You are on page 1of 1

Ceilcote Technical Bulletin

CEILCOTE CORROSION CONTROL PRODUCTS TECHNICAL BULLETIN #CC9 HINGE JOINT DETAIL FOR CONCRETE FLOOR & WALL JUNCTION

1. 2.

Abrasive blast joint and concrete surface, approximately 6-10" on vertical and horizontal side. Prime area, which will receive the CEILCOTE EJ-4 expansion joint material (4-6" on each side of the crack) with CEILCOTE 380 PRIMER @ 2-5 mils (WFT) for polyester or vinyl ester systems. Use CEILCOTE 680 Primer @2-5 mils (WFT) for epoxy systems. Mix per data sheet instructions. Allow to cure. Repair rough areas with primer and S-1 or S-11 powder, depending on size of repair. Apply CEILCOTE EJ-4 with a trowel at 40-120 mils, 4-6" on either side of crack. Allow to cure. Layout and saturate fiberglass mat (1 1/2oz.). Use CEILCOTE 680 Primer for epoxy and CEILCOTE CeilLine saturant or CEILCOTE 380 Primer for polyester or vinyl ester systems. Be sure to overlap on both sides of the CEILCOTE CeilLine Basecoat at least 3-4 inches. While layer of mat is still wet, repeat with a second layer of 1 1/2-oz. mat. Remove entrapped air with a ribbed roller. No white spots should be obvious on fiberglass. Allow to cure. After curing (generally the next day), grind off any imperfections or protrusions and feather edges. Proceed with normal installation or repair procedure of product. For heavy splash & spill or immersion conditions with the use of coating systems, two coats may be required. Contact Ceilcote. This is designed to handle approximately 1/16 1/8 inch crack movement.

3. 4. 5.

6.

7. 8. 9.

10.

Protective Coatings
All products supplied and technical advice or recommendations given are subject to our standard Conditions of Sale.