Display Buttons
I U-V PQS E PF F
PHASE U PQS Ph
DMD V DMD Qh
PEAK
Sh
E DMD
DMD PASSW
Setup CT Ratio:
1. In SETUP mode, press uuntil METER is visible 2. Press METER. 3. Press CT. 4. Enter the SCALE value: x1, x10, x100. No CT (for direct connect). 5. Press OK 6. Enter the PRIM (primary CT) number. 7. Press OK 8. Enter the SEC. (secondary CT) number. 9. Press OK to return to the METER SETUP screen. 10. Press to return to the SETUP MODE screen.
Setup PT Ratio:
1. In SETUP mode, press uuntil METER is visible 2. Press METER. 3. Press PT. 4. Enter the SCALE value: x1, x10, x100. No PT (for direct connect). 5. Press OK 6. Enter the PRIM (primary CT) number. 7. Press OK 8. Enter the SEC. (secondary CT) number. 9. Press OK to return to the METER SETUP screen. 10. Press to return to the SETUP MODE screen.
Schneider Electric - North America 295 Tech Park Drive LaVergne, TN 37086 Ph: 866-466-7627 PowerLogic.com Document#3000DB0806 April 2008 04-2008