NPV Calculation for Transformers NPV = (Po+A^2*Pk) * 8760 * B * C Po = No Load Loss (KW) Pk = Load Loss (kW) A = Loading factor,

as a percentage of Transformer rating / 100 B = Energy Unit Cost / kWH (USD) C = Capitalisation, at "r" rate of interest for "t" years C= 1 r

__

1 r(1+r)^t

Factor Po Pk A B C NPV (USD)

NPV 2.6 25 0.5 0.055 10.67 45,496