ball Valve and cylinder
Discharge time is limited due to the x-sectional area of the ball valve orifice.
8/16/2013
8/16/2013
OPTIONS
PRESSURE SWITCH
Monitors pressure in the tubing and in cylinder Can use one on cylinder and as many as needed on tubing network Used for: Building alarm tie-in Power lock-out or shunt trip Fan/damper control Auxiliary controls 8/16/2013
10