You are on page 1of 32

APPLICATION GUIDE

This application guide is intended to illustrate the extensive range of application and schemes to which our products and systems can be
applied. For ease of use typical schemes have been provided to cover the standard voltage ranges.

Our company specialises in customised applications and we have a dedicated team of senior applications engineers who can provide
solutions for any voltage in the power system network.

The voltage levels indicated in this guide are as follows:-

i) LV typically less than 1kV


ii) MV typically 1kV to 132kV – Distribution
iii) HV typically 132kV and above – Transmission

Busbar Protection

Some general considerations to be taken into account when establishing the optimum protection

• Busbar configuration
• Cost
• Protection redundancy requirements
• Phase/earth fault scheme or phase/earth and phase/phase scheme
• Speed and sensitivity
• Existing c.t. characteristic for retrofit projects

Overcurrent protection - blocking principle, distribution networks, single source.

APPLICATION
GUIDE

ANSI No Function Reyrolle Relay

51 Three-phase time delayed overcurrent Argus 1 – (3P+E)


51N Time delayed earth fault AG1-(411-412)
50CBF Circuit breaker fail
S1 Blocking signal status input
51 Three-phase time delay overcurrent Argus 1 – (3P+E)
51N Time delay earth fault AG1-(411-412))
50CBF Circuit breaker fail
BS Blocking signal output (e.g low set o/c e.f)
1
Directional overcurrent protection - Blocking principle, distribution networks, parallel source

ANSI No Function Reyrolle Relay

67 Bi-directional three-phase time delayed overcurrent Argus 2 – (3P+E)


67N Bi-directional time delayed earth fault AG2-(411-412)
50CBF Circuit breaker fail
SI Blocking signal status input
67 Directional three-phase time delayed overcurrent Argus 2 – (3P+E)
67N Directional time delayed earth fault AG2-(411-412)
50CBF Circuit breaker fail
BS Blocking signal output (eg low set o/c and e.f)
High impedance busbar differential protection - Single busbar, two zone, phase/phase & phase/earth fault scheme, with overall check zone

ANSI No Function Reyrolle Relay

87H-1 Differential using circulating current principle with CT supervision – main zone 1
87H-2 Differential using circulating current principle with CT supervision – main zone 2 DAD
87H-CH Differential using circulating current principle with CT supervision – check zone

3
High impedance busbar differential protection - Mesh corner, duplicate phase fault scheme with C.T supervision

ANSI No Function Reyrolle Relay

Differential using circulating current principle with


87H DAD
C.T supervision - Main 1

87H Differential using circulating current principle - Main 2 B3


ANSI Case Availability
Function Description Ref Modular Vedette Other

Busbar protection and circuit breaker fail schemes

Differential

Electronic high speed, high/medium impedance circulating current principle with excellent harmonic rejection, includes current
transformer supervision. 87 DAD
CT Shorting High speed multi-contact relay, hand reset contacts

86 TR221
Leakage to frame Attracted armature relay with a fixed current setting. Normally connected to a C.T. placed between the switchgear
frame and earth. A check system is possible

64N MR111
Busbar prot'n for distribution Blocking scheme using the feeder overcurrent and earth fault protection.

87 Argus
Interlocked overcurrent Relay for discriminative clearance of blind spot faults, actioned by a main protection contact (DTL)

51 2DAB
51 Argus
Circuit Breaker fail Electronic relay with phase segregated inputs and outputs. Internal interface system permits factory set output options of
up to 9 output contacts. Features a low overshoot and a particularly wide range of settings. Integrated timer.

50 2DAB
Intergrated in multi-function relay Argus
D.C. Supervision

Low burden attracted armature relays 27


Self reset reverse flag XR152
As above with hand reset flag XR153
Trip supply supervision incorporated in Argus multi function relay Argus
Trip High speed multi-contact hand reset trip relay

86 TR221
Time delay Range of electronic high accuracy time delay relays

2 DDB
Low impedance Numerical protection system providing percentage differential protection, differential protection and undervoltage monitoring.
High speed operation. Fully self supervised.

87 DRS-BB

5
Feeder Protection

Some general considerations to be taken into account when establishing the optimum protection:–

• Method of system earthing


• Type of load
• System requirements (eg fault clearance time)
• Existing protection
• Protection redundancy requirements
• Cost of protection relative to degree of security required

Cable feeders, radial or ring feed, high security.

ANSI No Function Reyrolle Relay

51 Three-phase time delayed overcurrent Argus 1 – (3P+E)


51N Time delayed earth fault AG1 -(401-402)
87F Pilot wire differential Solkor Rf

Note: Pilotwire supervision, intertripping and guard relays can be added to Solkor-Rf scheme as required.
Alternatively Solkor-N may be used with fibre optic or RS485 communication link, or Solkor-M for 4-wire VF circuit.
Cable feeder, ring main

ANSI No Function Reyrolle Relay

51 Three-phase time delay overcurrent Argus 1 – (3P+E)


51N Time delayed earth fault AG1-(401-402)
67 Bi-Directional three-phase time delayed overcurrent Argus 2 – (3P+E)
67N Bi-Directional time delayed earth fault AG2-(411-430)

Note: Argus 2 relays have independent settings for forward and reverse directions. Where distances permit blocking connections can
be added.

7
Overhead line feeder with auto-reclosing circuit breaker

ANSI No Function Reyrolle Relay

51 Three-phase time delayed & instantaneous overcurrent


Argus 4 – (3P+E)
51N Time delayed & instantaneous earth fault
AG4-(401-404)
79 Auto reclose
Overhead line feeder with single main protection, high security

Communication Channel-CCITT M1020


Standard 4 wire voice frequency
(Option of digital interface)

ANSI No Function Reyrolle Relay

51 Three-phase time delayed overcurrent Argus 1 – (3P+E)


51N Time delayed earth fault AG1-(401-402)
87CD Current differential Solkor M
SK2-(101-203)

9
Overhead line feeder with duplicate main protection

Communication Channel-CCITT M1020


Standard 4 wire voice frequency
(Option of digital interface)
Ohmega communications channel is optional

ANSI No Function Reyrolle Relay

51 Three-phase time delayed overcurrent Argus 1 – (3P+E)


51N Time delayed earth fault AG1 – (401-402)
87CD Phase comparison current differential Microphase-FM
MF1 - (101-203)
21 Distance protection scheme Ohmega
79 Autoreclose
25 Check synchronising Argus 7
AG7-(101-102)
ANSI Case Availability
Function Description Ref Modular Vedette Other

Feeder protection

Distance Numeric full scheme distance protection relay with selectable functions for complete flexibility. Upto 4 zones of protection with
different operating times for distribution and transmission voltage applications. Additional features include logic programming,
waveform and event recording and remote communications.

21 Ohmega range

Numeric Current Differential Multi-microprocessor relays providing unit protection using software derived positive and negative phase
sequence components. V.T. not required. Manual or automatic delay compensation, continuous supervision of communications
link. Integral fault data storage.

87 Microphase-FM

Multi-microprocessor relays providing unit protection using the Solkor principle derived in software. V.T. not required. Manual or
automatic delay compensation, continuous supervision of communications link. Integral fault data storage.

87 Solkor-M

Numeric phase segregated differential protection for use with fibre optic or RS485 communication. Integrated supervision,
intertripping and guard functions

87 Solkor-N

Overcurrent and/or earth fault

Electro-mechanical relays: Instantaneous fixed setting 50/51 MR111


Instantaneous variable setting MR112

Numeric with selected DTL, NI, VI, EI, LTEF characteristics. Two integral highset functions, IDMT/DTL instantaneous or delayed
reset. Waveform storage of last 5 faults and time-tagged storage of 500 events. Ammeter display can be set to read primary
amps. Integral condition based circuit breaker maintenance data.
50/51/87 Delta 1
Ditto with bi-directional control of all measuring elements
67/67N/87 Delta 2

Integrated protection and auto reclose, three or four pole, with individual auto reclose sequence for the OC, EF and EF / SEF
functions. Optional integral directional control available.

50/51/87/67 Argus 4 / 6
Delta
Restricted earth fault

Electro-mechanical high impedance circulating current principle, setting increases


for harmonics and has a integral metrosil. 87 5B3

Numeric, with high harmonic rejection ratio. 87 Argus 1


Delta
Sensitive earth fault Numeric with excellent harmonic rejection and integral time delay.

50 Argus 1
Delta
Auto reclose Numeric for three pole autoreclose schemes. Multi-shot, integrated with IDMT and EF / SEF protection

79 Argus 4
Delta
Check synchronising Numeric with independent check & system sync settings

25 Argus 7
Overload Numeric thermal overload

49 Rho 3
Delta
Pilot wire Circulating current principle, high speed operation, 2000 ohms pilot loop. Up to 5kV or 15kV with isolating transformers, pilot
insulation levels.

87 Solkor-R / Rf
Pilot wire supervision Pilot supervision for Solkor-R (5kV) and Solkor-Rf pilot wire protection schemes

part of 85 Solkor supervision


Guard relay Instantaneous OC & EF

B69
Pilot wire intertrip

For use with Solkor-R installations where sufficient fault current will be present during the
11
intertrip operation. 50 5kV 5kV
AR101T AR101T
A.C. injection intertripping schemes to use Solkor-R or Solkor-Rf pilot wire link. Slightly different equipment is required for each -
state if Solkor-R or Rf. Not suitable for use with pilot supervision

TEC Inverter
ANSI Case Availability
Function Description Ref Modular Vedette Other

Intertripping 85 TEC

Intertrip send relay for pulse or continuous intertrip 5kV and 15 kV pilot insulation models

Surgeproof intertrip receive relay for up to 500 V rms across pilot cores GF3

Surgeproof intertrip relay for up to 5kV rms across pilot cores BD BD

Pilot supervision relay for intertrip pilots with 15kV insulation (uses the send
unit of Solkor supervision) 15kV CF2

Intertrip send relay complying with ESI 48-4 Class ESI XR101

Intertrip receive relay complying with ES141-15 Part 5 (1988) XR102


Interposing control For use over pilot wires of up to 200 ohms, and not susceptible to certain ac voltages

A) Without flag indication XR105 XR105


B) With flag indication XR106 XR106
Neutral displacement Numeric relay with variable settings and time delay 59

Argus 8
Undervoltage 27

Electro-mechanical: Fixed setting VR121/22


Adjustable setting VR123
Numeric Argus 8
Overvoltage 59

Electronic-mechanical: Fixed setting VR115/16


Adjustable setting VR117
Numeric Argus 8

Voltage monitoring

Electro mechanical suitable for Mesh Corner to NGC Specification B68


Fault detection indication Earth fault passage indication for cable circuits.

FIND
Motor Protection

Some general considerations to be taken into account when establishing the optimum protection:-

• Importance of the drive circuit (i.e. duty cycle)


• Cost (implications of downtime, motor rewind, etc)
• Operating environment
• Plant requirements
• Motor rating and cost

LV motor circuit controlled by a fuse-switch or contactor – motor rating typically up to 75kW

* Core balance c.t. recommended

ANSI No Function Reyrolle Relay


46 Negative phase sequence overcurrent
Rho 0
49 Three-phase thermal overload
RH0 – (101-108)
51N Time delayed earth fault LV

Motor controlled by a fuse-switch or contactor – ratings typically above 75kW

* Core balance c.t. recommended


13
ANSI No Function Reyrolle Relay
46 Negative phase sequence overcurrent
49 Three-phase thermal overload Rho 0
48 Locked rotor / stalling RH0 – (101-108)
51N Time delayed earth fault
Motor controlled by a circuit breaker – ratings typically above 75kW to 1MW asynchronous motor, direct on line start

* Core balance c.t. recommended

ANSI No Function Reyrolle Relay


46 Negative phase sequence overcurrent
49 Three-phase thermal overload Rho 3
48 Locked rotor / stalling RH3 – (101 –112)
50 Three-phase instantaneous overcurrent
50N Instantaneous earth fault

Motor / transformer circuit controlled by a circuit breaker, typically 500kW

* Core balance c.t. recommended

ANSI No Function Reyrolle Relay


46 Negative phase sequence overcurrent
49 Three-phase thermal overload
48 Locked rotor / stalling Rho 3
50 Three-phase instantaneous overcurrent RH3 – (101-112)
37 Undercurrent
30 Thermal pre-alarm
50N Instantaneous earth fault
51N Time delayed earth fault Argus 1 – (1P EF)
AG1 – (101-102)
Motor controlled by a circuit breaker – ratings typically above 1MW

* Core balance c.t. recommended

ANSI No Function Reyrolle Relay

46 Negative phase sequence overcurrent Rho 3


49 Three-phase thermal overload RH3 – (101-112)
48 Locked rotor / stalling
50 Three-phase instantaneous overcurrent
37 Undercurrent
30 Thermal pre-alarm
50N Instantaneous earth fault
87M Three-phase differential 3 X Argus 1 – (1P SEF)
AG1 – (103-104)#

# Employed as 3-phase high impedance differential

ANSI Case Availability


Function Description Ref Modular Vedette Other

Motor Protection

LV motor protection Integrated numeric LV motor protection with a large number of functions including thermal overload, earth fault, short
circuit and under/over voltage

44 Rho 0
46
48
49
50
27/59
HV motor protection Integrated numeric HV motor protection with a large number of functions including thermal overload, earth fault, short
circuit and stall protection

46 Rho 3
66
48
49
50
Over/undervoltage Numeric with programmable time delay

27/59 Argus 8

Differential High impedance principle

87 5B3
Argus 1
15
Generator Protection

Some general considerations to be taken into account when establishing the optimum protection:–

• Mode of operation (i.e single or parallel running)


• Type of duty (i.e base load, emergency supply, standby duty)
• Direct connected to a substation busbar or via generator transformer
• Method of system earthing
• Protection redundancy required
• Generator rating and cost

Direct connected generator, low impedance earthing, rating typically 2MW. Base load generation in parallel with grid network.

ANSI No Function Reyrolle Relay

27UV Undervoltage
81 Over / under frequency Gamma 4
59 Overvoltage GM4 - (401-412)
32R Reverse power
50N Instantaneous earth fault
51V Three-phase time delayed overcurrent with voltage restraint
81R Rate of change of frequency
60FL Voltage transformer supervision
51N Time delayed earth fault (neutral end) Argus 1 – (3P+E)
51 Three-phase time delayed overcurrent (line end) AG1 - (401-402)
51N Time delayed earth fault (line end)
Direct connected generator, high impedance earthing, rating typically 15MW. Base load generation in parallel with grid network.

ANSI No Function Reyrolle Relay

27UV Undervoltage
81 Over / under frequency
59 Overvoltage
40 Loss of field
46 Negative phase sequence overcurrent Gamma 4
87G Generator biased differential GM4-(201-212)
32R Reverse power
59N Stator earth fault (95% winding protected)
51V Three-phase time delayed overcurrent with voltage restraint
60FL Voltage transformer supervision
51 Three-phase time delayed overcurrent (line end) Argus 1 - 3P+E
51N Time delayed earth fault (line end) AG1-(401-402)

17
Isolated generator transformer, high impedance earthing, rating typically 50MW and above. Base load generation in parallel with grid network

ANSI No Function Reyrolle Relay

27UV Undervoltage
81 Over /underfrequency
59 Overvoltage
50/27 Inadvertent energising Gamma 4
50CBF Circuit breaker failure GM4 – (401-412)
24 Overexcitation V /Hz
46 Negative phase sequence overcurrent
40 Loss of field
87G Generator biased differential
32R Reverse power
21 Phase distance
60FL Voltage transformer supervision
59N Stator earth (95% of winding protected)
27TN Startor earth fault (100% of winding protected)
51 Three-phase time delayed overcurrent (line end) Argus 1 – (3P + E)
51N Time delay earth fault (line end) AG1 – (401-102)
87T Transformer biased differential
64REF Restricted earth fault Duobias M
WTA, WTT Winding temperature alarm and trip status inputs 2 Wdg, 50Hz
PT Pressure relief device trip status input
BG/BT Buchholz alarm and trip status inputs
ANSI Case Availability
Function Description Ref Modular Vedette Other

Generator Protection

Numeric generator Suitable for protection of a variety of machines down to 1MW this relay can be purchased as minimum protection base
system and built up with the addition of function modules into a more protection functionally comprehensive protection package.
Comprehensive generator protection system suitable for use on all machine sizes. Dual CT inputs in a standard 19” rack mounting
design.

Gamma 4 Range

Differential ( unit or transformer )

High impedance principle with voltage setting for generator or generator


transformer 87 5B3
Numeric current differential, features include data storage 87 Argus Duobias-M

Overcurrent & earth fault Numeric multi-function, multi-characteristic, including ammeter display, waveform storage, event recording, comms
link etc.

50/51 Argus 1
Delta

Restricted earth fault High impedance principle

50 5B3
Argus 1
Delta

Sensitive earth fault Numeric with wide setting ranges, excellent harmonic rejection and integral time delay

50 Argus 1
Delta

Over/undervoltage Numeric with programmable time delay

27 / 59 Argus 8

Neutral Displacement Numeric with 2 settings

Argus 8

Over/underfrequency Numeric with programmable time delay

81 Argus 8

19
Transformer Protection

Some general considerations to be taken into account when establishing the optimum protection:
• Mode of operation (i.e parallel or single operation)
• Method of system earthing
• Transformer rating and cost
• Importance of high-speed fault clearance
• HV and LV switching devices (i.e c.b, fuse switch, or isolator)

Transformer controlled by a fuse-switch or contactor, eg ratings up to 1MVA Transformer type – dry

ANSI No Function Reyrolle Relay

51 Three-phase time delayed overcurrent Argus 1 – (3P+E)


51N Time delayed earth fault HV AG1-(401-402)
51N Time delayed earth fault LV Argus 1 – (1P+EF)
AG-(101-102)
Transformer controlled by a circuit breaker, typically 800kVA to 2MVA. Transformer type – oil filled, sealed (with pressure sensor) or with
conservator.

ANSI No Function Reyrolle Relay

51 Three-phase time delayed overcurrent Argus 1 – (3P+E)


50 Three-phase instantaneous high-set overcurrent
51N Time delayed earth fault HV AG1-(411-412)
WTA, WTT Winding temperature alarm and trip status inputs
PT Pressure relief device trip status input
64REF Restricted earth fault LV Argus 1 –
51N Time delayed earth fault LV (2P+E+REF)

AG1-(403-404)

21
Two winding, transformer controlled by a circuit breaker, typically above 2MVA. Transformer type-oil filled with conservator.

ANSI No Function Reyrolle Relay

51 Three-phase time delayed overcurrent LV Argus 1 - (3P + 3)


51N Time delayed earth fault LV AG1 – (401-402)
51 Three phase time delayed overcurrent HV Argus 1 - (3P + E)
50 Three phase instantaneous high-set overcurrent HV AG1 – (401-402)
51N Time delayed earth fault HV
90 Automatic voltage control SuperTAPP/MicroTAPP
87BD Bias Differential Duobias M
WTA,WTT Winding temperature alarm and trip status inputs 2 Wdg
PT Pressure relief device trip status input
BG,BT Buchholz alarm and trip status inputs
64REF Restricted earth fault LV
25 Check & system synchronising Argus 7
Three winding transformer controlled by a circuit breaker, typically above 2MVA. Transformer type – oil filled with conservator

ANSI No Function Reyrolle Relay


51 Three-phase time delayed overcurrent LV1 Argus 1 – (3P + E)
51N Time delayed earth fault LV1 AG1 - (401-402)
51 Three-phase time delayed overcurrent LV2 Argus 1 – (3P + E)
51N Time delayed earth fault LV2 AG1 - (401-402)
51 Three-phase time delayed overcurrent HV Argus 1 – (3P + E)
50 Three-phase instantaneous high-set overcurrent HV AG1 - (401-402)
51N Time delayed earth fault HV
87BD Bias differential
64REF Restricted earth fault LV1
64 REF Restricted earth fault LV2 Duobias M
WTA, WTT Winding temperature alarm and trip status inputs 3 Wdg
PT Pressure relief device trip status input
BG, BT Buchholz alarm and trip status inputs

23
ANSI Case Availability
Function Description Ref Modular Vedette Other

Transformer protection

Differential Numeric current differential relay with integral current magnitude and vector compensation setting for 2 or 3 winding transformers.
Eliminates interposing CT's and flag relays for most applications. Protection functions are differential, differential highset, and
restricted earth fault for HV and LV: also has a data storage facility triggered internally or externally.

87 Duobias-M

Impedance

21 Ohmega
Overcurrent & earth fault Argus range of numeric relays with multiple independent characteristics, 2 highest & SEF or REF options, data
storage and event logging, comms link, ammeter displays and facilities to produce a condition based CB maintenance regime.
Single, three and four pole models

50/51 Argus 1

Overload Numeric Thermal Overload

49 Rho 3

Standby earth fault

For resistance earthed systems. Long time characteristic (form 30/5 51 Argus 1

Restricted earth fault

Electro-mechanical relay with low-pass filter circuit which increases the setting at harmonic
frequencies 87 5B3

Numeric relays using high impedance principle, with high harmonic rejection ratio. 87 Argus 1

Sensitive earth fault Numeric relay with wide setting ranges, low burden and adjustable time delay.

50 Argus 1

Transformer voltage control

Automatic voltage control

SuperTAPP solid state control relay of 4u height for mounting with modular relays. Incorporates the patented TAPP circuitry.
Requires the 19 rack frame, part RHW19R. 90 RVM/5

Tap change control and monitor unit, includes manual controls, tap position
indicator and voltage level monitor. For use in conjunction with the RVM/5 relay
both units fit into the 19 rack frame, part RHW19R, to make a single 4u rack tier. RTMU/1

SuperTAPP solid state relay designed as a direct replacement for AVE relays. RVM/4

Solid state tap position indicator with digital read-out designed to replace analogue
units which use a resistor chain for position sensing. RTPI/1

Tap position indicator, similar to that above, with intelligent runaway protection. RTPI/2

Numeric integrated tap change control and monitor unit MicroTAPP


ANSI Case Availability
Function Description Ref Modular Vedette Other

Control relays

Repeat relay

4 or 6 contact relay which can be provided with heavy duty contacts, no flag RD26-1
As above but with a self reset flag RD26-2

General applications

Auto-reclose

Single-shot repetitive scheme relay for single and three pole circuit breakers, normally used in conjunction with distance
protection. 79 Tau 100/200 range

Multi Shot DAR Schemes Tau 400 range

Schemes to the requirements of NGC Transmission Plant Standards using multi-element relays Tau 500 range

Multi-shot schemes, with individual sequence settings, integrated into OC, EF


and/or SEF microprocessor based protection Argus 4
Delta

Auxiliary A range of voltage operated attracted armature relays with hand, self or electrical
reset contacts, various flag and fixed time delay options.

AR series

Directional Numeric integrated with feeder protection relay

67 Argus 2
Check Numeric with check and system sync settings synchronising

25 Argus 7
Flag relays

Attracted armature relays with hand reset flag and self reset contacts FR111
With fixed time delay FR111T
With reverse operating flag for undervoltage applications AR121

Ferro-resonance Ferro-resonance detection with the system energised or de-energised

XR309

B34

Interposing control Control relays with a.c. rejection for use with pilot wires

52 XR105 XR105
XR106

Lockout relay Send relay with either 5kV or 15kV pilot insulation level

85 TEC

Intertripping

Receive relays with either 5kV or 15kV pilot insulation level and: 85
a) Surgeproof to 500V GF3 GF2 & GF4
b) Surgeproof to 5kV BD GF3

Neutral displacement

59
Numeric with programmable time delay Argus 8

Switching relays

Electrical reset relays for general switching 52 AR103


Switchgear position follower, 10 contacts, coils to EB2 specification TR901
Protection or Auto reclose IN/OUT to CEGB TDM 5/11 TR431
Protection unstabilising, to CEGB specification P11 TR512
25
ANSI Case Availability
Function Description Ref Modular Vedette Other

Test plugs

Modular test unit based upon a size R2 case 2 RMLG01


Modular system, multi-point test plug RMLB01
Modular system, single point test plug RMLB02

Time delay Electronic time delay with models for delay on energisation, delay on reset and delay on de-energisation

2 DDB

Trip relays High speed relays with a choice of burden and type of contact reset

86 TR

Trip Circuit supervision

Basic trip circuit supervision, e.g. BEBS S15 Scheme H4 27


Self reset flag XR250
Hand reset flag XR251

Full trip circuit supervision with the circuit breaker open or closed, can also
provide pre-close supervision, e.g. BEBS S15 Scheme H7 27
Self reset flag XR350
Hand reset flag XR351

D.C. supply supervision 27

Self reset flag XR152


Hand reset flag XR153

Rectifier protection

Overcurrent Short Circuit Numeric/microprocessor IDMT, normal inverse for class I rectifiers (light or general industrial duty) or very inverse
for class II rectifiers (heavy industrial or light traction duty)

51 Argus 1

Earth fault

Numeric/microprocessor IDMT, normal inverse for class I rectifiers (light or general industrial duty) or very inverse for class II
rectifiers (heavy industrial or light traction duty) 50/51 Argus 1
High impedance earth fault protection on traction transformers.
Solid state with high harmonic rejection ratio 67N Argus 1

Overload Numeric thermal overload

49 Rho 3

Capacitor bank protection

Overcurrent Numeric with selected DTL, NI, VI, EI, LTI characteristics. Two integral highset functions, IDMTL / DTL instantaneous or delayed
reset

50/51/87 Argus 1
Overload Numeric thermal overload

49 Rho 3
SERVICES

The following services are available by means of written quotation through our Customer Service Department.

Protection Setting studies System review

• Design Criteria and protection performance confirmed. • Design criteria and performance identified.
• Equipment withstand established • Solutions for inadequate systems.
• Full record of data settings, and performance • Report following serious incidents.

Benefits include: Benefits include:


Production of master protection guide for future references; Up to date record of the system, weakness identified; security
Confidence in capability of main plant. Assists with analysis following complies with good Health & Safety practice.
an incident.

Conjunctive Testing
Intelligent relay programming
• Either on site or in the Hamilton Laboratory
• Setting parameters optimised through experienced engineers. • Effects of harmonic distortion or power systems transients on
• Stored in software and hard copy. relay performance can be examined.
• Waveforms can be supplied
Benefits include:
A cost effective approach: Accuracy avoids need for re- Benefits include:
programming and re-testing. Confidence in relay performance: confidence in scheme
performance when carried out in the laboratory reduces site
commissioning and outage time.
Commissioning Support

• Highly skilled engineers


Training
• Test equipment with latest technology
• Test programmes prepared • Products and system design training
• Supervision for insurance certification • Application training
- standard courses
Benefits include: - customer specified/tailored
Optimisation of customer resource: Access to commissioning • On site or at Reyrolle with access to laboratory test facilities.
knowledge and high tech equipment to ensure a high degree of
security, Independent witness, Full test records produced. Benefits include:
Confidence to self manage during plant life; To carry out routine
testing and performance assessment following an incident
Design Specification

• Highly experienced engineers with knowledge in customs and


Service Contracts
practice, and also international standards.
• Optimum designs emphasising on achieving the best results • Maintenance and spares management

SERVICES
possible • Emergency support 24 hours a day, 365 days a year
• Clear specifications of design and alternative options • Design update with changes in design

Benefits include:
Optimum security of supply: Minimum plant outage following a fault;
damage limitations: latest technology: standards and experience Emergency Support
taken into account. Transmission distribution or generation plant power system
protection
• Standby resource for an immediate response
Consultancy
• Any protection and control problems
• Assistance with establishing design concepts • Backed by International technical resource
• Risk and Health and Safety Assessment • Support from office base or on site in minimum response time
• Insurance assessment
• Optimisation studies

Benefits include:
Optimisation of Customer resources: access to a complete power
system design team and a large pool of knowledge.

27
EQUIVALENTS GUIDE

Reyrolle/Alstom comparison table

ALSTOM TYPE REYROLLE TYPE ALSTOM TYPE REYROLLE TYPE

AUXILIARY AUXILIARY UNDERVOLTAGE/ UNDERVOLTAGE/


MVAA11 AR101 OVERVOLTAGE OVERVOLTAGE
MVAA14 AR103* MVAG23 VR123
MVAA11 AR111 MVTU13 B37
MVAA13 AR112 MVAG21 B68
MVAA11 AR131 KVFG Argus 8
MVAA13 AR141 P920
MVAA21 AR201 IDMTL IDMTL
MVAA21 AR211 KCGG122 Argus 1 (1P)
MVAA21 AR212 KCGG142 Argus 1 (3P)
TRIPPING TRIPPING KCGG142 Argus 1 (4P)
MVAJ11 TR112 KCEG112 Argus 2 (1P)
MVAJ13 TR121 KCEG142 Argus 2 (3P)
MVAJ14 TR131 KCEG142 Argus 2 (4P)
MVAJ15 TR141 KCGG + KVTR Argus 4
MVAJ21 TR212 KCEG + KVTR Argus 6
MVAJ23 TR221 P120 Argus 1 (IP)
MVAJ24 TR231 P121/P122 Argus 1 (4P)
MVAJ25 TR241 P123 Argus 4
MVAJ34 TR431 P125 Argus 2 (IP)
SUPERVISION SUPERVISION P126 Argus 2 (4P)
MVAW11 XR105 P127 Argus 6
MVAW21 XR205 P140 Delta
MVAX12 XR152 TRANSFORMER TRANSFORMER
MVAX21 XR250 KBCH120 Doubias-M (2W)
MVAX21 XR251 KBCH130 Doubias-M (3W)
MVAX31 XR350 P630
MVAX31 XR351 GENERATOR GENERATOR
MEASURING MEASURING LPGP111 Gamma 4
MCAG11 MR111 P340
MCAG12 MR112
FEEDER FEEDER
FOLLOWER FOLLOWER LFCB102 Microphase-FM
MCAA11 FR101 MHOR4 Solkor-RF/M/N
MCAA11 FR111
OPTIMHO Ohmega
MCAA21 FR211
LFZR
MCAA21 FR212
P400
TIME DELAYS TIME DELAYS
MVTT14 DDB1 MOTOR MOTOR
MVTT14 DDB5 MCHG Rho 3
MVTT15 DDB7 MOPN
MVTT15 DDB11 P220
MVTT15 DDB12
OTHERS OTHERS
UNDERVOLTAGE/ UNDERVOLTAGE/ MFAC14/34 or
OVERVOLTAGE 5B3
OVERVOLTAGE
MCAG14/34 DAD
MVAG15 VR115
KAVS100 Argus 7
MVAG16 VR116
MVAG17 VR117 MBCZ DRS-BB
MVAG21 VR121 KVTL IOTA
MVAG22 VR122 KAVR100/130/159 TAU500
EQUIVALENTS
LFAA TAU502/503
MMLG 2RMLG
GUIDE

*Note: AR103 does not have a cut-off contact in the operate coil.

51
DELIVERY GUIDE

Product line times

Relay Lead Time Guide for Products with standard ratings, settings and contacts

These are despatch dates from receipt of a full order to ex-works release for a UK mainland delivery.
For FOB delivery add 2 weeks to the printed lead time, for other types of delivery consult our Sales Office.

4 WEEKS 6 WEEKS 8 WEEKS 10 WEEKS 12 WEEKS 20 WEEKS


Alpha range B68 Delta BD Solkor Inverter DRS-BB
Argus range Sigma Duobias DAD
DDB Solkor-N Find GF
Reydisp Solkor-R/Rf Iota Gamma
Rho Solkor Supervision Microphase-FM TEC
2RMLG 5B3 MicroTAPP 2DAB
MSCDN
Ohmega 300/400
Solkor-M
SuperTAPP
Tau

DELIVERY
GUIDE

53

You might also like