Protection Scheme Requirements
Dependability

Distribution Protection Transmission


Scheme

Reliability
Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
IEEE/CIGRE Recommendations

 Integrity test
 Application test

IEEE

Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
Integrity Test

Confirm relay meets


manufacturer’s published
specifications.

Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
Integrity Test
 In service Periodic testing
 Mfg. recommended Routine test
 Operating history of Relay type
 Complexity and criticality of protected circuit
 Maintenance schedule

Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
Integrity Test

Determine if the
performance of the relay is
satisfactory for the
intended application.

Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
Application Test
 Type testing
 Relay selection
 Commissioning/System testing
 Operation analysis
 CT saturation and CVT transients
 Load flow and system condition
 Evolving fault, fault with high arc or ground
resistance

Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
Test Methods
 Steady state
 Dynamic state test
 60/50 Hz Dynamic testing
 Transient testing
 End to End satellite synchronized testing

Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
Steady State Test

Apply phasors to
determine relay settings
by slowly varying the relay
input.

Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
Steady State Testing
 Integrity test
 Traditional tests
 Slow changing of phasors
 Individual control of phasors
 Reach accuracy, PU/DO test
 Does not simulate power system conditions

Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
Steady State Testing: Phasors

VC

VA

I
A
VB
Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
Steady State Characteristic

Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
Steady State Test : Assumptions

 Distance relay reach test


 Radial line
 No load condition
 No fault resistance
 Homogeneous system
 Source impedance Line
Impedance

Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
Steady State Test: Limitations
 Relay is alive and working
 Test results are for reference only
 Important circuits are not tested
 Polarizing circuit
 Memory circuit
 Effect of load

Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
Steady State Test: Advantages

 Simple
 Test results tracking
 Drift in setting
 Component failure
 Computerized testing gains productivity

Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
PRODUCTIVITY GAINS
Testing Automation
to gain productivity
250 240

200
Minutes
150
Manual
90 100
100 Auto
75

50 30
12
0
MBCH KCEG SPAJ

Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
Meaningful Testing

 Test relays under power system conditions


 Check complete scheme not only
individual components/relays
 Tests complete protection schemes along
with pilot channels if possible

Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
Dynamic
Protection Scheme
Testing

Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
. . . testing under
Power System
Conditions

Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
Dynamic State Test

Simultaneously apply
fundamental frequency
component of voltage and
current that represent
power power system
states.

Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
Scheme Tests: Digital Protection

AR

21/79/25

XMTR
RCVR

Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
Dynamic State Testing
 Synchronous Phasor switching
 Closely approximates power system events
 Relay response check for
 Evolving fault
 Current reversal
 Actual operating time
 Polarizing and memory circuit check

Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
Dynamic State Testing

Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
Dynamic State Testing

Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
Dynamic Mho Characteristic
Z set
Z

ZS
Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
Power Requirements

Protection Scheme
Testing

Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
Scheme Test: Ph-G Fault

EC 50 FD 21
EA
EB

Test Equipment 67N

Total impedance for Ph-G fault = 2.508 Ohms


Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
Scheme Test: Ph-G Fault

EC 50 FD 21
EA
EB

Test Equipment 67N


Total Burden VA for 5*In VA for 10*In
Ph - G FLT 2.508 63 251
Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
Transient Tests

Simultaneously apply
fundamental and non
fundamental frequency
component of voltage and
current that represent
power system Event.

Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
Transient Testing
 Simulates power system conditions
 Plays waveform coefficient
 Point by point control
 Fault inception angle control
 DC coupled amplifiers to play transients in
to the relay

Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
Transient Testing

 Evaluating relay performance under


actual power system conditions
 Analysis of questionable relay
operation
 Testing relays of special
characteristics

Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
Transient Testing: Data Sources

DFR EMTP / ATP


Files Files

RS 232
TransWin
Ethernet

Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
End to End Testing
 Ultimate testing tool
 Evaluates complete relay and associated
equipment performance
 POTT scheme : Relay and communication
equipment
 Co-ordination between two end of relaying
scheme
 Current reversal
 Evolving fault

Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
End to End Testing
 Commissioning test
 Diagnostic tool
 Requires satellite synchronization
 Requires high power for checking complete
scheme
 Primary and backup relaying
 High fault current events
 Mixed scheme e.g. Digital and E/M relays

Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
End to End Testing

Comm Channel

Protection
under test

Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
End to End Testing
 Alternate to costly stage fault testing
 Must for critical lines
 Ensures proper operation of the complete
relaying scheme

Knowledge Is Power SM

Apparatus Maintenance and Power Management


for Energy Delivery
Present Trends

 Availability of Power System Simulators at


affordable price
 Downsizing
 Deregulation of power industry
 Meaningful testing of the protection scheme