You are on page 1of 2

Project Specifications

INSPECTION AND HEAT TREATMENT SUMMARY


ATTACHMENT 'A'
LINE
CLASS
PC
INSP
CLASS
MATERIAL PWHT
RT UT MT PT CV BH VT
ACCEPTABLE WELDING
PROCESSES
NOTES
SEE PC STD AP-200-9.1
AND E-29-2.0 FOR DETAILS
PMI
PRODUCTION DESTRUCTIVE AND
NON-DESTRUCTIVE TESTING
A6CV
Arequipa, Peru
Cerro Verde Production Unit Expansion
Fluor Canada Ltd. - Sociedad Minera Cerro Verde S.A.A
REV
NONE ASME B31.3 Category D CARBON STEEL NONE NONE NONE NONE NONE NONE NONE 100% C1A
NONE *0% FOR CAT.D LINES PER
LDT
CARBON STEEL NONE 5%* NA 5%* NONE NONE NONE 100% C1B 0
NONE CARBON STEEL NONE 5% NONE 5% NONE NONE NONE 100% C1C
NONE CARBON STEEL NONE 5% NONE 5% NONE NONE NONE 100% C1D
NONE NFPA 13, 14, 24 CARBON STEEL NONE 5% NONE 5% NONE NONE NONE 100% C1F 0
NONE CARBON STEEL NONE 5% NONE 5% NONE NONE NONE 100% C1G
NONE *ASME B31.4 para 434.8.5
(3)
CARBON STEEL CTE
COATED
NONE 10%/100%NONE 10%/100%NONE NONE NONE 100% C1H 0
NONE ASME B31.3 Category D CARBON STEEL CTE
COATED
NONE NONE NONE NONE NONE NONE NONE 100% C1K
NONE *ASME B31.4 para 434.8.5
(3)
CARBON STEEL NONE 10%/100%NONE 10%/100%NONE NONE NONE 100% C1L 0
NONE *ASME B31.4 para 434.8.5
(3)
CARBON STEEL NONE 10%/100%NONE 10%/100%NONE NONE NONE 100% C1M 0
NONE NFPA 13, 14, 24 CARBON STEEL
LINED
NONE 5% NONE 5% NONE NONE NONE 100% C1P 0
NONE CARBON STEEL NONE 5% NONE 5% NONE NONE NONE 100% C2A
NONE *ASME B31.4 para 434.8.5
(3)
CARBON STEEL CTE
COATED
NONE 10%/100%NONE 10%/100%NONE NONE NONE 100% C2B 0
NONE *ASME B31.4 para 434.8.5
(3)
CARBON STEEL CTE
COATED
NONE 10%/100%NONE 10%/100%NONE NONE NONE 100% C2C 0
NONE *ASME B31.4 para 434.8.5
(3)
CARBON STEEL NONE 10%/100%NONE 10%/100%NONE NONE NONE 100% C2D 0
NONE *ASME B31.4 para 434.8.5
(3)
CARBON STEEL NONE 10%/100%NONE 10%/100%NONE NONE NONE 100% C2E 0
NONE CARBON STEEL CTE
COATED
NONE 5% NONE 5% NONE NONE NONE 100% C2G
NONE CARBON STEEL NONE 5% NONE 5% NONE NONE NONE 100% C2H
NONE ASME B31.3 Category D GALVANIZED STEEL NONE NONE NONE NONE NONE NONE NONE 100% G1A
NA RT/MT CS ONLY UT-TOFD PER CS-50-006 HDPE(SDR 7.3/DI
FTG)
NA 5% 20% 5% NA NA NA 100% H0A
NA RT/MT CS ONLY UT-TOFD PER CS-50-006 HDPE (SDR 9/DI FTG) NA 5% 20% 5% NA NA NA 100% H0B
NA RT/MT CS ONLY UT-TOFD PER CS-50-006 HDPE (SDR 11/DI
FTG)
NA 5% 20% 5% NA NA NA 100% H0C
RT - RADIOLOGY CV - CHARPY IMPACT
UT - ULTRASONIC BH - BRINELL
HARDINESS
MT - MAGNETIC PARTICLE VT - VISUAL
PT - LIQUID DYE PENETRANT PMI - POSITIVE MATE
DATE PRINTED: 01FEB13
PAGE: 1 OF 2
17:53:2 Search Specification: Line Class is not equal to SYSTEM and Line Class is
not equal to A0A and Line Class is not equal to S4A and Line Class is not
equal to T1A and Line Class is not equal to T1B and Line Class is not equal
to T1C and Line Class is not equal to T1D and Line Class is not equal to
T1K and Line Class is not equal to T1L and Line Class is not equal to T1M
and Line Class is not equal to T2A and Line Class is not equal to T2B and
MR-INSP-001
Document No. 240K-C2-SP-50-001
Revision 0
Attachment 5
Project Specifications
INSPECTION AND HEAT TREATMENT SUMMARY
ATTACHMENT 'A'
LINE
CLASS
PC
INSP
CLASS
MATERIAL PWHT
RT UT MT PT CV BH VT
ACCEPTABLE WELDING
PROCESSES
NOTES
SEE PC STD AP-200-9.1
AND E-29-2.0 FOR DETAILS
PMI
PRODUCTION DESTRUCTIVE AND
NON-DESTRUCTIVE TESTING
A6CV
Arequipa, Peru
Cerro Verde Production Unit Expansion
Fluor Canada Ltd. - Sociedad Minera Cerro Verde S.A.A
REV
NA RT/MT CS ONLY UT-TOFD PER CS-50-006 HDPE (SDR 17/DI
FTG)
NA 5% 20% 5% NA NA NA 100% H0D
NA RT/MT CS ONLY UT-TOFD PER CS-50-006 HDPE (SDR 21/DI
FTG)
NA 5% 20% 5% NA NA NA 100% H0E
NA UT-TOFD PER CS-50-006 HDPE (FM200/DI
FTG)
NA NA 20% NA NA NA NA 100% H0F
NA RT/MT CS ONLY UT-TOFD PER CS-50-006 HDPE (SDR 17) NA 5% 20% 5% NA NA NA 100% H0K
NA RT/MT CS ONLY UT-TOFD PER CS-50-006 HDPE (SDR 21) NA 5% 20% 5% NA NA NA 100% H0L
NA RT/MT CS ONLY UT-TOFD PER CS-50-006 HDPE (SDR 32) NA 5% 20% 5% NA NA NA 100% H0N
NA RT/MT CS ONLY UT-TOFD PER CS-50-006 HDPE (SDR 9) NA 5% 20% 5% NA NA NA 100% H0Q 0
NA PVC SDR 35 B&S NA NA NA NA NA NA NA 100% P0A
NONE *0% FOR CAT.D LINES PER
LDT
6 MM RUBBER LINED
CS
NONE 5%* NONE 5%* NONE NONE NONE 100% R1A 0
NONE *0% FOR CAT.D LINES PER
LDT
13 MM RUBBER
LINED CS
NONE 5%* NONE 5%* NONE NONE NONE 100% R1B 0
NONE *0% FOR CAT.D LINES PER
LDT
9.5 MM URETHANE
LINED CS
NONE 5%* NONE 5%* NONE NONE NONE 100% R1C 0
NONE *0% FOR CAT.D LINES PER
LDT
25MM RUBBER
LINED CS
NONE 5%* NONE 5%* NONE NONE NONE 100% R1D 0
NONE *0% FOR CAT.D LINE PER
LDT
304/304L SS NONE 5% NONE NA 5%* NONE NONE 100% S1A 0
NONE 304/304L SS NONE 5% NONE NA 5% NONE NONE 100% S1B
N/A GAUGE 100%
JOINT TESTER 100%
GRP N/A N/A N/A N/A N/A N/A N/A N/A T1N 0
N/A GAUGE 100%
JOINT TESTER 100%
GRP N/A N/A N/A N/A N/A N/A N/A N/A T1P 0
N/A GAUGE 100%
JOINT TESTER 100%
GRP N/A N/A N/A N/A N/A N/A N/A N/A T1Q 0
N/A GAUGE 100%
JOINT TESTER 100%
GRP N/A N/A N/A N/A N/A N/A N/A N/A T1R 0
RT - RADIOLOGY CV - CHARPY IMPACT
UT - ULTRASONIC BH - BRINELL
HARDINESS
MT - MAGNETIC PARTICLE VT - VISUAL
PT - LIQUID DYE PENETRANT PMI - POSITIVE MATE
DATE PRINTED: 01FEB13
PAGE: 2 OF 2
17:53:2 Search Specification: Line Class is not equal to SYSTEM and Line Class is
not equal to A0A and Line Class is not equal to S4A and Line Class is not
equal to T1A and Line Class is not equal to T1B and Line Class is not equal
to T1C and Line Class is not equal to T1D and Line Class is not equal to
T1K and Line Class is not equal to T1L and Line Class is not equal to T1M
and Line Class is not equal to T2A and Line Class is not equal to T2B and
MR-INSP-001
Document No. 240K-C2-SP-50-001
Revision 0
Attachment 5