You are on page 1of 4

Merritt 7 Bldg 501

Norwalk, CT
www.flowtechinc.com

VFD PM Checklist / Worksheet


Equipment TAG

AC-3

DATE

VFD Manufacturer

ABB

Location

BLDG 501

ACH550UH125A4

VFD S/N

2093302922

VFD Model
Bypass Model
VFD SW/FW

D-Tech
313D Hex

Bypass S/N
Dwg 40E-4-CB-HO-L1-SF-N12-PLT

Run Time since Last PM (hrs)


Fault History:

Total Operating Time (hrs)

Motor Data:
HP: 100
V: 460
Motor Mfg / Model: Couldn't access motor
Confirm Motor Pgm:

12/14/13

I: 122

VFD Rotation:

0
RPM: 1780

VFD Fuses: Bussmann 170M1370

16.28KH

SF: 1.15

PF:

Bypass Rotation:

Main Fuses: NA

VFD O.L. Config: 700sec/110%


VFD I-Limit Setting: 174.6
Bypass O.L. Config: FURNAS OL PART#48JA38AA4 heaters:E102
VFD U.V. Config: Enabled

VFD Freq Limits:

System Check

12

TO

System Check`

/ Data

60

Hz

/ Data

Set / Confirm VFD Date/Time

NA

Check Cooling Fan Operation

Back-up Parameters to Panel

Record Fan Capacitor Rating

NA

16C

Record Fan Capacitor Actual

NA

Ambient Temp
VFD Temp at Check-out (Display)

55.1C

Motor / Wire Insulation Check

IR Scan of VFD / Panel

Check Speed Control Signal

Inspect / Tighten all Elec. Conn.

Check Other I/O Signals

Clean VFD & Bypass Panel

Perform Static Diode / IGBT Test

Check all Panel Indicator Lamps

Reset VFD Fault History

DYNAMIC SYSTEM POWER CHECKS

OPERATING SPEED

51

Hz

Input Voltage A-B:

478

Vac

B-C:

479

Vac

C-A:

476

Vac

Output Voltage A-B:

383

Vac

B-C:

383

Vac

C-A:

383

Vac

B:

53

Amps

C:

52

Amps

B:

78

Amps

C:

77

Amps

77

Amps

AC Level:

15

Vac

631

Vdc

Input Current

A:

Output Current

A:

DC Bus Voltage

55.7 Amps
78

DC Level:

Amps
624

Vdc

VFD: AC-3

Display
391

Vac

Display

STATIC SYSTEM VOLTAGE CHECKS

OPERATING SPEED

DC Bus Voltage

DC Level:

673

Vdc

AC Level:

>1

Vac

+10vdc VFD Supply

DC Level:

10

Vdc

AC Level:

20

mVac

+24vdc VFD Supply

DC Level:

25

Vdc

AC Level:

14

mVac

AC Level:

127

Vac

Control TX Voltage
+7vdc E-Bypass V

DC Level:

NA

Vdc

AC Level:

NA

mVac

+24vdc E-Bypass V

DC Level:

NA

Vdc

AC Level:

NA

mVac

VFD: AC-3

Hz
677

VFD PM COMMENTS
VFD started up 4/7/2001
Cleaned exhaust cabinet filters and installed

VFD: AC-3

VFD: AC-3

You might also like