You are on page 1of 2

www.sodeca.com Data in this report can change without notice v1.1.0.

0
TECHNICAL DATA REPORT
CJSRX-500-1.5-F-400
400C/2h belt-driven extraction units to work outside fire danger zones with
backward-curved impeller
400C/2h belt-driven extraction units with backward-curved impeller with electric motor,
pulley, belt kit and standardised protectors accordance with standard EN-294 and ISO-
13852
Fan:
- Steel sheet casing
- Impeller with backward-curved blades made from sheet steel
- Approval according to Standard EN-12101-3:2002, certificate no.: 0370-CPD-1578
- Pulley and belt kit and standardised protectors in accordance with standard EN-294 and
ISO-13852
Motor:
- Motors with IE-2 efficiency, except for motors with lower powers than 0.75 kW, single-
phase motors or two-speed motors
- Class F motors, with bearings, IP55 protection
- Three-phase 230/400V.-50Hz. (up to 5.5CV.) and 400/690V.-50Hz. (power over 5.5CV.)
- Max. air temperature to transport: -20C.+ 150C.
Finish:
- Anticorrosive galvanized sheet steel
On request:
- Special windings for different voltages
CHARACTERISTIC CURVE AND ACOUSTICS AT 1.2KG/M
Design Point
Q (m/h) 4850
Ps (Pa) 450
Service Point (SP)
Q (m/h) 4870.09
Ps (Pa) 453.74
Pd (Pa) 22.80
Pt (Pa) 476.53
Impeller (rpm) 1140
Max. Temp. (C) 150
Air Speed (m/s) 6.16
Efficiency (%) 71.81
Power (kW) * 0.90
(*) Power at shaft
TECHNICAL CHARACTERISTICS
Airflow maximum (m/h) 7330
Speed (rpm) 1140
Approx. weight (kg) 88

Max. Efficiency
Actual ErP 2013 ErP 2015
Efficiency 54.8% 42.0% 47.7%
Efficiency grade N 65.0 52.2 57.9
Measurement category C
Efficiency category Static
Specific ratio 1.01
Flowrate (m/h) 4093
Pressure (Pa) 513.67
Input power (kW) 1.07
Speed (rpm) 1140
Variable speed drive VSD not necessary
Data established at point of optimum efficiency
1/2
www.sodeca.com Data in this report can change without notice v1.1.0.0
TECHNICAL DATA REPORT
MOTOR DATA
Power installed (kW) 1.10
Hz/phases 50/3
Motor (rpm) 1400
Poles 4
Max. current (A) 400 V Y 2.32
Max. current (A) 230 V D 4.03
Motor protection IP55
Motor frame size 80
Data can change, please check motor plate

AVAILABLE ACCESSORIES
INT IAT CABLE
BOX
C2V AR RFT/RF
M
AET CENTRA
L CO

It must be checked that the accessory is suitable for the fan model
DIMENSIONS
A B B1 C D E E1 F F1 G1 G2 G3 H H1
1430 1100 60 730 515 103 83 45 315 456 624 579 413.5 585
H2 L K O V V1 X
415 644 350 15 897 817 1289
Dimensions without explicitly defined units are shown in millimeters (mm)
2/2