(ONE WAY) Simply supported / Cantilever (Type S/C) in ft. c
Short Span (Clear) 3.50 1.07 m Long Span (Clear) 40 12.19 m Live Load on the Slab (LL) 2.50 KN / sqm Comp.stess of concrete M - 15 (fck) 15.00 N / sqm Tensile stress of steel (fy) 415.00 N / sqm Unit wt of concrete 25.00 KN / cum Unit wt of floor finish 50 mm 24.00 KN / sqm Clear concrete cover 15.00 mm Bearing of slab 150.00 mm Overall depth 35.56 mm Provide Overall depth D 125.00 mm Dia of bars for short direction 8.00 mm Dia of bars for long direction 8.00 mm Effective Depth d 106.00 mm Loading on the slab Dead Load of the slab (DL) 3.13 KN / sqm Floor Finish 1.20 KN / sqm Other Load 0.20 KN / sqm Live Load on the slab 2.50 KN / sqm Total Load on the slab (TL) 7.03 KN / sqm Design Load = (Total Load x Load Factor i.e. 1.5) 10.54 KN / sqm Effective Span lx 1.17 m ly 12.30 m Ratio ly/lx 10.486 > 2 Effective Span = 1 + 0.15 = 1.22 m Calculated BM at mid span of slab as follows; For simply supported :- Mu = (w x l 2 )/8 = 10.54 x 1.22 x 1.22 / 8 = 1.95 KN-m/m For Cantilever :- Mu = (w x l 2 )/2 = 10.54 x 1.22 x 1.22 / 2 = 7.80 KN-m/m Effective depth of slab will now be fixed up on consideration of of flexural strength as well as control of deflection. Flexural strength consideration Maximum BM = 7.80 KN-m/m BM = 0.36 x fck x 0.48 (1-0.42 x 0.48) x 1000 d 2 = BM x 10 6 N-mm/m or 0.36 x 15 x 0.48 (1-0.42 x 0.48) x 1000 d 2 = 7800923.052 or d = 61 mm Adopt effective depth (d) = 96 mm Tension R/F for the positive BM along the short span is BM = 7.80 Ast = BM / 0.87 x fy (1-0.42 x 0.48) x d = 1950231 / 0.87 x 415 (1-0.42 x 0.48) x 96 = 70.5 mm2/m 8 mm dia 713 mm c/c Control of deflection Actual Span / effective depth ratio = 1217 / 96 = 12.68 pt = 100 Ast/bd = 100 x 70.5 / 1000 x 61 = 0.07 From Modification curve, Modification factor = 2 Basic value of span / effective depth ratio = 7 Therefore permitted value of span / effective depth ratio = 7 x 2 = 14 Actual S/d is < Permitted S/d Hence effective depth "d" should be OK Try an effective depth "d" = 106 mm Tension R/F for short span +BM is given by = 0.87 x fy x Ast (d - fy x Ast / (fck x 1000)) = 7.8 x 1000000 0.87 x 415 x 216.02 (106 - 415 x 216.02 / (15 x 1000)) = 7800923.052 7801231 7800923 Ast = 216.02 Actual Span / effective depth ratio = 1217 / 106 = 11.48 pt = 100 Ast/bd = 100 x 216.02 / 1000 x 106 = 0.204 From Modification curve, Modification factor = 1.6 Basic value of span / effective depth ratio = 7 Therefore permitted value of span / effective depth ratio = 7 x 1.6 = 11.20 Actual S/d is > Permitted S/d Hence effective depth "d" should be increase Adopt Overall thickness (D) = 125 mm Minimum R/F in slab = 0.12% of area of slab = 0.12 x D x 1000 / 100 = 150 mm2/m 8 mm dia 335 mm c/c Hence provide Main R/F Ast = 216.02 mm2/m i.e. 8 mm dia 8 mm dia 233 mm c/c Maximum Spacing (3d or 450mm) = 318 mm Hence provide Distribution R/F Ast = 150 mm2/m i.e. 8 mm dia 8 mm dia 335 mm c/c Maximum Spacing (5d or 450mm) = 450 mm OK SLAB DESIGN :- Temp Room Size :- 3.5 x 40 Ft. Thickness of Slab :- 125 mm Concrete Grade M-15 (fck 15 N/Sqm) Steel :- HYSD (fy 415 N/Sqm) Live Load :- 2.5 KN/Sqm Floor Finish + Other Load :- 1.2 + 0.2 KN/Sqm Moments (at bottom) Mid Span:- 1.95 KN-m/m Main R/F Ast = 216.02 mm2/m i.e. 10 mm dia 10 mm dia 364 mm c/c Maximum Spacing (3d or 450mm) = 375 mm Maximum R/F(Flexural Consideration) :- 70.47 mm2/m, 10 mm dia. 1114 C/C Distribution R/F Ast = 150 mm2/m i.e. 8 mm dia 8 mm dia 335 mm c/c Maximum Spacing (5d or 450mm) = 450 mm Calculated BM per unit width of slab are as follows; 241103554.xls.ms_office[Report] 3/9 8/12/2014(8:47 PM) SLAB DESIGN :- Frontside Bed Room Edges conditions :- (All four edges contineous) Room Size :- 12.5 x 13.25 Ft. Thickness of Slab :- 125 mm Concrete Grade M-15 (fck 15 N/Sqm) Steel :- HYSD (fy 415 N/Sqm) Live Load :- 3.5 KN/Sqm Floor Finish + Other Load :- 1.2 + 0.5 KN/Sqm Mx My For negative moments (at top) Support :- 6.69 6.13 KN-m/m For positive moments (at bottom) Mid Span:- 5.04 4.60 KN-m/m Maximum R/F(Flexural Consideration) :- 307.77 mm2/m, 8 mm dia. 162 C/C Short Span Top At support :- 183.52 mm2/m 8 mm dia. 270 mm c/c Bottom At Mid Span :- 136.65 mm2/m 8 mm dia. 300 mm c/c Long Span Top At support :- 182.61 mm2/m 8 mm dia. 270 mm c/c Bottom At Mid Span :- 135.04 mm2/m 8 mm dia. 294 mm c/c Minimum R/F :- 150.00 mm2/m 8 mm dia 335 mm c/c Maximum Spacing :- 294 mm Calculated BM per unit width of slab are as follows; Required Reinforcements & Spacing UP UP UP 8 mm dia. 6" c/c 8 mm dia. 7" c/c 8 mm dia. 9" c/c 241103554.xls.ms_office[1] 4/9 8/12/2014[8:47 PM] SLAB DESIGN :- Drawing Room Edges conditions :- (All four edges contineous) Room Size :- 14 x 15.5 Ft. Thickness of Slab :- 125 mm Concrete Grade M-15 (fck 15 N/Sqm) Steel :- HYSD (fy 415 N/Sqm) Live Load :- 3.5 KN/Sqm Floor Finish + Other Load :- 1.2 + 0.5 KN/Sqm Mx My For negative moments (at top) Support :- 8.90 7.64 KN-m/m For positive moments (at bottom) Mid Span:- 6.73 5.73 KN-m/m Maximum R/F(Flexural Consideration) :- 355.92 mm2/m, 10 mm dia. 221 C/C Short Span Top At support :- 251.36 mm2/m 10 mm dia. 300 mm c/c Bottom At Mid Span :- 186.64 mm2/m 10 mm dia. 300 mm c/c Long Span Top At support :- 239.40 mm2/m 10 mm dia. 285 mm c/c Bottom At Mid Span :- 176.06 mm2/m 10 mm dia. 285 mm c/c Minimum R/F :- 150.00 mm2/m 8 mm dia 335 mm c/c Maximum Spacing :- 285 mm Calculated BM per unit width of slab are as follows; Required Reinforcements & Spacing UP UP UP 10 mm dia. 7" c/c 10 mm dia. 8" c/c 241103554.xls.ms_office[[2] 5/9 8/12/2014[8:47 PM] SLAB DESIGN :- Backside Bed Room Edges conditions :- (Two short edges contineous) Room Size :- 15.5 x 17 Ft. Thickness of Slab :- 145 mm Concrete Grade M-15 (fck 15 N/Sqm) Steel :- HYSD (fy 415 N/Sqm) Live Load :- 3.5 KN/Sqm Floor Finish + Other Load :- 1.2 + 0.5 KN/Sqm Mx My For negative moments (at top) Support :- 0.00 14.01 KN-m/m For positive moments (at bottom) Mid Span:- 13.24 10.90 KN-m/m Maximum R/F(Flexural Consideration) :- 558 mm2/m, 10 mm dia. 141 C/C Short Span Top At support :- 0.00 mm2/m #DIV/0! Bottom At Mid Span :- 315.48 mm2/m 10 mm dia. 240 mm c/c Long Span Top At support :- 370.40 mm2/m 10 mm dia. 210 mm c/c Bottom At Mid Span :- 281.48 mm2/m 10 mm dia. 270 mm c/c Minimum R/F :- 174 mm2/m 8 mm dia 289 mm c/c Maximum Spacing :- 300 mm Calculated BM per unit width of slab are as follows; Required Reinforcements & Spacing UP UP UP 10 mm dia. 5" c/c 10 mm dia. 6" c/c 241103554.xls.ms_office[3] 6/9 8/12/2014[8:47 PM] SLAB DESIGN :- Study Room Edges conditions :- (One long edge discontineous) Room Size :- 9 x 10.5 Ft. Thickness of Slab :- 125 mm Concrete Grade M-15 (fck 15 N/Sqm) Steel :- HYSD (fy 415 N/Sqm) Live Load :- 3.5 KN/Sqm Floor Finish + Other Load :- 1.2 + 0.5 KN/Sqm Mx My For negative moments (at top) Support :- 4.67 3.75 KN-m/m For positive moments (at bottom) Mid Span:- 3.49 2.84 KN-m/m Maximum R/F(Flexural Consideration) :- 254.92 mm2/m, 8 mm dia. 197 C/C Short Span Top At support :- 126.06 mm2/m 8 mm dia. 300 mm c/c Bottom At Mid Span :- 93.45 mm2/m 8 mm dia. 300 mm c/c Long Span Top At support :- 109.39 mm2/m 8 mm dia. 294 mm c/c Bottom At Mid Span :- 82.13 mm2/m 8 mm dia. 294 mm c/c Minimum R/F :- 150.00 mm2/m 8 mm dia 335 mm c/c Maximum Spacing :- 294 mm Calculated BM per unit width of slab are as follows; Required Reinforcements & Spacing UP UP UP 8 mm dia. 7" c/c 8 mm dia. 7" c/c 241103554.xls.ms_office[4] 7/9 8/12/2014[8:47 PM] SLAB DESIGN :- Kitchen Edges conditions :- (One long & one short edge discontineous) Room Size :- 9 x 15.5 Ft. Thickness of Slab :- 125 mm Concrete Grade M-15 (fck 15 N/Sqm) Steel :- HYSD (fy 415 N/Sqm) Live Load :- 3.5 KN/Sqm Floor Finish + Other Load :- 1.2 + 0.5 KN/Sqm Mx My For negative moments (at top) Support :- 8.32 4.76 KN-m/m For positive moments (at bottom) Mid Span:- 6.23 3.55 KN-m/m Maximum R/F(Flexural Consideration) :- 341.01 mm2/m, 8 mm dia. 147 C/C Short Span Top At support :- 231.25 mm2/m 8 mm dia. 210 mm c/c Bottom At Mid Span :- 170.40 mm2/m 8 mm dia. 290 mm c/c Long Span Top At support :- 140.21 mm2/m 8 mm dia. 294 mm c/c Bottom At Mid Span :- 103.29 mm2/m 8 mm dia. 294 mm c/c Minimum R/F :- 150.00 mm2/m 8 mm dia 335 mm c/c Maximum Spacing :- 294 mm Calculated BM per unit width of slab are as follows; Required Reinforcements & Spacing UP UP UP 8 mm dia. 5" c/c 8 mm dia. 8" c/c 241103554.xls.ms_office[5] 8/9 8/12/2014[8:47 PM] fy = 120 fy =145 fy =190 fy =240 fy = 290 0 Modification factore for tension reinforcement 1.6 2.0 0.4 0.8 1.2 2.0 2.4 2.8 3.0 0.4 0.8 1.2 1.6