Integra Automasi
2 3
NM NM
HT HT
HH HH
REV
DATE
ISSUE TYPE
PREPD BY
REVD BY
APPD BY
CLIENT APPD
0 1 2 3
FEB 19, 2012 SEP 4, 2012 SEP 28, 2012 NOV 13, 2012
AT NM NM NM
HT HT HT HT
HH HH HH HH
2 OF 12
TABLE OF CONTENT
1 1.1
HARDWARE AND SOFTWARE FOR TERAS STATION Hardware SCADA Workstation Workstation LED Monitor Manageable Switch Workstation Desk Software SCADA Software
4 4 4 4 5 5 6 6 7 7 7 8 8 10 10 10 11 12
1.1.1 1.1.2 1.1.3 1.1.4 1.2 1.2.1 2 2.1 2.2 2.3 2.4 3 3.1 3.2 3.3 4
SYSTEM ARCHITECTURE SCADA System Architecture Teras Station Existing System Architecture Teras Station Proposed System Architecture Bandwidth Requirement SCADA/HMI DESIGN Overview Teras Station Alarms Trending BILL OF MATERIALS
3 OF 12
Optical drive : DVDRW Video graphic : VGA NVIDIA Quadro FX580 512M Network USB Serial : one (1) Gigabit Lan Integrated Broadcom 5764 LAN, Infineon TPM 1.2 controller : Front 2 USB 2.0, Rear 6 USB 2.0 : None
1.1.2
Model
: ZR2440w
4 OF 12
Response Time : 6ms, Contrast Brightness Type Input USB : 5000000:1 : 250cd/m : LED Monitor Wide Screen : one (1) VGA Port, one (1) DVI-D Port, one (1) HDMI Port : Integrated, self-powered 4 port USB 2.0
1.1.3
Manageable Switch
: Cisco Catalyst 2960-8TC-L : Cisco : 8 Ports : 10/100 MBps : Industrial Ethernet switch Workstation Desk
5 OF 12
1.2 1.2.1
6 OF 12
2 SYSTEM ARCHITECTURE
The Operator Station shall be based on standard off-the-shelf workstation hardware running on a Windows based operating system. Vijeo Citect is using full 32 bit (65 million) colors. For integration with existing Historian we use Matrikon OPC Server client for ODBC. This OPC server is using for logging data to SQL Server. 2.1 SCADA System Architecture
SCADA System centralizes in Soka Office. All parameter in all stations can be monitor in Central Monitoring room SCADA at Soka Office.
2.2
An existing system at Teras is Infilink HMI and AllenBradley SLC-500 PLC. PLC System is not redundant. And communication to PLC is RS485 using protocol DH+.
7 OF 12
2.3
2.4
Bandwidth Requirement
Bandwidth requirement for SCADA is less than 32 Kbps. Please find this example below. This example is for bandwidth calculation. Status Register The 128 Status Register will be retrieve every 250 ms and using Modbus Function code 2
Teras Station Function Design Specification
8 OF 12
Request 8 bytes
Response 15 bytes
This results is 23 bytes every 250 ms = 92 bytes per second or 736 bits per second = 0.7 kbps
Input Register The 64 Input Register will be retrieve every 250 ms and using Modbus Function code 4 Request 8 bytes Response 133 bytes
This results is 141 bytes every 250 ms = 564 bytes per second or 4512 bits per second = 4.5 kbps
9 OF 12
3 SCADA/HMI DESIGN
3.1 Overview Teras Station
3.2
Alarms
10 OF 12
3.3
Trending
11 OF 12
4 BILL OF MATERIALS
ITEM NO. DESCRIPTION Hardware & Software Teras Station SCADA Hardware Operator and Engineering Workstation - Xeon W3520, 2GB, DDR3-1333 ECC, 320GB HDD SATA, DVDRW, VGA NVIDIA Quadro FX580 512MB, Win 7 23", 1920 x 1080, 2ms, 5000000:1, 250cd/m, LED WideScreen Industrial Ethernet switch with 8 Ethernet 10/100 ports Computer Desk Cable and Accessories Software Full Server, 15000 points Box with USB key 2 Engineering and Services Teras Station Adaptation Work / Installation Engineering Documents Training Mob Demob Manufacture Model Qty Unit
1 1.1
1 1
Ea Ea
Cisco Alba
1 1 1 1 1 1
Ea Ea Lot Ea Ea Lot
1.2
Schneider Schneider
12 OF 12