- Connect External socket with DG – OK - Simulated the main power failure opening the DG incomer – OK - Check the Phase sequence in the Incomer Breaker Q2 incomer to from external Socket – OK - Check the input voltage(P-P & P-N) in the Breaker Q2 – OK - Check the input voltage(P-P & P-N) in the Breaker Q2 – OK - Close the breaker Q2-OK in manual mode – OK - Close breaker Q8 230V AC UPS – OK - Close the breaker RICB UPS Input – OK - Check the Main ok in display-OK - Close the Breaker ROCB UPS Output – OK - Check the polarity of BCB breaker and close the breaker BCB– OK - Press and Hold MANUAL VOLTAGE REGULATION CPSC button for 5 Sec – OK - Close the input of Invertor ICB INVERTER INPUT – OK - Close the EMERGENCY LINE INPUT ELCB – OK - Close SBCB STATIC SWITCH INPUT – OK - Close OCB UPS OUTPUT – OK - Close the QGD INCOMMING DISTRIBUTION – OK - Check all values and reading the reading in UPS Panel – OK - Close the distribution auxiliary breaker Q52.1 AUXILLARY LV SWITCH GEAR – OK - Close the distribution s auxiliary breaker Q52.5ASP1 F&G – OK - Close the distribution auxiliary breaker Q52.4 ASP1 LIGHT – OK - Close Q7 auxiliary panel and HVAC – OK - Close the MAIN FEEDER 400 AC FROM ASP1 – OK - Close the MINIMUM Voltage Relay QF10C – OK - Close BATTERY ROOM EXPRACTOR FAN A , B QF7A & QF7D – OK - Close IG13 C F&G INPUT FEEDER FROM UPS – OK - Close MINIMUM Voltage Relay QF10C – OK - Switched on F&G panel BY Close AA00A BREAKER – OK - Close QF13 C UNIT F&G – OK - Close QF 13 F FIRE FIGHTING CONTROL – OK - Close IG .1C MAIN SWITCH– OK - Close AUXILLARY BREAKER 230V AC QF2A – OK - Close AUXILLARY BREAKER 24 V AC QF2C – OK - Close AUXILLARY SOCKET 220 V AC QF2E – OK - Close QF2A AUXILLARY BREAKER 230 V AC – OK - Close QF2C AUXILLARY BREAKER 24 V AC – OK - Close QF2CE AUXILLARY SOCKET 220V AC – OK - Close FIRE DAMPER QF14A – OK - Close FIRE DAMPER ELECTRICAL ROOM QF 14C – OK - Close FIRE DAMPER TRANSFORMER ROOM QF 14D – OK - Close FIRE DAMPER TRANSFORMER ROOM QF 14E – OK - Simulation FAUL of detector. Has been removed detector and noted alarm appeared on F&G panel screen. After reinstalled the detector in base alarm has been cancelled-OK - Simulation of alarm opening the door of telecom room. Sound & visual alarm appeared in screen of F&G panel. Test –OK. - Simulation of batteries FAULT disconnecting the F&G local batteries. Alarm appeared in screen of F&G panel. After re-connect batteries alarm canceled. Test – OK - Close LIGHT MAIN BREAKER IG10D – OK - Close LIGHT ELECTRICAL ROOM QF-11B – OK - Close LIGHT TRANSFORMER QF11D – OK - Close LIGHT TRANSFORMER ROOM QF12C – OK - Close OUTDOOR LIGHT QF8A – OK - Close Breaker of incomer switch gear Q16 to Q35 in series– OK - Check the reading on display – OK - Move the Q2 breaker in auto mode – OK - Close SOLENOID for A& B QF4C & QF6C – OK - Close CRANKCASE for A& B QF4E & QF6E – OK - Close COMPRESSOR for A& B QF 3B & QF5B – OK - Close CONDENSOR FAN for A & B QF 4A & QF6A – OK - Close Auxiliary breaker HVAC C & D i.e. QF3A & QF5A – OK - Close SOLENOID for C& D QF-4C & QF-6C – OK - Close CRANKCASE for C& D QF-4A & QF-6A – OK - Close COMPRESSOR for C& D QF-3B & QF-5B – OK - Close CONDENSOR FAN for C& D – OK - EVAPORATOR FAN HVAC C QF-3D & QF-5D – OK - CONDENSOR FAN HVAC C QF-4A & QF-6A – OK - SOLENOID HVAC C QF-4C & QF-6C – OK - CRANKCASE HEATER HVAC C QF-4E & QF-6E – OK - SWITCH ON HVAC A &B AND HVAC C & D RESPECTIVELY AND CHECK THE TEMPERATURE IN DISPLAY-OK - Simulate and show alarm HP and LP in all HVAC. - Press EXNCP for CO2 gas release. - Press button EXTPB to emergency Push Button. - Shut Down All Breakers in Series. - At end of all mentioned tests power supply from generator switched OFF, DG stopped and substation shelter doors closed.