You are on page 1of 2

208VAC

WYE(Y)
L1
OPTION A THREE 240VAC SPLIT PHASE, 2 WIRE SOURCES
A B
C
N
GND
COMMANDER AC INPUT
CB*
*DOUBLE POLE CIRCUIT BREAKER: 40AMP FOR A-L1/A-L2
30 AMP EACH FOR B-L1/B-L2 & C-L1/C-L2 INPUTS
CB*
CB*
COMMANDER AC INPUT WIRING OPTIONS
SIZE DRAWING NO.
DATE
DRAWN
APPROVALS
CHECKED
ENGR.
SCALE
REV.
2911 W. GARRY AVE. SANTA ANA, CA. 92704
TEL 714-751-0488 FAX 714-957-1621
B
SHEET 1 OF 2
R. Cortes 19JUL2012
NA B 15656-0
AC INPUT WIRING OPTIONS,
COMMANDER
PE C-L2 B-L2 A-L2 C-L1 B-L1 A-L1
CB*
L2
CB*
CB*
GND
COMMANDER AC INPUT
PE
OPTION B 208VAC 3 PHASE, 3 WIRE SOURCE
NOT
USED
208V
208V 208V
*DOUBLE POLE CIRCUIT BREAKER:

40AMP FOR A-L1/A-L2
30 AMP EACH FOR B-L1/B-L2 & C-L1/C-L2
INPUTS
Note: AC wiring should only be performed by qualified electrician or technician familiar with
ac wiring practices and local electrical code.
APPROVED DESCRIPTION
REVISIONS
REV DATE
INITIAL RELEASE 0 19JUL2012 RC
UPDATED OPTION A CONFIGURATION A 20SEPT2012 RC
240VAC DISTRIBUTION PANEL
C-L2 B-L2 A-L2 C-L1 B-L1 A-L1
COMMANDER SHELF (FRONT)
COMMANDER AC INPUT WIRING OPTIONS
SIZE DRAWING NO.
DATE
DRAWN
APPROVALS
CHECKED
ENGR.
SCALE
REV.
2911 W. GARRY AVE. SANTA ANA, CA. 92704
TEL 714-751-0488 FAX 714-957-1621
B
R. Cortes 19JUL2012
NA 15656-0
AC INPUT WIRING OPTIONS,
COMMANDER
SIZE DRAWING NO.
DATE
DRAWN
APPROVALS
CHECKED
ENGR.
SCALE
REV.
2911 W. GARRY AVE. SANTA ANA, CA. 92704
TEL 714-751-0488 FAX 714-957-1621
B
SHEET 2 OF 2
R. Cortes 19JUL2012
NA B 15656-0
AC INPUT WIRING OPTIONS,
COMMANDER
SM-36 1 2 3
5 6 7 4
DISTRIBUTION
2KW RECTIFIER CURRENT DRAW:
@208VAC = 10.8 A
@230VAC = 9.8 A
RECTIFIER BAY LOCATION
EACH PAIR OF AC INPUT TERMINALS (L1/L2) FEED TWO OR THREE RECTIFIER BAYS
A-L1/A-L2: BAY # 1, 4 & 7
B-L1/B-L2: BAY # 2 & 5
C-L1/C-L2: BAY # 3 & 6