Brief Introduction for Automated Relay
Testing
Kamin Dave
Manager Marketing & Protection Applications
DOBLE ENGINEERING COMPANY, INDIA
kdave@doble.com
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Protection Relay Testing:
Testing of Generator Protection
Relay type SEL300G
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Under & Over Voltage Protection (27/59)
Negative sequence Protection (46)
Reverse & Low Forward Power Protection (32)
Over Excitation Protection (24)
Over & Under Freq. Protection (81O/81U)
Under Impedance Protection (21)
Loss of Excitation Protection (40G)
100% Stator E/F Protection (27TN/64G2)
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Out of Step Protection (78)
Voltage Restrained O/C Protection (51VR)
Voltage Controlled O/C Protection (51VC)
Rotor E/F Protection (64R)
Breaker Failure Protection
Generator Differential Protection (87D)
Ground differential Protection (87N)
95% Stator E/F Protection (59GN/64G1)
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Primary & Backup Protection
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Rotor Earth Fault Protection
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Characteristic plotted in F6TEST2.21 software for testing
Load Encroachment
characteristic plotted
Zone2 Reach
Zone1 Reach
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Select D from List
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
GCB Status Close Input
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Breaker close input & VT fuse fail input
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
VT fuse fail Status Input
Characteristic selection
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
V/Hz Curve1
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
V/Hz Curve2
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
V/Hz Curve3
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Selection of Curve
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Set as a Low Forward
Power threshold
range
Set as a Reverse
Power threshold
range
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Set as Reverse Power function
VT Fuse fail Input
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Relay Logic for Reverse Power Function
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
VT fuse fail Status Input
Offset reactance for Zone1
Zone1
Zone2
Offset reactance for Zone2
Directional Angle for Zone2
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Directional Angle for Zone2
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Relay Logic for Loss of Excitation Function
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Enter Setting of NPS Threshold
Enter Time Dial Setting
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Relay Logic for Negative Sequence current Function
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Select function V
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Threshold value
Curve selection C1
VT fuse fail status input
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
K = 0.25
Normal
Inverse
Curve
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Select function C
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Threshold value
Curve selection C1
VT fuse fail status input
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
K = 0.2
Normal Inverse Curve
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
0-95% SEF
100% SEF
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Relay Details: SEL300G
Under Freq. function
Under Freq. function
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Test Equipment
Make : DOBLE
Model : F6150
Software
F6TesT Version 2.21-1165
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
F6150 Connections:
CT Connections
PT Connections
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
SEL300 Connections:
PT Connections CT Connections
Connections
of 4
th
Voltage
for 100% SEF
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Testing of Over Excitation Function (24)
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
VA
VB
VC
I1
I2
I3
SEL
Test Circuit: Over Excitation Function Test
Source Configurations:
3V X 3I
CT Inputs
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Inverse Time Curve Test
Tests conducted:
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Use VFChar Module for
Characteristic Search Test
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Curve3 selection
Enter Time Dial
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Curve3 for Testing
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Expected Curve
Actual Curve from relay
Phasor
Select ABC Fault for testing
Relay settings:
V/Hz = 1PU
Curve = 3
Time Dial = 1
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Testing of Reverse Power Function (32)
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R): Example1
G
D Y
GT
GCB
Gen Set
G
D Y
GT
GCB
Gen Set
CB1
CB2
CB3
CB4
C
B
5
TL Line
TL Line
MW
MW
Healthy Prime-mover
Failed Prime-mover
MVAR
MVAR
E
E
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R): Example2
G
D Y
GT
GCB
Gen Set
G
D Y
GT
GCB
Gen Set
CB1
CB2
CB3
CB4
C
B
5
TL Line
TL Line
MW
MW
Healthy Prime-mover
Failed Prime-mover
MVAR
MVAR
E
E
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R): Example3
G
D Y
GT
GCB
Gen Set
CB1 CB3
C
B
5
TL Line
MW
Failed Prime-mover
MVAR
E
Active Power Import from Grid sources
Grid
Grid
MW
MW
MW
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Reverse Power Protection (32R): Example4
G
D Y
TR1
GCB
Gen Set
Failed Prime-mover
MVAR
E
Only Reactive Power Export to Loads
CB1 CB2
D Y
TR2
CB3 CB4
M
C
B
5
CB6
L
o
a
d
s
L
o
a
d
s
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
VA
VB
VC
I1
I2
I3
SEL
Test Circuit: Reverse Power Function Test
Source Configurations:
3V X 3I
CT Inputs
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Pickup Test
Time Test
Tests conducted:
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Use RAMP Module for Pickup Test
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Pickup Test @ Unity PF:
MW - MW
- MVAR
MVAR
Watts = VA = 952.87W
- MVAR
MVAR
MW - MW
I
Expected = 1A
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Pickup Test @ Unity PF:
Vn = 110V
In = 5A
PF = 1 (Unity)
P
N
= (1.7325*0.11*1000*5) = 952.87watts
%P
Set
= 20% of P
N
P
Set
= (952.87 * 20)/(PF*100) = 190.5watts
I
Expected
= (190.5)/(1.7325*0.11*1000*PF) = 1A
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Enter Expected Value = 1A
Enter Action
details
Pickup
Actual Operating Values
IA@180
o
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Pickup Test @ 0.8 lag PF:
MW
- MW
- MVAR
MVAR
Watts = 762.3W
- MVAR
MVAR
MW - MW
I
Expected = 1.15A
V
A

=

9
5
2
.
8
7
V
A

Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Enter Expected Value = 1.15A
Enter Action
details
Pickup
Actual Operating Values
IA@150
o
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Pickup Test @ 0.8 lead PF:
MW
- MW
- MVAR
MVAR
Watts = 762.3W
- MVAR
MVAR
MW - MW
I
Expected = 1.15A
V
A

=

9
5
2
.
8
7
V
A

Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Enter Expected Value = 1.15A
Enter Action
details
Pickup
Actual Operating Values
IA@210
o
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Use SSIMUL Module for Time Test
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
T
Exp
= 200ms
T
Act
= 262ms
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Testing of Loss of Excitation Function (40G)
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
VA
VB
VC
IA
IB
IC
SEL
Test Circuit: Field Failure Function Test
Source Configurations:
3V & 3I
3V
3I
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Characteristic Search
Test
Characteristic Time Test
RCA (MTA) Test
Tests conducted:
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Use ZChar Module for Characteristic
Search Test
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Zone1 setting = 20.4Ohms
Zone2 setting = 30.5Ohms
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Show Phasors: fault voltage & current of ABC fault
Blue color shows expected
characteristic and pink color
shows actual tested
characteristic
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Click on Oscillograph: Shows, voltage & current waveform of ABC fault
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Zone1 setting = 20.4Ohms
Zone2 setting = 30.5Ohms
Offset = -3.5 Ohms
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Show Phasors: fault voltage & current of ABC fault
Blue color shows expected
characteristic and pink color
shows actual tested
characteristic
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Use ZTime Module for Characteristic
Time Test
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Show Phasors: fault voltage & current of ABC fault
Results Table shows; Zone1 time is 0.1s & Zone2 time is 0.4s
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
SEL300G: Field Failure Function Testing
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
SEL300G: Field Failure Function Testing
LED Indicator operated
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Use ZMTA Module for Characteristic
MTA (RCA) Test
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Fault type ABC selected for testing
Angle Boundary (Theta1)
Angle Boundary (Theta2)
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
SEL300G: Field Failure Function Testing
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Testing of Negative Sequence Function (46)
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Negative Sequence Protection (46)
Ia
Ic
Ib
Ia
Ic
Ib
Ia
Ic
Ib
+VE Seq. -VE Seq. Zero Seq.
Sequence Components
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
G
D Y
GT
GCB
Gen Set
MW
MVAR
E
3
46
Operate:
I2
Measure
>I2
Set
Sys
MVAR
MW
F1
Negative Sequence Protection (46)
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
G
D Y
GT
GCB
Gen Set
3
46
Operate:
I2
Measure
>I2
Set
F1
Negative Sequence Protection (46)
3
3
I
R
@ 0
o
I
Y
@ 120
O
I
B
@ 240
O
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
I1@0
o
I2@120
o
I3@240
o
SEL
Test Circuit: Negative Phase Seq.
Function Testing
Source Configurations:
3I
3I
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Inverse Time Curve Test
Tests conducted:
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Use IChar Module for Characteristic
Search Test
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Curve selection
Enter Time Dial
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Inverse Curve for Testing
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Blue color line shows Expected curve &
Pink color line shows Actual tested curve
Phasors shows symmetrical components
value (i.e. I1, I0 & I2)
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Testing of Voltage Controlled Over Current
Function (51VC)
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Voltage Controlled over current function (51VC):
Normally Protection applied for Directly connected
Generators where system voltage collapse drastically
falls below set value (V
Set
) during faults.
Voltage Dependent Over Current Protection (51V)
G
GCB
D Y
3
51VC Y Y
CB1 3
51
D Y
CB2
3
51
CB2 3
Motpro
M
VT
F1
F2
6.37 MVA
11KV
PF = 0.8, Xd=36.4%, Xd=26%
Xd = 231%
1.5MVA, 11KV/0.415KV, %Z = 4.9%
1.5MVA, 11KV/0.415KV, %Z = 4.9%
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
V/Vs
I*/ [I>]
0.2 0.8
0.2
1.0
51V-Voltage Controlled
V
measured
< V
set
I
pickup
= (k*I
set
)
T = (0.14*T) / ((I
pickup
)
0.02
-1)
V
measured
> V
set
I
pickup
= (I
set
)
T = (0.14*T) / ((I
pickup
)
0.02
-1)
Voltage Dependent Over Current Protection (51V)
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
VA
VB
VC
IA
IB
IC
SEL
Test Circuit: Voltage Controlled O/C
Function Testing
Source Configurations:
3V & 3I
3V
3I
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Inverse Time Curve Test
Tests conducted:
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Use IChar Module for Characteristic
Search Test
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Curve selection
Enter Time Dial
Relay Settings:
I> = 0.5*In
Curve = C1
Time Dial = 1
V1 = 50V
L-N
V2 = 25V
L-N
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Characteristic created
for testing
Relay Settings:
I> = 0.5*In
Curve = C1
Time Dial = 1
V1 = 50V
L-N
V2 = 25V
L-N
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Injected Voltage to relay
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Display Phasors
Blue color shows expected
characteristic and pink color
shows actual tested
characteristic
Right click on check box to enable voltage O/P
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Testing of Voltage Restrained Over
Current Function (51VR)
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Voltage Restrained over current function (51VR):
Normally Protection is applicable when Generator is
connected to system through GT.
Voltage Dependent Over Current Protection (51V)
G
GCB
3
51VC Y Y
VT
D Y
D Y
CB1 3
51
D Y
CB2
3
51
CB2 3
Motpro
M
F1
F2
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
VA
VB
VC
IA
IB
IC
SEL
Test Circuit: Voltage Restrained O/C
Function Testing
Source Configurations:
3V & 3I
3V
3I
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
V/Vs
I*/ [I>]
0.2 0.8
0.2
1.0
51V-Voltage restrained V
measured
> V
set2
I
pickup
= (I
set
)
V
measured
< V
set1
I
pickup
= (k*I
set
)
V
set1
< V
measured
< V
set2
S
l
o
p
e

r
e
g
i
o
n
Voltage Dependent Over Current Protection (51V)
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Inverse Time Curve Test
Tests conducted:
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Use IChar Module for Characteristic
Search Test
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Curve selection
Enter Time Dial
Relay Settings:
I> = 1*In
Curve = C1
Time Dial = 1
V1 = 50V
L-N
V2 = 25V
L-N
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Characteristic created
for testing
Relay Settings:
I> = 1*In
Curve = C1
Time Dial = 1
V1 = 50V
L-N
V2 = 25V
L-N
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Injected Voltage to relay
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Display Phasors
Blue color shows expected
characteristic and pink color
shows actual tested
characteristic
Right click on check box to enable voltage O/P
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Testing of 0-95% Stator Earth Fault
Function (64R1/59GN)
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Resistor Ground
Maximum Ground Fault Amps = (Line to Neutral Voltage)
-------------------------------------
(NGR Resistance)
V
LN
= 21000/1.7325
100 Ohms, 10s
I
F
I
F PTR = 21000/240V
CTR = 20/1A
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (59GN):
Impedance Ground (NGT)
V
LN
= 21000/1.7325
KVPri = 21kV
KVSec = 0.240kV
KVA = 70KVA
R = 0.913 Ohms
Full Load current in Primary wdg = 3.33A
Ground Fault Impedance = 3640.004 Ohms
I
F
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
VA
VB
VC
VN
SEL
Test Circuit: 0-95% SEF Function Testing
Source Configurations:
4V
3V
4
th
V@50Hz
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Pickup Test
Time Test
Tests conducted:
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Use RAMP Module for Pickup Test
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
4
th
Voltage used
Expected value = 5V
Actual value = 5.3V
Pickup Value = 5V
Action details for Voltage Ramp
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Use SSIMUL Module for Time Test
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Ground Fault condition
Display Phasor
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Ground Fault condition
Display Waveforms (Analogue & Digital Channels)
4
th
Voltage
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Actual trip time = 1s
Relay Output (Open to Close contact)
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Testing of 100% Stator Earth Fault
Function (64R2/27TN)
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (27TN)
3
rd
Harmonic
Current circulate
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Stator Ground Fault Protection (27TN): 3
RD
Harmonic Under Voltage Method
3
rd
Harmonic
Under voltage relay
3
rd
Harmonic
Voltage at Neutral End reduced
3
rd
Harmonic
Voltage at Neutral End reduced
I
F
3
rd
harmonic
voltage drop
Because capacitance
Is shorted
I
F
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
VA
VB
VC
VN
SEL
Test Circuit: 100% SEF Function Test
Source Configurations:
4V
3V
4
th
V@150Hz
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Pickup Test
Time Test
Tests conducted:
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Use RAMP Module for Pickup Test
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
4
th
Voltage used @ 150Hz Freq.
Expected value = 1V
Actual value = 1.2V
Pickup Value = 1.2V
Action details for Voltage Ramp
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Use SSIMUL Module for Time Test
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Ground Fault condition close to Neutral
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Actual trip time = 0.55s
Relay Output (Open to Close contact)
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
SEL300G: 100%SEF Function Testing
LED Indicator operated
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Testing of Under Frequency Function
(81UF)
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
VA
VB
VC
IA
IB
IC
SEL
Test Circuit: Under Freq. Function Test
Source Configurations:
3V & 3I
3V
3I
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Pickup Test
Time Test
Tests conducted:
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Use RAMP Module for Pickup Test
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Freq. of Voltage sources
Expected value = 48.5Hz
Actual value = 48.498Hz
Pickup Value = 48.5Hz
Action details for Freq. Ramp
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Use SSIMUL Module for Time Test
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Under Frequency condition (48Hz Freq. for Voltage sources)
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Actual trip time = 0.33s
Relay Output (Open to Close contact)
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Testing of Over Frequency Function
(81O/F)
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
VA
VB
VC
IA
IB
IC
SEL
Test Circuit: Over Freq. Function Test
Source Configurations:
3V & 3I
3V
3I
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Pickup Test
Time Test
Tests conducted:
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Use RAMP Module for Pickup Test
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Freq. of Voltage sources
Expected value = 51Hz
Actual value = 51.0002Hz
Pickup Value = 51.0002Hz
Action details for Freq. Ramp
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Use SSIMUL Module for Time Test
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Over Frequency condition (51Hz Freq. of Voltage sources)
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Actual trip time = 93.9ms
Relay Output (Open to Close contact)
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
SEL300G: 100%SEF Function Testing
LED Indicator operated
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
Training to L&T Power at Doble Training Center
Knowledge Is Power
SM
Apparatus Maintenance and Power Management
for Energy Delivery
DOBLE ENGINEERING COMPANY
2
nd
Floor Suvidhi Pride,
Gorwa-Refinery Road
Opposite Shell Petrol Pump
VADODARA
INDIA. Cell:- +91 98980 55956
EMAIL ID:- kdave@doble.com
Website:- www.doble.com

You might also like