2" 1" W.G. Static Pos. or Neg.

SHOP STANDARDS DUCT CONSTRUCTION TABLE (FOR GALVANIZED & 304 S.S. & 316 S.S. DUCTWORK) (NOT FOR ALUMINUM)

DUCT SIZE 0" - 12" 13" - 30" 31" - 54" 55" - 84" 85" & above Plenum

DUCT GAUGE 26 24 22 20 18 18

JOINT LENGTH 59" 59" 56" 56" 56" 56"

WIDE SIDE CONNECTOR Flat Slip T-6 24 GA Standing Slip T-11 26 GA T.D.C. T-25a T.D.C. T-25a T.D.C. w/C.T.R. & J.T.R. T-25a T.D.C. w/C.T.R. & J.T.R. T-25a

NARROW SIDE CONNECTOR Flat Drive T-1 24 GA Flat Drive T-1 24 GA T.D.C. T-25a T.D.C. T-25a T.D.C. w/C.T.R. & J.T.R. T-25a T.D.C. w/C.T.R. & J.T.R. T-25a

SPECIAL NOTES Ref. 1 Ref. 1 Ref. 1 Ref. 1 Ref. 2 Ref. 1

NOTES: J.T.R. - JOINT TIE ROD C.T.R. - CENTER TIE ROD TIE RODS ARE 1/2" EMT If MPT (Mid-point Tie Rods) are used, the reinforement spacing is based on 2 1/2" References:
1. SMACNA-HVAC Duct Construction Standards Metal and Flexible, Second Edition 1995, page 1-20, Table 1.4 2. SMACNA-HVAC Duct Construction Standards Metal and Flexible, Second Edition 1997, Addendum 1, page 1-41.6 Table 1-45

2519 Monroe Drive; Gainesville, GA 30507 Phone: 770-532-9130. Fax: 770-287-1870