GeneralRatingStructureofHighVoltageCircuit Breakers:IEEEC37.041999
ConsiderationsforselectionofCircuitBreakersfor CapacitiveCurrentSwitching
Ratingsforcapacitancecurrentswitching 1)Ratedoverheadlinechargingcurrent; 2)Ratedisolatedcableandisolatedshuntcapacitorbankswitchingcurrent; 3)Ratedbacktobackcableandisolatedshuntcapacitorbankswitchingcurrent; 4)Ratedtransientinrushcurrentpeak; 5)Ratedtransientinrushcurrentfrequency;
ConsiderationsforselectionofCircuitBreakersfor CapacitiveCurrentSwitching
Capacitivecurrentscanbeencounteredinfollowingsituations: Switchingofnoloadoverheadlines Switchingofnoloadcables Switchingofcapacitorbanks Switchingoffilterbanks Selectionofratingofcircuitbreakerstoswitchcapacitivecurrentfollowing considerationsarerequired: Application Powerfrequencyofthenetwork Groundingsituationsofthenetwork Presenceofsingleortwophasegroundfaults
OverheadlinechargingcurrentandInterruption
NoLoadOverheadLines: Uncompensated Compensated Uncompensatedlines: Especially longlinesarerepresentedas capacitance. HighchargingcurrentandRecovery voltagesoninterruptionofcharging currents CompensatedLines: Havelesser chargingcurrentshencelesser recoveryvoltages.
FigureEnergization ofnoloadlines:basicphenomena
FigureHalfcycleofrecoveryvoltage
CableEnergization anddeenergization
Energization ofcables: IsolatedCable BacktoBackCable Theinrushcurrentsincables isnonoscillatory. InitialRateofRiseshouldnot overthebreakerrating.
FigureTypicalcircuitforbacktobackswitching
FigureEquivalentcircuitforbacktobackcableswitching
Shuntcapacitorbankenergization anddeenergization
Energization ofshuntcapacitorbanks: Isolatedcapacitorbanks BacktoBackcapacitorbanks Theinrushcurrentsareoscillatoryand havehighfrequencies InitialRateofRiseshouldnotoverthe breakerrating. Recoveryvoltagescanbehigh,especially iftherearerestrikes.
FigureParallelcapacitorbanks
FigureVoltageandcurrentwaveshapesinthecaseofarestrike
TransientRecoveryVoltage
Voltagewhichappearsacrossthecircuitbreakercontactsafter interruptionoffaultorinterruptionofcircuit. Itconsistsofthehighfrequencyvoltagesuperimposedonsystem frequencyvoltage Generallytheresultantvoltagewaveturnsouttobe1cosinewaveand alsohastheexponentialcomponent.
Figure EquivalentRLCcircuit
TransientRecoveryVoltage
IEEEC37011ApplicationguideforTransient RecoveryvoltageofACHighVoltagecircuit breakers:SpecifiestheTRVenvelopetobe usedforselectionofcircuitbreakers. BasedonSystemVoltage SystemConditionsdecide ThecircuitbreakerspecificTRVenvelopeis tobecalculatedandsystemTRVistobe comparedtothisenvelope. ThesystemTRVshouldbebelowthecircuit breakerTRVenvelopetomakethe application.
Figure EquivalentRLCcircuit
FigureTRVenvelopes100kVandbelow