ERROR CODE

MULTI VARIABLE AIR CONDITIONERS CASSETTE TYPE INDOOR UNIT


ERROR
MODEL NO. MEANING
CODE
TMV-ND28T/A-T, L0 Indoor Unit Error
TMV-ND36T/A-T, L1 Indoor Fan Protection
TMV-ND45T/A-T, L2 E-heater Protection
TMV-ND50T/A-T,
L3 Water Full Protection
TMV-ND56T/A-T,
TMV-ND63T/A-T, L4 Wired Controller Power Supply Error
TMV-ND71T/A-T, L5 Anti-Frosting Protection
TMV-ND80T/A-T, L7 No Master Indoor Unit Error
TMV-ND90T/A-T, L8 Power Insufficiency Protection
TMV-ND100T/A-T,
L9 Quantity Of group Control Indoor Units Setting Error
TMV-ND112T/A-T,
TMV-ND125T/A-T, LA Indoor Units Incompatibility Error
TMV-ND140T/A-T, LC Outdoor-Indoor Incompatibility Error
TMV-ND160T/A-T, LH Low Air Quantity Warning

SPLIT AIR CONDITIONER INVERTER: WIRED CONTROLLER (OPTIONAL)


ERROR
MODEL NO. MEANING
CODE
E1 High Pressure Protection
E2 Anti-Freezing Protection
E3 Low Pressure Protection
E4 High Discharge Temperature Protection
E5 Whole Unit Over-Current Protection
E6 Indoor and Outdoor Communication Error
E7 Running Mode Conflict
TWC 09VRL, E8 Overload Protection
TWC12VRL, E9 Indoor Unit Full Water Error
TWC18VRL, EU Frequency Restricted/Reduced with IPM Temperature Protection
TWC24VRL, En Frequency Restricted/Reduced with IPM Current Protection
F0 System Charge Shortage or Blockage Protection
F1 Return Air Temperature Sensor Open/Short Circuited
F2 Evaporator Temperature Sensor Open/Short Circuited
F3 Outdoor Ambient Temperature Sensor Open/Short Circuited
Outdoor Unit Condenser Mid-Tube Temperature Sensor
F4
Open/Short Circuited
F5 Discharge Temperature Sensor Open/Short Circuited
SPLIT AIR CONDITIONER INVERTER: WIRED CONTROLLER (OPTIONAL)
ERROR
MODEL NO. MEANING
CODE
F6 Frequency Restricted/Reduced with Overload Protection
F8 Frequency Restricted/Reduced with Whole Unit Current Protection
F9 Frequency Restricted/Reduced with High Discharge Temperature
FH Frequency Restricted/Reduced with Anti-Freezing Protection
Fo Pump-Down
H1 Forced Defrosting
H3 Compressor Overheating Protection
H5 IPM Current Protection
H6 Motor Stalling
H7 Compressor Desynchronizing
HE Compressor Demagnetization Protection
Hc PFC Protection
U1 Compressor Phase Current Sensing Circuit Error
U3 DC Bus Voltage Drop Error
U5 Whole Unit Current Sensing Circuit Error
U7 4-Way Valve Reversing Error
U8 PG Motor Zero-Crossing Protection
LA Outdoor Fan 2 Error Protection
TWC 09VRL, Lc Compressor Start-up Failure
TWC12VRL, Ld Compressor Phase Loss/Reversal Protection
TWC18VRL, LE Compressor Stalling
TWC24VRL, LF Over-speeding
LP Indoor and Outdoor Units Unmatched
L3 Outdoor Fan 1 Error Protection
L9 Over-Power Protection
Pd Sensor Connection Protection
PE Temperature Drift Protection
PF Drive Board Temperature Sensor
PH DC Bus Over-Voltage Protection
PL DC Bus Under-Voltage Protection
PP AC Input Abnormal Protection
PU Capacitor Charging Error
P5 Over Phase Current Protection
P6 Drive Board Communication Error
P7 IPM Temperature Sensor Open/Short Circuited
P8 IPM Temperature Protection
P9 AC Contactor Protection
b5 Indoor Unit Liquid Valve Temperature Sensor Open/Short Circuited
b7 Indoor Gas Valve Temperature Sensor Open/Short Circuited
C5 Jumper Error
dn Communication Line Misconnected Or Expansion Valve Error
DC INVERTER U-MATCH SERIES FLOOR STANDING TYPE UNIT / DC INVERTER U-MATCH SERIES
CASSETTE TYPE UNIT / DC INVERTER U-MATCH SERIES DUCT TYPE UNIT / WIRED CONTROLLER XK60
ERROR
MODEL NO. MEANING
CODE
E1 Compressor High Pressure Protection
E2 Indoor Anti-Freeze Protection
Compressor Low Pressure Protection, Refrigerant Lack Protection
E3
and Refrigerant collecting mode
FLOOR E4 Compressor High Discharge Temperature Protection
STANDING E6 Communication Error
INDOOR UNIT: E8 Indoor Fan Motor Error
TVH36D3FI, E9 Full Water Protection
TVH60D3FI
EE Outdoor Memory Chip Error
OUTDOOR UNIT:
ee Drive Memory Chip Error
TUHD36ND3FO,
F0 Indoor Ambient Temperature Sensor Error
TUHD60ND3FO
F1 Evaporator Temperature Sensor Error
F2 Condenser Temperature Sensor Error
F3 Outdoor Ambient Temperature Sensor Error
F4 Discharge Temperature Sensor Error
F5 Temperature Sensor Error of Wired Controller
CASSETTE TYPE H3 Compressor Overload Protection
INDOOR UNIT: H4 Overloading
TKH18D3FI, H5 IPM Protection
TKH24D3FI, H6 DC Fan Motor Error
TKH36D3FI, H7 Drive Desynchronizing Protection
TKH48D3FI, Hc PFC Protection
TKH60D3FI Lc Activation Failure
OUTDOOR UNIT: Ld Compressor Phase Sequence Protection
TUHD18ND3FO, LE Compressor Stalling Protection
TUHD24ND3FO, LF Power Protection
TUHD36ND3FO, Lp Indoor and Outdoor Mismatch
TUHD48ND3FO, P0 Drive Reset Protection
TUHD60ND3FO, P5 Over-Current Protection
P6 Communication Error Between Main Control and Drive
DC INVERTER U-MATCH SERIES FLOOR STANDING TYPE UNIT / DC INVERTER U-MATCH SERIES
CASSETTE TYPE UNIT / DC INVERTER U-MATCH SERIES DUCT TYPE UNIT / WIRED CONTROLLER XK60
ERROR
MODEL NO. MEANING
CODE
P7 Drive Module Sensor Error
DUCT TYPE P8 Drive Module Over Temperature Protection
INDOOR UNIT: P9 Zero Passage Protection
TFH18D3FI, PA AC Current Protection
TFH24D3FI, Pc Drive Current Protection
TFH36D3FI, Pd Sensor Connecting Protection
TFH48D3FI, PE Temperature Drift Protection
TFH60D3FI PF Electric Box Sensor Error
OUTDOOR UNIT: PL Bus Low Voltage Protection
TUHD18ND3FO, PH Bus High Voltage Protection
TUHD24ND3FO, PP Input Voltage Abnormality
TUHD36ND3FO, PU Charge Loop Error
TUHD48ND3FO, C4 Outdoor Unit Capacity Code Error
TUHD60ND3FO, C5 Indoor Unit Capacity Code Error
U7 4-Way Valve Direction Changing Protection

WIRED CONTROLLER XK46


ERROR CODES FOR OUTDOOR UNIT
b1 Outdoor Ambient Temperature Sensor Error
b2 Defrosting Temperature Sensor 1 Error
b3 Defrosting Temperature Sensor 2 Error
b4 Sub cooler Liquid-out Temperature Sensor Error
b5 Sub cooler Gas-out Temperature Sensor Error
b6 Gas-Liquid Separator Inlet Temperature Sensor Error
b7 Gas-Liquid Separator outlet Temperature Sensor Error
b8 Outdoor Humidity Sensor Error
b9 Heat Exchanger Gas-out Temperature Sensor Error
bA Oil-Return Temperature Sensor Error
bC Compressor 1 Top Temperature Sensor Detachment Protection
bE Malfunction of Entry Tube Temperature Sensor of Condenser
bF Malfunction of Exit Tube Temperature Sensor of Condenser
bJ High and Low Pressure Sensors are Connected Inversely
bL Compressor 2 Top Temperature Sensor Detachment Protection
E0 Outdoor Unit Error
E1 High Pressure Protection
E2 Discharge Low Temperature Protection
E3 Low Pressure Protection
E4 Excess Discharge Temperature Protection of Compressor
F0 Bad Performance of the Outdoor Main Board
F1 High Pressure Sensor Error
F3 Low Pressure Sensor Error
F5 Compressor 1 Discharge Temperature Sensor Error
F6 Compressor 2 Discharge Temperature Sensor Error
F7 Compressor 3 Discharge Temperature Sensor Error
F8 Compressor 4 Discharge Temperature Sensor Error
F9 Compressor 5 Discharge Temperature Sensor Error
FA Compressor 6 Discharge Temperature Sensor Error
Fb/FU Compressor 2 Top Temperature Sensor Error
FC Compressor 2 Current Sensor Error
FE Compressor 4 Current Sensor Error
FF Compressor 5 Current Sensor Error
FH Compressor 1 Current Sensor Error
FL Compressor 3 Current Sensor Error
FJ Compressor 6 Current Sensor Error
FP Malfunction of DC Motor
P0 Compressor Drive Board Error
P1 Compressor Drive Board Malfunction
P2 Protection of Compressor Drive Board Power Supply
P3 Protection of Compressor Drive Board Module Reset
J1 Compressor 1 Over-Current Protection
J2 Compressor 2 Over-Current Protection
J3 Compressor 3 Over-Current Protection
J4 Compressor 4 Over-Current Protection
J5 Compressor 5 Over-Current Protection
J6 Compressor 6 Over-Current Protection
J7 4-Way Valve Blow-by Protection
J8 System Pressure Over-Ratio Protection
J9 System Pressure Under-Ratio Protection
JA Protection of Abnormal Pressure
JC Protection of Water Flow Switch
JE Oil Return Pipe is Blocked
JF Oil Return Pipe is Leaking
JL Protection of Low High-Pressure
H2 Protection of Fan Drive Board Power Supply
ERROR CODES FOR INDOOR UNIT
A0 Unit is Waiting For Debugging.
A1 Check the Compressor Operation Parameters.
A2 After-Sales Refrigerant Reclaim
A3 Defrosting
A4 Oil Return
A5 Online Testing
A8 Vacuum-Pumping Mode
Ab Emergency Stop
AC Cooling
Ad Operation Restriction
AF Fan
AH Heating
AJ Filter Clean Reminder
An High Temperature Prevention Control
AU Remote Urgent Stop
Communication Between Indoor Unit And Outdoor Unit and the
C0 Communication Between Indoor Unit And Wired Controller Have
Malfunction
Communication Error Between Master Control and Inverter
C2
Compressor Drive
Communication Error Between Master Control and Inverter Fan
C3
Motor Drive
C4 Error of Lack of Indoor Unit
C5 Alarm of Indoor Unit Project Number Collision
C6 Alarm of Wrong Number of Outdoor Unit
Cb Outflow of Units IP Address
CF Error of Multiple Master Indoor Unit
CH Rated Capacity is Too High
CJ System Addressed is Compatible
CL Rated Capacity is Too Low
CP Error of Multiple Master Wired Controller
CU Communication Error Between Indoor Unit and Remote Receiver
d1 Indoor Unit PC-Board Error
d3 Ambient Temperature Sensor Error
d4 Inlet Pipe Temperature Sensor Error
d5 Malfunction of Middle Tube Temperature Sensor
d6 Outlet Pipe Temperature Sensor Error
d7 Humidity Sensor Error
d8 Water Temperature Sensor Error
d9 Jumper Cap Error
dA Indoor Unit Hardware Address Error
db Special Debugging Code
dC Capacity DIP Switch Setting Error
dE Indoor Unit CO2 Sensor Error
dH Wired Controller PC-Board Error
dL Outlet Air Temperature Sensor Error
L0 Indoor Unit Error
L1 Indoor Fan Protection
L2 E-Heater Protection
L3 Water Full Protection
L4 Wired Controller Power Supply Error1
L5 Anti-Frosting Protection
L7 No Master Indoor Unit Error
L8 Power Insufficiency Protection
L9 Quantity of Group Control Indoor Units Setting Error
LA Indoor Units Incompatibility Error
LC Outdoor-Indoor Incompatibility Error
LH Low Air Quantity Warning
LP Zero-Crossing Malfunction of PG Motor
n3 Compulsory Defrosting
n5 Compulsively excursion of Indoor Unit Project Number
nJ High Temperature Prevention Under Heating Mode
nL Target Low Pressure Modification
nP Temperature-Adjusting Value During Defrosting
nU Clear the Remote Control Shielding Order of Indoor Unit
U2 Outdoor Unit Capacity Code/Jumper Cap Setting Error
U3 Phase Sequence Protection Of Power Supply
U4 Protection Of Lack of Refrigerant
U5 Wrong Address of Compressor Drive Board
U6 Valve Abnormal Alarm
U8 Indoor Unit Tube Malfunction
U9 Outdoor Unit Tube Malfunction
UC Outdoor Master Indoor Unit is Successfully Set
UE Refrigerant Charging is Ineffective
Emergency Operation DIP Switch Setting of the Compressor is
UL
Wrong
TOSOT PHILIPPINES CORPORATION
2162 F.B. HARRISON STREET SAN JOSE, PASAY CITY
TELEPHONE NO: (02) 833-0000
Error Code 101
This Error code is for Cassette Type, Duct Type, Floor Standing and Floor Ceiling Inverter.

Model Error code Meaning


E1 Compressor High Pressure Protection
E2 Indoor Anti-Freeze Protection
Compressor Low Pressure Protection, Refrigerant Lack Protection and
CASSETTE TYPE E3
Refrigerant collecting mode
INDOOR UNIT: E4 Compressor High Discharge Temperature Protection
TKH18D3FI, E6 Communication Error
TKH24D3FI, E8 Indoor Fan Motor Error
TKH36D3FI, E9 Full Water Protection
TKH48D3FI, EE Outdoor Memory Chip Error
TKH60D3FI ee Drive Memory Chip Error
F0 Indoor Ambient Temperature Sensor Error
DUCT TYPE F1 Evaporator Temperature Sensor Error
INDOOR UNIT: F2 Condenser Temperature Sensor Error
F3 Outdoor Ambient Temperature Sensor Error
TFH18D3FI,
F4 Discharge Temperature Sensor Error
TFH24D3FI,
F5 Temperature Sensor Error of Wired Controller
TFH36D3FI, H3 Compressor Overload Protection
TFH48D3FI, H4 Overloading
TFH60D3FI H5 IPM Protection
H6 DC Fan Motor Error
FLOOR H7 Drive Desynchronizing Protection
STANDING Hc PFC Protection
INDOOR UNIT: Lc Activation Failure
TVH36D3FI, Ld Compressor Phase Sequence Protection
TVH60D3FI LE Compressor Stalling Protection
LF Power Protection
Lp Indoor and Outdoor Mismatch
P0 Drive Reset Protection
FLOOR CEILING
P5 Over-Current Protection
INDOOR UNIT: P6 Communication Error Between Main Control and Drive
TFH18D3FI, P7 Drive Module Sensor Error
TFH24D3FI, P8 Drive Module Over Temperature Protection
TFH36D3FI, P9 Zero Passage Protection
TFH48D3FI, PA AC Current Protection
TFH60D3FI Pc Drive Current Protection
Pd Sensor Connecting Protection
OUTDOOR UNIT: PE Temperature Drift Protection
TUHD18ND3FO, PF Electric Box Sensor Error
TUHD24ND3FO, PL Bus Low Voltage Protection
PH Bus High Voltage Protection
TUHD36ND3FO,
PP Input Voltage Abnormality
TUHD48ND3FO, PU Charge Loop Error
TUHD60ND3FO C4 Outdoor Unit Capacity Code Error
C5 Indoor Unit Capacity Code Error
U7 4-Way Valve Direction Changing Protection
TOSOT PHILIPPINES CORPORATION
2162 F.B. HARRISON STREET SAN JOSE, PASAY CITY
TELEPHONE NO: (02) 833-0000

Error Code 101


This Error code is for Wall mounted type Inverter. MODEL: TWC09VRL, TWC12VRL, TWC18VRL, TWC24VRL.

Error code Meaning


E1 High Pressure Protection
E2 Anti-Freezing Protection
E3 Low Pressure Protection
E4 High Discharge Temperature Protection
E5 Whole Unit Over-Current Protection
E6 Indoor and Outdoor Communication Error
E7 Running Mode Conflict
E8 Overload Protection
E9 Indoor Unit Full Water Error
EU Frequency Restricted/Reduced with IPM Temperature Protection
En Frequency Restricted/Reduced with IPM Current Protection
F0 System Charge Shortage or Blockage Protection
F1 Return Air Temperature Sensor Open/Short Circuited
F2 Evaporator Temperature Sensor Open/Short Circuited
F3 Outdoor Ambient Temperature Sensor Open/Short Circuited
F4 Outdoor Unit Condenser Mid-Tube Temperature Sensor Open/Short Circuited
F5 Discharge Temperature Sensor Open/Short Circuited
F6 Frequency Restricted/Reduced with Overload Protection
F8 Frequency Restricted/Reduced with Whole Unit Current Protection
F9 Frequency Restricted/Reduced with High Discharge Temperature
FH Frequency Restricted/Reduced with Anti-Freezing Protection
Fo Pump-Down
H1 Forced Defrosting
H3 Compressor Overheating Protection
H5 IPM Current Protection
H6 Motor Stalling
H7 Compressor Desynchronizing
HE Compressor Demagnetization Protection
Hc PFC Protection
U1 Compressor Phase Current Sensing Circuit Error
U3 DC Bus Voltage Drop Error
U5 Whole Unit Current Sensing Circuit Error
U7 4-Way Valve Reversing Error
U8 PG Motor Zero-Crossing Protection
LA Outdoor Fan 2 Error Protection
Lc Compressor Start-up Failure
Ld Compressor Phase Loss/Reversal Protection
LE Compressor Stalling
LF Over-speeding
LP Indoor and Outdoor Units Unmatched
L3 Outdoor Fan 1 Error Protection
L9 Over-Power Protection
Pd Sensor Connection Protection
PE Temperature Drift Protection
PF Drive Board Temperature Sensor
PH DC Bus Over-Voltage Protection
PL DC Bus Under-Voltage Protection
PP AC Input Abnormal Protection
PU Capacitor Charging Error
P5 Over Phase Current Protection
P6 Drive Board Communication Error
P7 IPM Temperature Sensor Open/Short Circuited
P8 IPM Temperature Protection
P9 AC Contactor Protection
b5 Indoor Unit Liquid Valve Temperature Sensor Open/Short Circuited
b7 Indoor Gas Valve Temperature Sensor Open/Short Circuited
C5 Jumper Error
dn Communication Line Misconnected Or Expansion Valve Error